Plan Review Stops For Permit 05070533 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-07-29 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-07-29 |
Time |
11:43 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2005-07-29 |
Time |
11:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-07-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-07-13 |
Time |
18:31 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2005-07-13 |
Time |
18:31 |
Sent To |
PC |
|
Notes |
2005-07-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- MULE-HIDE BITUMEN ROOF SYSTEM | | SUBMITTED DOESN'T WORK. IT'S LIMITED BY | | LIMITATION #9 WHICH DOESN'T ALLOW | | ENHANCED FASTENING TO INCREASE THE | | UPLIFT VALUE AT CORNERS AND PERIMETER | | ZONES. PROVIDE ANOTHER SYSTEM THAT IS | | NOT LIMITED BY LIMITATION #9. (SEE TABLE | | 1606.2B FBC 2001 FOR DESIGN PRESSURES AT | | CORNERS AND PERIMETER AREAS) | | | | 2- CLEARLY SPECIFY ROOF TILE FASTENING. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC | | 2001. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|
|
|