Plan Review Stops For Permit 05070853 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-11-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-11-09 |
Time |
11:03 |
Rev Time |
0.44 |
Received By |
jwitmer |
Date |
2005-11-09 |
Time |
11:03 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-09-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-09-28 |
Time |
13:19 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2005-09-28 |
Time |
13:19 |
Sent To |
PC |
|
Notes |
2005-09-28 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05070853 | | ADD: 7327 HORIZON DR | | CONT: DANIEL ELECTRIC | | TEL: (561)718-5324 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | | | 2) ENGINEERING COPIED. | | PLANS, SPECIFICATIONS,REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | 3) REMOVE ALL PAPERWORK THAT IS NOT | | REQUIRED FOR THIS PERMIT, MAKE SETS OF | | PLANS!!!!!!!!!!! | | | | 4)NOTE: | | CHAPTER 553.80(2)(B) FLORIDA STATUTES | | STATES THAT A LOCAL GOVERNMENT SHALL | | IMPOSE A FEE OF FOUR TIMES THE FEE FOR | | PLAN REVIEW, IF PLANS ARE REJECTED THREE | | OR MORE TIMES FOR REPEATED FAILURE TO | | CORRECT A CODE VIOLATION. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-08-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-08-13 |
Time |
08:46 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2005-08-13 |
Time |
08:46 |
Sent To |
P |
|
Notes |
2005-08-13 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05070853 | | ADD: 7327 HORIZON DR | | CONT: DANIEL ELECTRIC | | TEL: (561)718-5324 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | | | 2) ENGINEERING COPIED. | | PLANS, SPECIFICATIONS,REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2005-11-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-11-08 |
Time |
06:35 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2005-11-08 |
Time |
06:31 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-09-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-09-22 |
Time |
13:19 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-09-22 |
Time |
12:58 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-08-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-08-03 |
Time |
13:40 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-08-03 |
Time |
12:55 |
Sent To |
M |
|
Notes |
2005-08-03 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PUT THE GEC SYSTEM ON THE | | RISER PER 250.53. | | | | 2} INDICATE THE EQUIPMENT GROUND TO THE | | GENERATOR PER 250.122. | | | | 3} PLEASE NOTE THAT A DISCONNECT IS | | REQUIRED ON THE BUILDING PER 225.31, | | GROUPED PER 230.71. THE ATS MUST BE | | SERVICE RATED PER 225.36 TO COMPLY WITH | | THIS REQUIREMENT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-10-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-17 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-17 |
Time |
08:52 |
Sent To |
E |
|
Notes |
2005-10-17 00:00:00 | TO "E" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-20 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-20 |
Time |
08:58 |
Sent To |
E |
|
Notes |
2005-09-20 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-09-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-12 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-12 |
Time |
16:05 |
Sent To |
Z |
|
Notes |
2005-09-12 00:00:00 | TO "ZONING" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-08-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-01 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-01 |
Time |
10:23 |
Sent To |
E |
|
Notes |
2005-08-01 00:00:00 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-08-13 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-21 |
Time |
13:19 |
Sent To |
|
|
Notes |
2005-07-21 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-08-03 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2005-08-03 |
Time |
19:30 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2005-08-03 |
Time |
19:30 |
Sent To |
P |
|
Notes |
2005-08-03 00:00:00 | -----------------PROVISO---------------- | | ----------------PROVISO----------------- | | | | LOCATION OF GENERATOR EXHAUST | | TERMINATION SHALL COMPLY WITH THE | | REQUIREMENTS OF FBC,M 804.3 | | | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2005-08-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-08-04 |
Time |
07:52 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-08-04 |
Time |
07:52 |
Sent To |
B |
|
Notes |
2005-08-04 00:00:00 | NAT.GAS PERMIT REQUIRED BEFORE FINAL | | INSPECTION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-09-19 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-09-19 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-09-19 |
Time |
13:57 |
Sent To |
I |
|
Notes |
2005-09-19 00:00:00 | GENERATOR CAN ONLY ENCROACH 4FT INTO | | SETBACK. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-07-29 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-07-29 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-07-29 |
Time |
18:03 |
Sent To |
I |
|
Notes |
2005-07-29 00:00:00 | DENIED, | | 1. MUST SHOW THE LOCATION OF GENERATOR | | ON 2 COPY OF SURVEYS, WITH DIMENSION | | (DISTANCE FROM THE STRUCTURE AND | | PROPERTY LINE) | | 2. NEED TO PROVIDE HOA APPROVAL & SIGN | | OFF ON THE PLANS FOR GENERATOR. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|