Plan Review Details - Permit 05070873
Plan Review Stops For Permit 05070873
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-10 Cont ID  
Sent By rbrown Date 2006-06-10 Time 20:12 Rev Time 0.00
Received By rbrown Date 2006-06-10 Time 20:11 Sent To  
Notes
2006-06-10 00:00:00NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-25 Cont ID  
Sent By rbrown Date 2006-03-25 Time 12:01 Rev Time 0.00
Received By rbrown Date 2006-03-25 Time 12:01 Sent To  
Notes
2006-03-25 00:00:00BUILDING PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.IF THE RESPONSE TO THE
 OUTSTANDING ELECTRICAL PLAN REVIEW
 COMMENTS REQUIRES SUBMITTAL OF NEW
 SHEETS, PLEASE ENSURE THAT THE
 CERTIFICATE OF AUTHORIZATION NUMBER
 (6141) FOR YKA CONSULTING ENGINEERS INC
 IS ON THE TITLE BLOCK OF THE NEW SHEETS.
 (471.023 F.S.).THIS MAY BE ADDED BY
 HAND.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-07 Cont ID  
Sent By rbrown Date 2006-02-07 Time 09:31 Rev Time 0.00
Received By rbrown Date 2006-02-06 Time 19:28 Sent To  
Notes
2006-02-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 8/26/05:
  
 2) FBC 424.1.1SIZING.IT IS NOTED
 THAT THE 21'-6" PLAN DIMENSION, TO MATCH
 THAT ON THE LOGITUDINAL POOL SECTION (ON
 SHEET 3), HAS BEEN HANDWRITTEN ON SHEET
 1.CHANGES TO THE SIGNED AND SEALED
 PLANS ARE ONLY ACCEPTABLE IF EACH CHANGE
 IS SIGNED AND DATED BY THE ENGINEER OF
 RECORD.
  
 IT IS NOTED THAT THE COMMENT 1 HAS BEEN
 ADDRESSED ALREADY.IF THE RESPONSE TO
 COMMENT 2 REQUIRES NEW SHEETS, PLEASE
 ENSURE THAT THE CERTIFICATE OF
 AUTHORIZATION NUMBER IS ON THE TITLE
 BLOCK OF THE NEW SHEETS.COMMENT 1 IS
 REPEATED BELOW ONLY FOR EASE OF
 REFERENCE:
  
 1) 471.023 F.S.ADD THE CERTIFICATE OF
 AUTHORIZATION NUMBER (6141) FOR YKA
 CONSULTING ENGINEER'S INC TO EACH SHEET.
 THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-26 Cont ID  
Sent By rbrown Date 2005-08-26 Time 12:55 Rev Time 0.00
Received By rbrown Date 2005-08-26 Time 12:55 Sent To  
Notes
2005-08-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 471.023 F.S.ADD THE CERTIFICATE OF
 AUTHORIZATION NUMBER (6141) FOR YKA
 CONSULTING ENGINEER'S INC TO EACH SHEET.
 THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 2) FBC 424.1.1SIZING.AMEND THE
 LOGITUDINAL POOL SECTION ON SHEET 3 TO
 SHOW DIMENSIONS THAT MATCH THE PLAN VIEW
 ON SHEET 1.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2006-06-01 Time 18:22 Sent To  
Notes
2006-06-02 00:00:00REDLINE DPLANS. THE NEW WP POOL PANEL AS
 SHOWN ON PLANS IS THE EIXISTING POOL
 PANEL PROVIDED UNDER MAIN BUILDING
 PERMIT AND SCOPE OF WORK.
 OCP, AWG ETC TO CORRELATE AND MATCH
 M,AIN BUILDING ELECTRICAL PLANS.
2006-06-01 00:00:00ON HOLD, FEES NOT PAID AS REQUIRED
 UNDER FS 553.80 WHEN RESUBMITTED .
 CALLED DON, FROM VAN KIRK AND WILL COME
 UP TO PAY ON 6/2/06

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2006-05-10 Cont ID  
Sent By btrobaug Date 2006-05-10 Time 10:12 Rev Time 1.00
Received By btrobaug Date 2006-05-10 Time 06:46 Sent To  
Notes
2006-05-10 00:00:00 
 I WILL DEFER THIS REVIEW, COMMENTS DO
 NOT APPEAR TO BE ADDRESSED REGARDING THE
 PANEL SHOWN, VOLTAGE/AMPERAGE RATINGS,
 FEEDER AND OCP INFORMATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-14 Cont ID  
Sent By dpalmer Date 2006-03-14 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2006-03-14 Time 18:15 Sent To  
Notes
2006-03-14 00:00:00********** UNSAT 3RD REVIEW************
  
