Plan Review Details - Permit 05070440
Plan Review Stops For Permit 05070440
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-12-02 Cont ID  
Sent By rmcdouga Date 2005-12-02 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2005-12-02 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-26 Cont ID  
Sent By rmcdouga Date 2005-08-26 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2005-08-26 Time 14:29 Sent To  
Notes
2005-08-26 00:00:00PROCESS AND ISSUE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-19 Cont ID  
Sent By rmcdouga Date 2005-08-19 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2005-08-26 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-08 Cont ID  
Sent By rmcdouga Date 2005-08-08 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2005-08-08 Time 16:02 Sent To  
Notes
2005-08-08 00:00:00DENIED
  
 1) THE REVISED SHEET CVR SPECIFIES THE
 INCORRECT EDITION OF THE BUILDING CODE.
 THE CORRECT EDITION IS THE 2001 FLORIDA
 BUILDING CODE.
  
 2) REVISE THE NOTE ON A1 WHICH ADDRESSES
 THE WORDING OF THE STENCIL REQUIRED BY
 FBC 704.2.1.4 TO INCLUDE SMOKE BARRIER.
  
 3) PLEASE REMOVE THE VOIDED PLAN SHEETS
 FROM THE TWO PERMIT SETS. ONE SET OF THE
 VOIDED PLANS CAN BE SUBMITTED TO HELP
 EXPEDITE PLAN REVIEWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By rmcdouga Date 2005-07-20 Time 09:32 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2005-07-20 00:00:00DENIED
  
 1)705.7.1 JOINTS INSTALLED IN OR
 BE- TWEEN FIRE RESISTANT WALLS, FIRE
 RESIS- TANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEIL- ING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE RE- QUIRED FIRE RESISTANCE
 RATING OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED. SHOW
 COMPLIANCE AT DETAIL 7 ON A4.
  
 2) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 3) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 5) PROVIDE A DETAIL OF THE EXISTING ONE
 HOUR FIRE RATED COLUMNS. SPECIFY THE
 MATERIAL AND REQUIRED THICKNESS OF THE
 SPRAYED ON FIREPROOFING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-01 Cont ID  
Sent By btrobaug Date 2005-12-01 Time 11:32 Rev Time 0.00
Received By btrobaug Date 2005-11-21 Time 08:43 Sent To  
Notes
2005-12-01 00:00:00 
 ENTERED FOR DVP./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 20:30 Rev Time 0.40
Received By dpalmer Date 2005-08-10 Time 20:11 Sent To  
Notes
2005-08-10 00:00:00OLD/VOIDED SHEETS WERE NOT REMOVED FROM
 SETS AS REQUESTED ON PREVIOUS REVIEW.
 ELECTRICAL SHEETS REMOVED FROM BOTH
 SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 20:18 Rev Time 0.50
Received By dpalmer Date 2005-07-15 Time 20:17 Sent To  
Notes
2005-07-15 00:00:00******** UNSAT ********
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS PLEASE MAKE THE FOLLOWING
 CHANGES.
  
 1)NOTE: PLEASE SEE 2002 NEC 210.8B3,
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 2)NOTE: PLEASE CLARIFY LOAD ON EXISTING
 SERVICE. IS THERE EXSITNG LOADS? NOTE
 RISER SEEMS TO INDICATE THIS BLD-OUT AS
 THE ONLY TENANT THUS FAR?
 215.5, 220
  
 3)NOTE: PLEASE CLARIFY EM LTS?
 FIXTURE TYPE "C" INDICATE HATCHED
 FIXTURES W/ BATTERY BACK UP, IS THIS THE
 SAME FOR FIXTURE "B"?
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ANY VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-02 Cont ID  
Sent By mwennerg Date 2005-12-02 Time 13:48 Rev Time 0.00
Received By mwennerg Date 2005-12-02 Time 13:48 Sent To  
Notes
2005-12-02 00:00:00REVISION DATED 10/13/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By mwennerg Date 2005-08-11 Time 09:17 Rev Time 0.00
Received By mwennerg Date 2005-08-11 Time 09:17 Sent To  
Notes
2005-08-11 00:00:00******PASSED******
  
 PLANS RED LINED ON SHEET E-3 REGARDING
 DUCT SMOKE DETECTORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By mwennerg Date 2005-07-20 Time 11:13 Rev Time 0.00
Received By mwennerg Date 2005-07-20 Time 11:13 Sent To  
Notes
2005-07-20 00:00:00******DENIED******
  
 1) ALL LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION.
  
