Plan Review Details - Permit 05070745
Plan Review Stops For Permit 05070745
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:31 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:31 Sent To M
Notes
2005-07-20 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-22 Cont ID  
Sent By hmoser Date 2005-12-22 Time 07:36 Rev Time 0.00
Received By hmoser Date 2005-12-22 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-23 Cont ID  
Sent By rregueir Date 2005-07-23 Time 13:47 Rev Time 0.00
Received By rregueir Date 2005-07-23 Time 13:47 Sent To PC
Notes
2005-07-23 00:00:00---------------PROVISO------------------
 1)AUXILIARY DRAIN PAN REQUIRED PER FBC,M
 307.2.3
  
 2)BALANCED RETURN REQUIRED FROM BACK
 BEDROOM PER FBC,M 601.4
  
 3)DRYER EXHAUST REQUIRED PER FBC,M 504
  
 4)AHU IN ATTIC REQUIRES NOTIFICATION AT
 C.B. PANEL PER FBC CH.13 SEC
 610.1.ABC.3.5.2
  
 5)AHU IN ATTIC TO HAVE MIN 30X20 ACCESS
 PANEL WITHIN 6' OF SERVICE PANEL PER FBC
 CH.13 SEC 610.1.ABC.3.5.2
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]