 1)NOTE: PLEASE SEE COMMENTS FROM TWO
 PREVIOUS REVIEWS WHICH HAVE STILL NOT
 BEEN ADDDRESS FOR CODE COMPLIANCE AND
 PER REQUIREMENTS OF FLORIDA STATUES.
 PLEASE SEE NOTE #1 FROM EACH OF THE
 PREVIOUS TWO REVIEWS.
 THE PLANS SUBMITTED ARE THE EXACT SAME
 PLANS.
 A) ELECTRICAL INFORMATION AS REQUESTED
 TO BE ON THESE PLANS ARE IS NOT DONE.
 B)THE PLANS DO NOT CORRELATE AND STILL
 SHOW TWO COMPLETELY DIFFERENT SIZE
 POOLS.
 C)PLANS NOW HAVE SOME AREAS CONTAINING A
 HANDWRITTEN CLOUDED AREA, WITH SOME SORT
 OF DATE AND INITIALS WHICH DO NOT MATCH
 WITH THE ENGINEER OF RECORD.
 PLEASE SEE PREVIOUS REVIEWS AS IT WAS
 REQUESTED AND IS REQUIRED FOR THESE
 PLANS TO BE CORRECTED, REVISED,
 RE-PRINTED, AND SIGNED,DATED AND SEALED
 BY THE ENGINEER OF RECORD.
 D) PLANS FOR BASE BLDG ARE STILL BEING
 SUBMITTED , WHEN PREVIOUS NOTES
 MENTIONED THIS WAS NOT NEEDED, INFACT
 MANY OF THE ITEMS ON THESE PHOTO-COPIED
 PLANS DO NOT HAVE ANY CORRELATION WITH
 THE PROPOSED WORK FOR POOL.
  
 2)NOTE: PLEASE SEE PREVIOUS REVIEW GAVE
 NOTICE TOFLORIDA STATUES 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS FOR
 THREE OR MORE REVIEWS.
 PLEASE KNOW; A 4X FEE IS NOW ASSESSED
 FOR THE PLAN REVIEW PORTION OF THE BASE
 PERMIT FEE AND THE AMOUNT OF $1,665.60
 IS NOW ASSESSED AND SHALL BE PAID BEFORE
 PLANS ARE RE-SUBMITTED. PLEASE ADDRESS
 ALL COMMENTS, AS THE FEE CAN BE ASSESSED
 EACH TIME AFTER FOR NO COMPLIANCE.
  
 ** PLEASE KNOW, ONE SET OF PLANS ARE NOW
 RETAINED AND MAY BE TURNED OVEER TO THE
 STATE OF FLORIDA'S BOARD OF PROFESSIONAL
 ENGINEERS FOR REVIEW OF NON-COMPLIANT
 PLANS. PLEASE KNOW, THESE MAY ALSO BE
 SUBMITTED TO THE STATE'S LEGAL COUNSEL
 TO THE BOARD FOR FS 417.025.
  
 PLEASE COMPLETE ALL, AND RESUBMIT ONCE
 ALL REVIEWS ARE DONE. IT IS STRONGLY
 RECOMMENDED THAT A MEETING BE HELD TO GO
 OVER ANY QUESTIONS OR COMMENTS TO HELP
 IN EXPEDITING THIS PROJECT, MOVE TOWARDS
 A PERMIT STATUS AND AVOID ANY FURTHER
 DELAY'S IN THE MAIN BUIDLING PROJECT.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 17:52 Rev Time 0.33
Received By dpalmer Date 2005-10-08 Time 17:47 Sent To  
Notes
2005-10-08 00:00:00************ UNSAT 2ND REVIEW ********
  
 PLEASE SEE SAME COMMENTS FROM PREVIOUS
 REVIEW AND SEE COMMENTS BELOW.
  
 1)NOTE: PLEASE SEE NOTE #1 FROM FIRST
 REVIEW, MOST OF THESE ITEMS REQUESTED
 WERE NOT DONE.
 SOME OF THE OTHERS WERE HAND DRAWN ON
 PLANS WHICH ARE SIGNED,DATED AND SEALED
 BY AN ENGINEER.THIS IS NOT PERMITTED
 UNDER FS 471.025
 PLEASE HAVE ENGINEER OF RECORD MAKE ALL
 CHANGES AND CORRECTIONS WITH INFORMATION
 NEEDED. PLEASE HAVE ENGINEER RE-PRINT
 SHEETS AND , SIGN, DATEAND SEAL ALL
 SHEETS AS PREVIOUSLY MENTIONED.
  