 2) SEPARATE SHOP MDRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 3) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS,DUCT SMOKE DETECTOR
 INSTALLATIONS SHALL BE WIRED TO CAUSE A
 GENERAL FIRE ALARM, NOT SUPERVISORY
 SIGNAL.
  
 4) DRAWINGS SHOW ONE EMERGENCY LIGHT.
 MORE MAY BE REQUIRED WHERE ARTIFICIAL
 LIGHTING IS NOT ADEQUATE.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 17:53 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 17:53 Sent To  
Notes
2005-11-17 00:00:00TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 14:03 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 14:03 Sent To  
Notes
2005-08-18 00:00:00TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 15:40 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 15:40 Sent To  
Notes
2005-08-05 00:00:00TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-07-20 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 13:22 Sent To  
Notes
2005-07-14 00:00:00TO "BOB" BD#4

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-01-10 Cont ID  
Sent By pkrauss Date 2006-01-10 Time 14:27 Rev Time 0.00
Received By pkrauss Date 2006-01-10 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-11-29 Cont ID  
Sent By hmoser Date 2005-11-29 Time 09:21 Rev Time 0.00
Received By hmoser Date 2005-11-29 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-25 Cont ID  
Sent By hmoser Date 2005-08-25 Time 08:41 Rev Time 0.00
Received By hmoser Date 2005-08-25 Time 08:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-08-10 Cont ID  
Sent By hmoser Date 2005-08-10 Time 09:24 Rev Time 0.00
Received By hmoser Date 2005-08-10 Time 09:24 Sent To  
Notes
2005-08-10 00:00:00PLAN DENIED
 SAME AS 1ST REVIEW HM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 08:34 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 07:32 Sent To  
Notes
2005-07-16 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 401.5.1
 FBC(M) INTAKE OPENINGS PLAN PAGE A/C-1.
 2) PLEASE PROVIDE INFORMATION ON
 E-30/12E/A AND E-30/12 O/A PLAN PAGE A/C
 1
 3) PLAN PAGE A/C-4 AUXILIARY DRAIN PAN
 SHALL BE 1 1/2 IN. DEEP PER SECTION
 307.2.3 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-11-18 Cont ID  
Sent By pschmitz Date 2005-11-18 Time 11:12 Rev Time 0.00
Received By pschmitz Date 2005-11-18 Time 11:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-06 Cont ID  
Sent By pschmitz Date 2005-08-06 Time 09:53 Rev Time 0.00
Received By pschmitz Date 2005-08-06 Time 09:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By kstevens Date 2005-07-15 Time 17:49 Rev Time 0.75
Received By kstevens Date 2005-07-15 Time 17:49 Sent To  
Notes
2005-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHTS A-1 & A-3, SHOW THE CLEAR FLOOR
 SPACE FOR THE W/C'S, LAVS, LOUNGE SINK,
 AND WATER COOLER:
 A. 11-4.15.5
 B. 11-4.16.2
 C. 11-4.19.3
 D. 11-4.24.5
 AND SHOW THE FOLLOWING FOR THE LAVS:
 E. 11-4.19.5
 AND SHOW THE FOLLOWING FOR THE LOUNGE
 SINK:
 F. 11-4.24.3 KNEE CLEARANCE (27")
 G. 11-4.24.4 SINK DEPTH
 H. 11-4.24.6 EXPOSED PIPES & SURFACES
 I. 11-4.24.7 FAUCETS
 2. SHT P-2 DOMESTIC WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS SHALL BE SHOWN AT
 THE WASH MACHINE AND THE ICE MAKER PER
 SECTION 604.9 AND SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" PER
 PDI-WH 201. (NOT IN THE CEILING).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]