Plan Review Details - Permit 05070837
Plan Review Stops For Permit 05070837
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-19 Cont ID  
Sent By jwitmer Date 2006-01-19 Time 07:15 Rev Time 1.00
Received By jwitmer Date 2006-01-19 Time 07:15 Sent To PC
Notes
2006-01-19 00:00:00BUILDING PROVISO:
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A "A5"
 FLOOD ZONE MINIMUM ELEVATION IS 7'-6".
 ***NOTICE THE FLOOD ELEVATION
 CERTIFICATE IS CERTIFYING THE ELEVATION
 OF THE GENERATOR SLAB. THE SURVEYOR CAN
 NOT CERTIFY SOMETHING THAT IS NOT THERE.
 ALSO NOTE THAT THE MINIMUM FLOOD
 ELEVATION FOR THE CITY IS 7'-6" FOR A
 "A5" FLOOD ZONE. THIS CERTIFICATE IS
 DUE AFTER THE SLAB IS POURED AND THE
 SURVEYOR CAN TAKE THE ACTUAL FINISH
 ELEVATION OF THE SLAB. DUE BEFORE FINAL
 INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-14 Cont ID  
Sent By jwitmer Date 2005-11-14 Time 08:21 Rev Time 0.55
Received By jwitmer Date 2005-11-14 Time 07:56 Sent To PC
Notes
2005-11-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070837
 ADD: 1801 S FLAGLER DR
 CONT: SULLIVAN
 TEL: (561)588-5886
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.THE
 NOC WAS RECORDED OVER 90 DAYS BEFORE
 COMMENCEMENT OF WORK, RQUIRING A
 RE-RECORDING OF NOTICE OF COMMENCEMENT.
 SEE 713.13(2)
  
 2)PROVISO:PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A "A5"
 FLOOD ZONE MINIMUM ELEVATION IS 7'-6".
 ***NOTICE THE FLOOD ELEVATION
 CERTIFICATE IS CERTIFYING THE ELEVATION
 OF THE GENERATOR SLAB. THE SURVEYOR CAN
 NOT CERTIFY SOMETHING THAT IS NOT THERE.
 ALSO NOTE THAT THE MINIMUM FLOOD
 ELEVATION FOR THE CITY IS 7'-6" FOR A
 "A5" FLOOD ZONE. THIS CERTIFICATE IS
 DUE AFTER THE SLAB IS POURED AND THE
 SURVEYOR CAN TAKE THE ACTUAL FINISH
 ELEVATION OF THE SLAB. DUE BEFORE FINAL
 INSPECTION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 09:49 Rev Time 0.33
Received By jwitmer Date 2005-08-28 Time 09:36 Sent To PC
Notes
2005-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070837
 ADD: 1801 S FLAGLER DR
 CONT: SULLIVAN
 TEL: (561)588-5886
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A "A5"
 FLOOD ZONE MINIMUM ELEVATION IS 7'-6".
  
 3) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-07 Cont ID  
Sent By dpalmer Date 2005-10-07 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2005-10-07 Time 15:17 Sent To  
Notes
2005-10-07 00:00:002ND SET OF SUBMITTIALS STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-29 Cont ID  
Sent By dpalmer Date 2005-09-29 Time 19:26 Rev Time 1.00
Received By dpalmer Date 2005-09-29 Time 19:07 Sent To  
Notes
2005-09-29 00:00:00IN "F" STATUS ONLY AWAITING 2ND SET OF
 SUBMITTALS.
 CALLED CONTRACTOR FOR 2ND SET, WILL
 BRING IN.
 SEE DV PALMER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 18:48 Rev Time 2.25
Received By dpalmer Date 2005-08-03 Time 18:47 Sent To  
Notes
2005-08-03 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE SEE FIRE PUMP INFORMATION
 IS CURRENTLY BEING REVIEWED UNDER
 GENERATOR PERMIT, HOWEVER FIRE PUMP WILL
 BE REQUIRED TO BE PERMITTED SEPARATELY.
 PLEASE SEE THIS MAY BE SUBMITTED ALONG
 WITH GENERATOR PERMIT SO IT MAY BE
 REVIEWED AND PERMITTED AT THE SAME TIME.
 PLANS, SPECS WILL BE REQUIRED FOR EACH
 AS EACH WILL BE FILED UNDER SEPRATE
 FILES.
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR, ATS,
 FIRE PUMP, FIRE PUMP CONTROLLER.
 PLEASE SEE OTHER COMMENTS FOR FPC, AS
 SOME INFORMATION CAN NOT VERIFIED AT
 THIS TIME.
 215.5
  
 3)NOTE: PLEASE SEE CONDUCTORS FROM FPL,
 GENERATOR TO FIRE PUMP, FIRE PUMP CONT,
 SHALL BE BASED ON 125%.
 PLEASE SEE 695.6(C)(2) ETC.
 PLEASE SEE PLANS INDICATE EXSITING
 "NAMEPLATE @ 100HP, 250 FLA'S. THIS IS
 ONLY A NOTE FOR VERIFICATION. NO
 CORRECTION NEEDED.
  
