Plan Review Details - Permit 05070853
Plan Review Stops For Permit 05070853
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-09 Cont ID  
Sent By jwitmer Date 2005-11-09 Time 11:03 Rev Time 0.44
Received By jwitmer Date 2005-11-09 Time 11:03 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-28 Cont ID  
Sent By jwitmer Date 2005-09-28 Time 13:19 Rev Time 0.55
Received By jwitmer Date 2005-09-28 Time 13:19 Sent To PC
Notes
2005-09-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070853
 ADD: 7327 HORIZON DR
 CONT: DANIEL ELECTRIC
 TEL: (561)718-5324
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) ENGINEERING COPIED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) REMOVE ALL PAPERWORK THAT IS NOT
 REQUIRED FOR THIS PERMIT, MAKE SETS OF
 PLANS!!!!!!!!!!!
  
 4)NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 08:46 Rev Time 0.33
Received By jwitmer Date 2005-08-13 Time 08:46 Sent To P
Notes
2005-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070853
 ADD: 7327 HORIZON DR
 CONT: DANIEL ELECTRIC
 TEL: (561)718-5324
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) ENGINEERING COPIED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-11-08 Cont ID  
Sent By btrobaug Date 2005-11-08 Time 06:35 Rev Time 0.25
Received By btrobaug Date 2005-11-08 Time 06:31 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By btrobaug Date 2005-09-22 Time 13:19 Rev Time 0.50
Received By btrobaug Date 2005-09-22 Time 12:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By btrobaug Date 2005-08-03 Time 13:40 Rev Time 0.50
Received By btrobaug Date 2005-08-03 Time 12:55 Sent To M
Notes
2005-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PUT THE GEC SYSTEM ON THE
 RISER PER 250.53.
  
 2} INDICATE THE EQUIPMENT GROUND TO THE
 GENERATOR PER 250.122.
  
 3} PLEASE NOTE THAT A DISCONNECT IS
 REQUIRED ON THE BUILDING PER 225.31,
 GROUPED PER 230.71. THE ATS MUST BE
 SERVICE RATED PER 225.36 TO COMPLY WITH
 THIS REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 08:52 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 08:52 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 08:58 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 08:58 Sent To E
Notes
2005-09-20 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 16:05 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 16:05 Sent To Z
Notes
2005-09-12 00:00:00TO "ZONING" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 10:23 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 10:23 Sent To E
Notes
2005-08-01 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 08:50 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 13:19 Sent To  
Notes
2005-07-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-03 Cont ID  
Sent By rregueir Date 2005-08-03 Time 19:30 Rev Time 0.00
Received By rregueir Date 2005-08-03 Time 19:30 Sent To P
Notes
2005-08-03 00:00:00-----------------PROVISO----------------
 ----------------PROVISO-----------------
  
 LOCATION OF GENERATOR EXHAUST
 TERMINATION SHALL COMPLY WITH THE
 REQUIREMENTS OF FBC,M 804.3
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 07:52 Rev Time 0.25
Received By jleech Date 2005-08-04 Time 07:52 Sent To B
Notes
2005-08-04 00:00:00NAT.GAS PERMIT REQUIRED BEFORE FINAL
 INSPECTION.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-19 Cont ID  
Sent By mmclean Date 2005-09-19 Time 13:57 Rev Time 0.00
Received By mmclean Date 2005-09-19 Time 13:57 Sent To I
Notes
2005-09-19 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-29 Cont ID  
Sent By mmclean Date 2005-07-29 Time 18:03 Rev Time 0.00
Received By mmclean Date 2005-07-29 Time 18:03 Sent To I
Notes
2005-07-29 00:00:00DENIED,
 1. MUST SHOW THE LOCATION OF GENERATOR
 ON 2 COPY OF SURVEYS, WITH DIMENSION
 (DISTANCE FROM THE STRUCTURE AND
 PROPERTY LINE)
 2. NEED TO PROVIDE HOA APPROVAL & SIGN
 OFF ON THE PLANS FOR GENERATOR.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720