Plan Review Details - Permit 05070507
Plan Review Stops For Permit 05070507
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-27 Cont ID  
Sent By jgomez Date 2006-02-27 Time 15:28 Rev Time 0.40
Received By jgomez Date 2006-02-27 Time 15:28 Sent To PC
Notes
2006-02-27 00:00:00PLANS UNDER "T". JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-22 Cont ID  
Sent By jgomez Date 2005-12-22 Time 13:05 Rev Time 1.00
Received By jgomez Date 2005-12-22 Time 07:59 Sent To PC
Notes
2005-12-22 00:00:00BUILDING REVISION CHECKLIST:
 1- SET OF PLANS SUBMITTED ARE FOR FBC
 2004 AND ASCE 7-02. ORIGINAL PLANS WERE
 REVIEWED UNDER FBC 2001 AND ASCE 7-98.
 REVISE AS REQUIRED.
  
 2- OWES $130.00 REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-22 Cont ID  
Sent By jgomez Date 2005-09-22 Time 10:13 Rev Time 0.50
Received By jgomez Date 2005-09-22 Time 10:13 Sent To PC
Notes
2005-09-22 00:00:00BUILDING REVIEW COMMENTS:
 1- REVISION OF DELETED WINDOWS IS IK.
 BUT NEED TO PROVIDE ALL INFORMATION
 (PRIOR TO CONSTRUCTION) REQUESTED ON
 PROVISO DATED 8-8-05. SEE ATTACHED COPY.
 2- SEE COMMENTS BY MECHANICAL AND
 ELECTRICAL PLAN REVIEWERS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-08 Cont ID  
Sent By jgomez Date 2005-08-08 Time 12:37 Rev Time 2.00
Received By jgomez Date 2005-08-08 Time 12:36 Sent To PC
Notes
2005-08-08 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE APPROVED LISTING AND SPECS
 FOR BBQ AND HOOD. SEC 2808 FBC 2001.
 2- RE-SUBMIT PRODUCT APPROVAL FOR:
 A) ROOF TILE. NEED FLORIDA APPROVAL.
 B) 90 DEGREE SLIDING GLASS DOORS.
 FLORIDA PRODUCT APPROVAL AND DADE COUNTY
 NOA DON'T CORRESPOND TO EACH OTHER.
 C)CASEMENT WINDOWS.NEED FLORIDA APPROVAL
 D) WINDOW MULLION SIZE SPECIFIED FOR
 LIVING ROOM AREA.
 3-SURVEY TO HAVE ORIGINAL SIGNATURE, NO
 COPY AS REQ'D BY CHAPTER 472 FL STATUTE.
 4-MULLION SIZE SPECIFIED FOR LIVING ROOM
 FIXED WINDOWS DON'T RESIST THE DESIGN
 PRESSURES. REVISE AS REQUIRED.
 5- REVISE TRUSS CONNECTOR G AND H. THEY
 CAN'T HAVE SAME UPLIFT CAPACITY IF THEY
 HAVE DIFFERENT # OF NAILS. ALSO, UPDATE
 SEE CATALOGUE FOR PROPER # OF NAILS.
 6- SHEET A2: REVISE BBQ NOTE. GRILL IS
 NOT OPTIONAL. IT SHALL BE INSTALLED IF
 BBQ IS GOING TO BE INSTALLED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-10-21 Cont ID  
Sent By dpalmer Date 2006-10-21 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2006-10-21 Time 15:03 Sent To PC
Notes
2006-10-21 15:27:02REV, AS BUILTS AFTER ROUGH.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 16:59 Rev Time 0.50
Received By btrobaug Date 2006-07-14 Time 16:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 14:17 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-26 Cont ID  
Sent By dpalmer Date 2005-08-26 Time 19:34 Rev Time 0.30
Received By dpalmer Date 2005-08-26 Time 19:26 Sent To M
Notes
2005-08-26 00:00:00********** UNSAT **********
  
 PLEASE SEE SOME NOTES FROM "PROVISO"
 WERE NOT CORRECTED FROM PREVIOUS
 REDLINED REVIEWED PLANS.
  
