Plan Review Stops For Permit 05070625 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-07-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-23 |
Time |
19:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-07-23 |
Time |
19:57 |
Sent To |
|
|
Notes |
2005-07-23 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.)PROVIDE A FLOOR PLAN SHOWING WHERE | | THE SHUTTERS ARE TO BE INSTALLED. | | | | 2.)COMPLETE THE INSTALLATION SCHEDULE, | | ATTACHED. | | | | 3.)PROVIDE INFORMATION IN REGARDS TO | | THE BUILDING AND WIND PRESSURES FBC1608. | | IF THIS BUILDING IS OVER 60' TALL | | ENGINEERING TO DETERMINE DESIGN PRESSURE | | REQUIREMENTS IS REQUIRED. | | | | 4.)CIRCLE THE INSTALLATION DETAILS AND | | DESIGN PRESSURE INSTALLATION | | REQUIREMENTS SPECIFIC TO THIS JOB ON THE | | PRODUCT APPROVAL. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-07-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-18 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-18 |
Time |
10:42 |
Sent To |
B |
|
Notes |
2005-07-18 00:00:00 | TO "MISC" BOX #1 |
|
|
|