 4)NOTE: PLEASE SEE SPECS/CUT SHEETS FOR
 FPC WERE SUBMITTED, HOWEVER PLEASE NOTE
 THE MANUAL MEANS OF DISCONNECT LOCATED
 ON OUTSIDE OF EQUIPMENT, RATED FOR THE
 LAOD SERVED SHALL BE PART OF THE FPC.
 PLEASE SEE 230.76,230.79,NFPA-20 CHAPTER
 7-4.
 5)NOTE:PLEASESEE THE LOCATION OF FIRE
 PUMP CONTROLLER SHALL BE ARRANGED TO
 PREVENT ANY DAMAGE TO FPC EQUIPMENT IN
 THE EVENT OF FIRE/EXPLOSION ETC.
 PLEASE KNOW,IT IS KNOWN THIS IS AN
 EXSITING ROOM AND THERE ARE SOME
 EXISTING CONDITIONS WHICH CAN NOT BE
 AVOIDED. HOWEVER,A STEEL REINFORCED
 CONCRETE WALL WILL BE REQUIRED TO HELP
 IN SHIELDING ANY SUCH FIRE /EXPLOSION
 FROM MAIN SERVICE EQUIPMENT.
 PLEASE SEE 695.3, NFPA-20 6-2.1.ETC
  
 6)NOTE: PLEASE SEE THE LOCATION OF FIRE
 PUMP CONTROLLER SHALL BE SUCH THE
 LEAKING OF ANY WATERFROM FIRE PUMP ,
 FIRE SPRINKLERS ETC WILL NOT AFFECT THE
 FPC, PLEASE SEE NFPA-20 7-2,7-3.3.1, FOR
 ENCLOSURE TYPE ETC.
 PLEASE SEE NOTE ON PLANS MENTIONS FOR
 FEEDERS FROM GEN TO ENTER BLDG AS LOW AS
 POSSIBLE INTO REAR OF FIRE PUMP
 CONTROLLER, HOWEVER PLEASE SEE
 7-2.2,695.12, WHICH REQUIRES FPC TO BE
 MOUNTED A MIN OF 12" ABOVE FLR.
  
 7)NOTE: PLEASE PROVIDE NOTE FOR SIGNAGE
 FOR ALL ELECTRICAL EQUIPMENT.
 695.4B3,4 ETC.
  
 8)NOTE: PLEASE SEE PROTECTIVE BOLLARDS
 WILL BE REQUIRED OUTSIDE TO PROTECT GEN
 ENCLOSURE FROM PARKING LOT AREA.
 PLEASE SEE ANY ZONING COMMENTS.
  
 9)NOTE: PLEASE SEE PLANS MENTIONS PIPING
 IN ROOM SHALL BE EMT, PLEASE SEE
 695.6(2)(E).
  
 10)NOTE: PLEASE SEE 701.11(B)(2)(3) FOR
 SOURCES OF FUEL.
 PLEASE SEE IT IS KNOWNTO OUR OFFICE
 THE LOCAL UTILITY COMAPNY SUPPLYING
 NATURAL GAS SEEMS TO BE AT OVER 500%
 CAPACITY. PLEASE SEE AN ALTERANTE FUEL
 SOURCE WILL BE REQUIRED FOR MIN REQUIRED
 RUN TIME.
  
 11)NOTE: PLEASE SEE SITE PLAN / SURVEY
 WILL BE REQUIRED TO INDICATE THE BASE
 FLOOD ELEVATION (BFE). GEN SLAB SHALL BE
 A MIN OF 6" ABOVE BFE. PLEASE SEE BLDG
 REVIEW COMMENTS.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 BOLT/TIE DOWN CONNECTIONS REQUIRED.
  
 12)NOTE: PLEASE SEE FBC LOCAL
 ADMINISTRATIVE SECTION 104.6.5, PERMIT
 VALUATION IS BASED ON ALL LABOR AND
 MATERIALS, EVEN IF EQUIPMENT IS OWNER
 SUPPLIED. PLEASE ADJUST.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By mwennerg Date 2005-09-30 Time 10:53 Rev Time 0.00
Received By mwennerg Date 2005-09-30 Time 10:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mwennerg Date 2005-08-23 Time 12:47 Rev Time 0.00
Received By mwennerg Date 2005-08-23 Time 12:47 Sent To  
Notes
2005-08-23 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT MANUFACTURER SPEC
 SHEETS ARE REQUIRED FOR GENERATOR AND
 ASSOCIATED EQUIPMENT.
  
 2) PLEASE PROVIDE A MEANS OF PROTECTING
 THE GENERATOR AGAINST MECHANICAL DAMAGE.
  