  
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES A WHIRLPOOL TUB, HOWEVER PLANS
 DO NOT SHOW THIS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED GFI
 PROTECTION TO BE INDICATED.
  
 2)NOTE: PLEASE SEE ALL RECEPTS WITH AREA
 OF LAUNDRY RM SINK SHALL BE GFI/ GFI
 PROTECTED.210.8
  
  
 3)NOTE: PLEASE SEE PANEL SCHEDULES
 INDICATE 80 RECESSED LTS, HOWEVER 80
 COULD NOT BE LOCATED ON PLANS.
 PLEASE ADJUST WHEN FINAL # IS INSTALLED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 ALONG WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION IS CALLED
 IN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-22 Cont ID  
Sent By dpalmer Date 2005-07-22 Time 16:00 Rev Time 0.75
Received By dpalmer Date 2005-07-22 Time 16:00 Sent To M
Notes
2005-07-22 00:00:00********** PROVISO/RELDINED ***********
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES A WHIRLPOOL TUB, HOWEVER PLANS
 DO NOT SHOW THIS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED GFI
 PROTECTION TO BE INDICATED.
  
 2)NOTE: PLEASE SEE ALL RECEPTS WITH AREA
 OF LAUNDRY RM SINK SHALL BE GFI/ GFI
 PROTECTED.210.8
  
 3)NOTE: PLEASE SEE KITCHEN APPEARS TO BE
 SHOWING AN "ISLAND", IF SO, PLEASE SEE
 210.52C2, 210.8A6 FOR REQUIRED GFI
 RECEPT(S).
  
 4)NOTE: PLEASE SEE PANEL SCHEDULES
 INDICATE 80 RECESSED LTS, HOWEVER 80
 COULD NOT BE LOCATED ON PLANS.
 PLEASE ADJUST WHEN FINAL # IS INSTALLED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 ALONG WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION IS CALLED
 IN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 16:23 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 16:23 Sent To P
Notes
2007-01-09 16:23:30TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 15:32 Sent To E
Notes
2006-10-18 15:32:41TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 14:39 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 14:39 Sent To E
Notes
2006-07-14 00:00:00TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 18:04 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 18:04 Sent To B
Notes
2006-02-15 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 09:49 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 09:49 Sent To E
Notes
2005-11-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 17:16 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 17:16 Sent To E
Notes
2005-08-24 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 09:55 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 09:55 Sent To E
Notes
2005-07-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-08 Cont ID  
Sent By jgomez Date 2005-08-08 Time 13:11 Rev Time 0.00
Received By jgomez Date 2005-07-14 Time 16:05 Sent To  
Notes
2005-07-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-02 Cont ID  
Sent By tgordon Date 2005-12-02 Time 10:52 Rev Time 0.30
Received By tgordon Date 2005-12-02 Time 10:52 Sent To E
Notes
2005-12-02 00:00:00INFO. REQUESTED HAS BEEN PROVIED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-08-31 Cont ID  
Sent By tgordon Date 2005-08-31 Time 08:44 Rev Time 0.15
Received By tgordon Date 2005-08-31 Time 08:44 Sent To B
Notes
2005-08-31 00:00:00***DENIED***
 NEED INFORMATION ABOUGHT FIREPLACE.
 MODEL NUMBER, COMBUSTON & VENTILATION
 AIR,NATURAL OR PROPANP GAS, ETC..
 IF YOU HAVE ANY QUESTONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-26 Cont ID  
Sent By prafter Date 2005-07-26 Time 07:20 Rev Time 0.75
Received By prafter Date 2005-07-26 Time 07:20 Sent To B
Notes
2005-07-26 00:00:00MECH.PLAN REVIEW.
  
 PROVISO: MASTER BATH REQUIRES EXHAUST
 2003 FBC/M 402.3.1 .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 13:29 Rev Time 0.33
Received By jleech Date 2005-07-23 Time 13:29 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-21 Cont ID  
Sent By mmclean Date 2005-07-21 Time 14:01 Rev Time 0.00
Received By mmclean Date 2005-07-21 Time 14:01 Sent To B
Notes
***NONE***