 2)NOTE: IF THERE IS NO "NIGHT TIME"
 AFTER DUSK" SWIMMING, THIS WILL BE
 REQUIRED TO BE REVISED BY ENGINEER.
 PLANS WILL STILL NEED TO BE STAMPED BY
 THE PALM BEACH COUNTY HEALTH DEPT AFTER
 SUCH CORRECTIONS/CHANGES ARE MADE TO
 PLANS.
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND PLANS BEING REVIEW WITH
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 *** PLEASE SEE PLANS SUBMITTED WHICH ARE
 COPIES OF PLANS FOR MAIN BLDG, NEED NOT
 BE SUBMITTED FOR ELECTRICAL.
 PLEASE SEE NUMEROUS SHEETS SUBMITTED
 WHICH HAVE NOTHING TO DO WITH ELECTRCAL
 FOR POOL. *CONDO UNITS ETC??
  
 NO REVIEW FOR CODE COMPLIANCE CAN BE
 DONE AT THIS TIME FOR CHANGESWHICH
 STILL NEED TO BE DONE PER ABOVE AND
 PREVIOUS REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-07-28 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2005-07-28 Time 15:31 Sent To  
Notes
2005-07-28 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT PLANS WHICH
 CORRELATE FOR POOL BEING INSTALLED.
 PLEASE SEE PLANS ON ONE SHEETS SHOWS ONE
 SIZE AND OTHER SHEETS SHOWS A POOL LESS
 THAN HALF THE SIZE?
 PLEASE CORRRELATE ALL LIGHTING FIXTURES,
 POOL , SPA PUMP ETS.
 PLEASE INCLUDE THE WIRING DIAGRAM FOR
 ALL ELECTRICAL EQUIPMENT BEING
 INSTALLED.
 PLEASE SEE WIRING DIAGRAMS SHOWS A NEW
 PANEL BEING INSTALLED, HOWEVER NO
 CONDUCTORS,CONDUIT ETC TO WHERE PANEL IS
 BEING FED, WHAT SIZE, OCP ETC.
 215.5
  
 2)NOTE: PLEASE SUBMIT A COMPLETE SIGNED,
 SEALED, DATED PHOTOMETRIC STUDY FOR POOL
 AREA.
 PLEASE BE SURE PHOTOMETRICS ARE STAMPED
 BY THE PALM BEACH COUNTY HEALTH DEPT.FOR
 ANY "NIGHT-TIME" AFTER DUSK" SWIMMING.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 14:11 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:11 Sent To  
Notes
2006-06-10 00:00:00SENT TO PAUL SCHMITZ DESK
  
  
2006-05-24 00:00:00TO "COMM" BD#49
2006-05-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 12:44 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 12:44 Sent To  
Notes
2006-03-13 00:00:00TO "COMM" BD#17
2006-02-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 16:07 Sent To B
Notes
2005-11-17 00:00:00TO "RBROWN" DESK/FROM "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-22 Cont ID  
Sent By adarroug Date 2005-09-22 Time 09:32 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 09:32 Sent To  
Notes
2005-09-29 00:00:00TO "COMM" BD#63
2005-09-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-26 Cont ID  
Sent By rbrown Date 2005-08-26 Time 13:33 Rev Time 0.00
Received By rbrown Date 2005-07-22 Time 13:09 Sent To  
Notes
2005-07-25 00:00:00TO "COMM" BD#22
2005-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-06-12 Cont ID  
Sent By pschmitz Date 2006-06-12 Time 09:21 Rev Time 0.00
Received By pschmitz Date 2006-06-12 Time 09:20 Sent To  
Notes
2006-06-12 00:00:00RE-STAMP
 PROVISO: OVER FLOW TO STORM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-22 Cont ID  
Sent By pschmitz Date 2005-10-22 Time 11:34 Rev Time 0.00
Received By pschmitz Date 2005-10-22 Time 11:34 Sent To  
Notes
2005-10-22 00:00:00PROVISO:
 PASS PENDING, OTHER PLAN REVIEWERS
 COMMENTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By kstevens Date 2005-08-24 Time 07:27 Rev Time 0.55
Received By kstevens Date 2005-08-24 Time 07:27 Sent To  
Notes
2005-08-24 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. POOL LAYOUT ON SHEET 1 OF 5 SHOWS
 POOL TO BE 50' BY 20' BUT LONGITUDINAL
 POOL SECTION ON SHT 3 OF 5 INDICATES A
 MEASUREMENT OF 21'6". PLEASE CLARIFY.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]