Plan Review Details - Permit 05070533
Plan Review Stops For Permit 05070533
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-29 Cont ID  
Sent By alange Date 2005-07-29 Time 11:43 Rev Time 0.33
Received By alange Date 2005-07-29 Time 11:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By jgomez Date 2005-07-13 Time 18:31 Rev Time 0.50
Received By jgomez Date 2005-07-13 Time 18:31 Sent To PC
Notes
2005-07-13 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- MULE-HIDE BITUMEN ROOF SYSTEM
 SUBMITTED DOESN'T WORK. IT'S LIMITED BY
 LIMITATION #9 WHICH DOESN'T ALLOW
 ENHANCED FASTENING TO INCREASE THE
 UPLIFT VALUE AT CORNERS AND PERIMETER
 ZONES. PROVIDE ANOTHER SYSTEM THAT IS
 NOT LIMITED BY LIMITATION #9. (SEE TABLE
 1606.2B FBC 2001 FOR DESIGN PRESSURES AT
 CORNERS AND PERIMETER AREAS)
  
 2- CLEARLY SPECIFY ROOF TILE FASTENING.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.