 3) GENERATOR TO COMPLY WITH NFPA 110 AND
 OTHER APPLICABLE CODES.
  
 4) PLEASE SEE ELECTRICAL REVIEW COMMENT
 REGARDING SEPARATE SHOP DRAWING AND
 PERMIT WITH SHOP CALCS FOR FIRE PUMP.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-05-05 Cont ID  
Sent By pschmitz Date 2006-05-05 Time 07:38 Rev Time 0.00
Received By pschmitz Date 2006-05-05 Time 07:39 Sent To  
Notes
2006-05-05 00:00:00REVISION

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 09:20 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 09:20 Sent To PC
Notes
2006-04-29 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
  
 REVISIONUNSAT
  
 REVISION NOT DRAWN AS BUILT
  
 END OF COMMENTS QUSTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 11:12 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 11:12 Sent To G
Notes
2006-05-03 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 14:42 Sent To  
Notes
2006-01-18 00:00:00GIVEN TO MICHELLE MCLEAN FOR REVIEW/
 DISCUSSION WITH ANGELLA JONES-VANN.
  
  
2005-12-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 09:14 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 09:14 Sent To  
Notes
2005-09-29 00:00:00TO "COMM" BD#6
2005-09-20 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-29 Cont ID  
Sent By mmclean Date 2005-08-29 Time 15:50 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 16:21 Sent To  
Notes
2005-07-22 00:00:00TO "COMM" BD#61
2005-07-21 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-10-18 Cont ID  
Sent By pkrauss Date 2005-10-18 Time 14:02 Rev Time 0.25
Received By pkrauss Date 2005-10-18 Time 14:02 Sent To Z
Notes
2005-10-18 00:00:00INSTALLED BOLLARDS AROUND THE NATURAL
 GAS GENERATOR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-09 Cont ID  
Sent By pkrauss Date 2005-08-09 Time 13:38 Rev Time 0.35
Received By pkrauss Date 2005-08-09 Time 13:20 Sent To  
Notes
2005-08-09 00:00:00PLEASE PROVIDE MANUFACTURER'S SUBMITTAL
 DATA FOR THE GENERATOR.ADDITIONAL
 PERMIT REQUIRED FOR NEW GAS LINE
 INSTALLATION.
  
 PER 2001 FBC(M)303.4, EQUIPMENT SHALL
 NOT BE LOCATED WHERE DAMAGE MAY OCCUR
 UNLESS PROTECTED BY APPROVED BARRIERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-17 Cont ID  
Sent By pschmitz Date 2005-10-15 Time 13:31 Rev Time 0.00
Received By pschmitz Date 2005-10-15 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By kstevens Date 2005-08-24 Time 06:48 Rev Time 1.00
Received By kstevens Date 2005-08-24 Time 06:26 Sent To  
Notes
2005-08-24 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED
 FOR REQUIRED GAS PERMIT:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 7. INDICATE THE BTU LOAD OF EXISTING
 GENERATOR. IF NEW GENERTATOR IS A
 SUBSTANTIAL ADDITION TO SYSTEM, TOTAL
 BTU OF SYSTEM MAY BE REQUIRED TO CHECK
 PIPE SIZING OUT OF THE METER. (BTU LOAD
 OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2001
 FUEL GAS CODE SECS. 401.8 THRU 402.5.2
 AND TABLES 402(1) THRU 402(34)).
 8. PLANS INDICATE THAT THE UNDERGROUND
 PIPING SHALL HAVE A MINIMUM OF 12"
 COVER. SECTION 404.9 REQUIRES MINIMUM
 18" COVER, BUT MAY BE REDUCED TO 12"
 WHERE EXTERNAL DAMAGE IS NOT LIKELY TO
 RESULT. PLEASE INDICATE HOW THIS
 EXCEPTION WILL BE APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-18 Cont ID  
Sent By mmclean Date 2006-01-18 Time 11:21 Rev Time 0.00
Received By mmclean Date 2006-01-18 Time 11:21 Sent To B
Notes
2006-01-18 00:00:00OK, HAVE MORE PARKING SPACE THAN NEEDED.
  
 GIVEN TO JIM WITMER.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-10-21 Cont ID  
Sent By mmclean Date 2005-10-21 Time 07:30 Rev Time 0.00
Received By mmclean Date 2005-10-21 Time 08:55 Sent To I
Notes
2005-11-02 00:00:00DENIED,
 1. GENERATOR CANNOT BE LOCATED IN A
 REQUIRED PARKING LOT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-29 Cont ID  
Sent By mmclean Date 2005-08-29 Time 15:49 Rev Time 0.00
Received By mmclean Date 2005-08-29 Time 15:49 Sent To  
Notes
2005-08-29 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF
 SURVEY/SITEPLANS SHOWING THE LOCATION OF
 THE GENERATOR AND SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy