Plan Review Details - Permit 05070334
Plan Review Stops For Permit 05070334
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-23 Cont ID  
Sent By jwitmer Date 2007-08-23 Time 11:02 Rev Time 2.22
Received By jwitmer Date 2007-08-23 Time 11:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-18 Cont ID  
Sent By jwitmer Date 2007-08-18 Time 15:20 Rev Time 0.77
Received By jwitmer Date 2007-08-18 Time 15:20 Sent To  
Notes
2007-08-18 15:31:54BUILDING PLAN REVIEW
 PERMIT:05070334/ 03031228/ 01051303
 ADD: 4011 NORTH SHORE DR.
 CONT: CARLO MERCURIO
 TEL: (561)329-8167
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW: PLANS SUBMITTED BY ENGINEER ALONSO,
 ALFREDO C
  
 ACTION: DENIED
 1 ) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICHTHE PROJECT WAS
 DESIGNED. THE DESIGNER OF RECORD NEGLECED TO SEE
 COMMENT# 5 FROM THE
 FIRST REVIEW, ALL REVIEWS TO BE COMPLETED UNDER THE
 2001 FBC. PLEASE CORRECT THE COVERSHEET TO REFLECT THIS
 COMMENT.
 TELLEPHONED DON GIBSON TO HAVE NEW COVERSHEETS
 SUBMITTED ON MONDAY 8-20-07. ***** UNSAT2ND REVIEW
 ****
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-21 Cont ID  
Sent By jwitmer Date 2007-06-21 Time 18:21 Rev Time 3.33
Received By jwitmer Date 2007-06-21 Time 17:43 Sent To  
Notes
2007-06-21 18:22:24BUILDING PLAN REVIEW
 PERMIT:05070334/ 03031228/ 01051303
 ADD: 4011 NORTH SHORE DR.
 CONT: CARLO MERCURIO
 TEL: (561)329-8167
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW: PLANS SUBMITTED BY ENGINEER ALONSO, ALFREDO
 C
  
 ACTION: DENIED
 1 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G)SQ. FT. UNDER ROOF (TOTAL)
 H) FLOOD ZONE
  
 2) FL ADMINISTRATIVE CODE 61G15-23.001(2) THE ENGINEER
 OF RECORD IS TO BE IN GOOD STANDING UNDER CHAPTER 471.
 SEE ATTACHMENT DEINGUENT LICENSE.
  
 3)THE SEET OF PLANS ARE MISSING THE ARCHITECTURAL
 SHEETS PROVIDING THE LIFE SAFETY SHEETS, FLOOR LAYOUT,
 WALL RATINGS, DOOR RATINGS ,ETC.
  
 4) SHEET S-17 IS MISSING THE GABLE WALL DETAIL, NOTE
 THAT THE MASONARY WALL IS TO CONTINUE TO THE GABLE TIE
 BEAM.
  
 5) MEETING WITH THE NEIL MELICK THE BUILDING OFFICIAL
 THE REVIEWS WILL TAKE PLACE UNDER THE 2001 FBC.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-14 Cont ID  
Sent By jwitmer Date 2006-06-14 Time 11:05 Rev Time 1.33
Received By jwitmer Date 2006-06-14 Time 11:05 Sent To PC
Notes
2006-06-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070334/ 03031228
 ADD: 4011 NORTH SHORE DR.
 CONT: CARLO MERCURIO
 TEL: (561)329-8167
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ALTHOUGH THIS IS A NEW PERMIT AND NEW CONTRACTOR,
 THE NEW CONTRACTOR IS USING
 PLANS THAT BELONG TO THE CONTRACTOR DON
 CLAY. A NOTIRIZED LETTER FROM DON CLAY CONSTRUCTION
 WILL BE REQUIRED
 RELINQUISHING OWNERSHIP OF THE PLANS.
  
 2) IF DON CLAY GIVES OWNERSHIP OF THE
 PLANS TO THE NEW CONTRACTOR, CARLO
 MERCURIO, THE SECOND ISSUE IS, IN
 SUBMITTING REVISIONS CREATED BY ZUHAIR
 JALLOUI, P. E. HE IS TAKING
 RESPONSIBLILITY FOR THE PROJECT. GLEEN
 GOLDBERG APPARTENTLY IS NO LONGER THE
 ENGEINEER OF RECORD. THE NEW P.E. WILL
 HAVE TO TAKE RESPONSIBILITY FOR THE JOB
 REMOVE THE OLD ENGINEERS SEAL FROM THE
 SHEETS, AND RESEAL THE SHEETS WITH HIS
 SEAL. SEE ATTACHED SHEET 61G15-27 FOR
 PROCEDURES FOR THE ADOPTION OF ANOTHER'S
 WORK.
  
 3) IF DON CLAY DOESN'T SUBMIT A LETTER
 GIVING THE NEW CONTRACTOR PERMISSION TO
 USE THE PLANS SUBMITTED UNDER 03031228,
 NEW PLANS WILL NEED TO ACCOMPANY THE NEW
 PERMIT.
  
 4)FLORIDA CONSULTING ENGINEERS, INC.
 IS MISSING THEIR:
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2005-07-27 Cont ID  
Sent By fgodard Date 2005-07-27 Time 15:01 Rev Time 0.01
Received By fgodard Date 2005-07-27 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 16:36 Sent To B
Notes
2007-08-23 16:39:522ND SERVICE GRANTED PER INSPECTOR BOB GERWE AND JAKE
 LEAHY.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-20 Cont ID  
Sent By dpalmer Date 2007-08-20 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2007-08-20 Time 11:32 Sent To  
Notes
2007-08-20 14:43:59*** DENIED ***
  
  
 1) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE COVER SHEET REFERENCING PLANS DESIGN
 STILL STATES THE 2004 FBC WHEN THIS SHOULD REFLECT THE
 2001 FBC.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO THE CORRECT LICENSE INFORMATION AND TITLE
 BLOCK INFORMATION TO BE ON PLANS. THIS IS INCLUSIVE OF
 MEP SHEETS.
 PLEASE SEE THE ATTACHED PRINT OUT DATED THE SAME DATE
 OF THIS REVIEW WHICH SHOWS THE PRINT OUT FOR
 ENGINEERING FIRM FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 PLEASE SEE THE FIRM NAME AS LISTED ON THE STATE WEBSITE
 DOES NOT COORDINATE WITH THE PLANS.
 PLEASE KNOW IT IS OUR UNDERSTANDING FROM THE DBPR THAT
 THIS INFORMATION NEEDS TO MATCH. PLEASE HAVE STATE
 UPDATE WEBSITE IF INDEED THIS INFORMATION ON TITLE
 BLOCKS IS CORRECT OR UPDATE TITLE BLOCKS TO MATCH
 LICENSURE WITH THE STATE.
 PLEASE KNOW A LETTER FROM THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION STATING THIS INFORMATION
 DOES NOT NEED TO MATCH IS ACCEPTABLE. MUST BE ORIGINAL
 AND NOTARIZED FROM THE STATE.
 FAC 61G15-23.002, FS 471.023, FS 117.05
  
 3) NOTE: PLEASE SEE NO RESPONSE FROM THE DESIGN
 PROFESSIONAL WAS SUBMITTED WITH RESPECT TO PREVIOUS
 COMMENT NUMBER 7. THE PLANS WERE REVISED HOWEVER WITH A
 NOTE WHICH STATES THE SERVICE MEETS 230.2 EXCEPTION #7.
 PLEASE CLARIFY THIS AS UPON REVIEW OF THE 1999, 2002
 AND 2005 NEC COULD NOT ANY *EXCEPTION #7* AS STATED.
 PLEASE VERIFY HOW THE ADDITIONAL SERVICE MEETS 230.2.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-26 Cont ID  
Sent By dpalmer Date 2007-06-26 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2007-06-26 Time 12:48 Sent To  
Notes
2007-06-26 17:09:23 
  
 *** UNSAT ***
  
 REVISIONS:
  
 1) NOTE: PLEASE SEE THE REVISIONS ARE NOW COMING IN
 DESIGNED AND SHOWING SEVERAL CODES WHICH ARE CURRENTLY
 IN EFFECT. PLEASE KNOW THE PERMITTED WORK FOR THIS
 BUILDING WAS UNDER PREVIOUS CODES AS STATED BELOW.
 ** PLEASE KNOW IF THE DESIGNS WERE UNDER THE 2004 FBC
 THERE WAS NO DESIGNS TO FBC CHAPTER 13.
  
 THE FOLLOWING CODES WERE APPLICABLE WHEN THIS PERMIT
 WAS APPLIED.
 2001 FBC
 1999 NFPA-70 (NEC).
 1997 NFPA-101 LIFE SAFETY CODE
 1999 NFPA-72
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADE WHICH ALSO
 MAY REQUEST CERTAIN CODE CHANGES.
  
 2) NOTE: NEW DESIGNERS OF RECORD:
 PLEASE SEE THE LICENSE NUMBER AS STATED AND SEALED ON
 PLANS IS SHOWN ON THE STATE WEBSITE FROM THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION AS *
 DELINQUENT*. PLEASE SEE ATTACHED PRINT OUT FROM DBPR.
 FS 481.
  
 3) NOTE: NEW ELECTRICAL DESIGNER/ENGINEER OF RECORD.
 PLEASE SEE THE SEAL WHICH IS BEING USED IS NO LONGER
 VALID WITH THE STATE OF FLORIDA. PLEASE SEE RULING
 UNDER THE FLORIDA ADMINISTRATIVE CODE 61G15-23.001 IN
 FEBRUARY 04 WHICH REQUIRED ALL SEALS FOR ENGINEERS TO
 CHANGE THE WORDING ON THE SEAL FROM *CERTIFICATE* TO
 THE WORDING OF *LICENSE*. AN EXTENSION WAS GIVEN TO THE
 DATE OF DECEMBER 31, 2005 HOWEVER ALL SEALED DOCUMENTS
 AFTER THAT DATE MUST HAVE NEW SEAL. PLEASE OBTAIN NEW
 SEAL FOR SAID DOCUMENTS.
 FS 471.025
  
 4) NOTE: PLEASE SEE MISSING INFORMATION FROM TITLE
 BLOCKS FOR ENGINEERING FIRM AS REQUIRED UNDER FAC
 61G15-23.002 AND FLORIDA STATUTES 471.023.
 PLEASE SEE THE MISSING *CERTIFICATE OF AUTHORIZATION
 NUMBER* ALSO KNOWN AS THE ENGINEERING BUSINESS NUMBER
 OR FIRM LICENSE NUMBER.
 ** PLEASE SEE THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 5) NOTE: PLEASE SEE THE PLANS NEED TO SHOW ALL
 LOCATIONS AND ALL MINIMUM LEVELS FOR HORNS, STROBES AND
 HORN/STROBE DEVICES.
 PLEASE SEE 2001 FBC 11-4.28.1,.2, AND .3(4).
  
 6) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS PER
 2001 FBC CHAPTER 13.
 A) PLEASE SEE THAT THESE ARE REQUIRED TO BE SIGNED,
 DATED, AND SEALED BY THE DESIGNER OF RECORD ALONG WITH
 SIGNATURE FROM OWNER AGENT. FS 481.221/ 471.025, FAC
 61G15-23.002, 61G1-16.004
 B) PLEASE SEE PLANS ARE MISSING THE FIXTURE LEGEND FOR
 LIGHTING FIXTURES. PLEASE PROVIDE ALL INFORMATION FOR
 THESE AND BE SURE TO CORRELATE WITH REVISED ENERGY
 CALCULATIONS.
  
 7) NOTE: PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN
 COMPLETELY REVISED WITH SEVERAL ITEMS INCLUDING NOW
 SHOWING A NEW SERVICE WHICH DOES NOT MEET THE
 EXCEPTIONS OF 230.2.
 PLEASE SEE THE RISER DIAGRAM ITSELF IS NOT SHOWN AS
 CODE COMPLIANT.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ARE SHOWN
 FOR THE FPL TRANSFORMER UNDERGROUND AND THEN THERE ARE
 THREE SETS OF TAPS FROM THE SAME UNDERGROUND????
 PLEASE SEE ONE TAP FOR A NEW A/C MAIN, A NEW FIRE PUMP
 MAIN, AND THE MAIN FOR THE BUILDING ELECTRICAL
 SERVICE.
 PLEASE SUBMIT A REVISED DIAGRAM WHICH INDICATES CODE
 COMPLIANCE WITH THE NEC.
 215.5,240.21,230.2,230.70,230.71 ETC.
 THE TAPS AS SHOWN ON RISER ARE NOT CLEAR AND ARE NOT
 PERMITTED.
  
 8) NOTE: PLEASE SEE RISER SHOWS AND NEW FIRE SPRINKLER
 MAIN WHICH CAN ONLY BE ASSUMED AS A FIRE PUMP MAINS
 HOWEVER THE PLANS DO NOT INDICATE ANY INFORMATION FOR
 THIS.
 PLEASE SEE 230.2, 230.70, 695.4 AND NFPA-20 FOR ALL
 INFORMATION NEEDED.
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THE
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE INDICATE THE LOCATION AND INFORMATION ON PLANS
 AS THESE COULD NOT BE LOCATED ON PLANS.
 ** PLEASE KNOW AS NO INFORMATION WAS SHOWN OR
 SUBMITTED, A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
 PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT.
  
 9) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AS REQUIRED PER 110.9 OF THE NEC.
  
 10) NOTE: PLEASE SEE THE TOTAL OF THE CONNECTED LOAD
 AMPS SEEMS TO BE A MISPRINT AS THIS SHOWS 110.5 AMPS.
 FBC104.1.2 COORDINATION.
  
 11) NOTE: PLEASE SEE THE AIC RATING WHICH IS BEING
 SHOWN ON THE MDP AS 65K, JUST A NOTE AS EACH OF THE
 BRANCH BREAKERS IN THIS MLO WILL BE REQUIRED TO BE 65K
 RATED AS SHOWN.
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-08-25 Cont ID  
Sent By dpalmer Date 2005-08-25 Time 08:30 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-08-25 00:00:00SEE NOTES/REVIEWS UNDER 03031228

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2007-08-22 Cont ID  
Sent By rchokshi Date 2007-08-22 Time 14:25 Rev Time 0.00
Received By rchokshi Date 2007-08-22 Time 14:21 Sent To  
Notes
2007-08-22 14:25:18 
 PLEASE MAKE SURE ALL ENGINEERING REVIEWREQUIREMENT
 MUST MEET INPERMIT # 03031228,# 03071082 FOR THIS
 PERMIT.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-21 Cont ID  
Sent By mawillia Date 2007-08-21 Time 15:43 Rev Time 0.00
Received By mawillia Date 2007-08-21 Time 13:58 Sent To  
Notes
2007-08-21 15:43:17*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;NEW ENGINEER PLAN SHEET A-3, FA-1, E-6,
 E-7, AND M-4 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-30 Cont ID  
Sent By mawillia Date 2007-06-30 Time 23:33 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 19:11 Sent To  
Notes
2007-07-01 00:01:27*****DENIED*****
  
  
 1.NO ARCHITECTURE SHEETS, INCLUDING A LIFE SAFETY
 SHEET, TO VERIFY THE NATURE OF REVISIONS/CHANGES TO THE
 FLOOR PLAN THAT WERE OR WERE NOT MADE.
  
 2.ON AT LEAST ONE OF THE THREE SET OF PLANS, NO SSEAL
 ON SHEET E-6 AND E-7. EACH SHEET OF PLANS MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471 SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 3.ON SHEET E-7, THERE IS AN EXIT SIGN NEAR THE BOYS'
 LOCKER ROOM AND AN EXIT SIGN NEAR THE GIRLS' LOCKER
 ROOM BUT NO EXIT EXIT DOOR FOUND.PLEASE EXPLAIN.
  
 4.ON SHEET E-7, THERE IS NO INDICATION OF THE
 MECHANICAL ROOM IN BOTH THE BOYS' AND GIRLS' LOCKER
 AREA AS INDICATED ON SHEET E-2 OF THE ORIGINAL
 PERMITTED PLANS.
  
  
 PLEASE NOTE THAT ADDITIONAL INFORMATION IS NEEDED IN
 ORDER TO CONDUCT A COMPLETE FIRE PLAN REVIEW.
 ADDITIONAL COMMENTS MAY BE GIVEN WHEN OTHER INFORMATION
 IS GATHERED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 11:21 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 11:21 Sent To M
Notes
2007-11-28 11:22:20TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 09:30 Sent To M
Notes
2007-10-19 09:30:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-01 Cont ID  
Sent By adarroug Date 2007-08-01 Time 11:42 Rev Time 0.00
Received By adarroug Date 2007-08-01 Time 11:42 Sent To  
Notes
2007-08-16 15:18:38TO "COMM" BD#37
2007-08-01 11:42:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-14 Cont ID  
Sent By adarroug Date 2007-06-14 Time 10:53 Rev Time 0.00
Received By adarroug Date 2007-06-14 Time 10:53 Sent To B
Notes
2007-06-26 10:13:236/26/07--TO "COMM" BD#4/PLANS ON RACK--4 ROLLS
2007-06-14 10:53:16TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 13:45 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 13:45 Sent To B
Notes
2006-06-01 00:00:00TO "JWITMER" DESK/REV--REVIEWS UNDER
 ORIGINAL PERMIT#03031228

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 18:51 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 18:51 Sent To E
Notes
2005-08-18 00:00:00TO "DPALMER" DESK/REV

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 10:40 Rev Time 0.25
Received By tgordon Date 2007-12-04 Time 10:40 Sent To  
Notes
2007-12-04 10:43:18RECEIVED ENGINEERING SHOWING HOW AIR DUCTS ARE TO BE
 SECURED TO ROOF.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-26 Cont ID  
Sent By tgordon Date 2007-10-26 Time 10:43 Rev Time 0.30
Received By tgordon Date 2007-10-26 Time 10:43 Sent To  
Notes
2007-10-26 11:03:54PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) WILL NEED TO SUBMIT THE ENGINEERING (BY THE ENGINEER
 ON RECORD) WITH WIND LOAD CALCULATIONS SHOWING
 COMPLIANCE WITH 2001 FBC 1606 WIND LOADS (140 MPH
 WINDS) SIGNED AND SEALED.
  
 2) SEE DETAIL SUBMITTED SHOWS DUCT SUPPORT SPACING TO
 BE 8 FOOT MINIMUM. WHAT WOULD THE MAXIMUM SPACING BE?
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By rregueir Date 2007-06-27 Time 12:02 Rev Time 0.00
Received By rregueir Date 2007-06-26 Time 19:16 Sent To  
Notes
2007-06-27 12:02:16-----------------DENIED--------------------
  
 FBC 2001 CODE FAMILY
  
 1. PG M3: AHU 15 & 16, RECIRCULATION OF AIR FROM LOCKER
 ROOMS AND TOILET ROOMS IS PROHIBITED PER FBC,M TABLE
 403.3(B). NOTE #13 CALLS FOR LOUVERED DOORS IN LOCKER
 ROOMS FOR RETURN. THERE ARE TWO OPTIONS FOR CODE
 COMPLIANCE:
 A) REPLACE LOUVER DOOR WITH A SOLID DOOR, PROVIDING
 DOOR GASKET AND SEALED THRESHOLD TO ISOLATE RETURN FROM
 BATHROOM/LOCKER ROOM AREA.
 B) PROVIDE A DUCTED RETURN TO RUN CONTINUOUS FROM
 RETURN GRILL IN WALL TO THE RETURN INLET ON AHU'S.
  
 2. AHU 16 RETURN IS LOCATED IN A STORAGE ROOM WHERE IT
 WILL BE ISOLATED FROM RETURNING ANY OF THE 1085 CFM
 SUPPLIED TO THE STAGE AREA.. BALANCED RETURN IS
 REQUIRED PER FBC,M 601.4.
  
 3. AHU'S 15 AND 16 SHOW 1380 CFM OF SUPPLY, BUT ARE
 RATED FOR 5 TONS OF COOLING. ADDISON UNITS SHOW 900 OR
 1100 CFM SUPPLY BUT ARE RATED FOR 5 OR 6 TONS OF
 COOLING. PLEASE PROVIDE COOLING LOAD CALCULATIONS,
 REVISED ENERGY CALCULATIONS AND MANUFACTURER'S DATA
 SHOWING THE EQUIPMENT WILL FUNCTION AS INTENDED WITHIN
 THESE DESIGN PARAMATERS.
  
 4. PLEASE PROVIDE ARCHITECTURAL PLANS SHOWING THE
 LOCATION OF ALL RATED WALLS TO VERIFY THE LOATION OF
 ALL FIRE DAMPERS RELATED TO THESE WALLS PER FBC,M
 607.1.2.
  
 NOTE: THE RETURN OPENINGS IN THE BLOCK WALLS IN THE
 GYMNASIUM, HAVE PROVISIONS BEEN MADE TO PROVIDE
 ADDITIONAL SUPPORT AT THESE OPENINGS, SUCH AS LENTILS?
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-08-17 Cont ID  
Sent By rregueir Date 2007-08-17 Time 15:17 Rev Time 0.00
Received By rregueir Date 2007-08-17 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-17 Cont ID  
Sent By kstevens Date 2007-08-17 Time 13:21 Rev Time 0.00
Received By kstevens Date 2007-08-17 Time 13:21 Sent To  
Notes
2007-08-17 13:21:50AS-BUILT REVISIONS OK

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-28 Cont ID  
Sent By kstevens Date 2007-06-28 Time 09:36 Rev Time 0.00
Received By kstevens Date 2007-06-27 Time 19:15 Sent To  
Notes
2007-06-28 10:38:28DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P1 ONE SHEET ON ONE SET IS NOT SIGNED, SEALED,
 DATED AS REQUIRED BYSECTION 104.2.2, FAC
 61G15-23.004(1)(2) & FS 471.025
  
 2. ALL ELECTRIC, MECHANICAL & PLUMBING SHEETS. THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2)
 & FS 471.025.
  
 3. SHT P2 DELETE THE SANITARY BRANCH LINE DOWNSTREAM OF
 THE JANITOR SINK OR INDICATE THE USE FOR THIS LINE.
 (NOT SHOWN ON THE RISER DIAGRAM). SECTION 104.2.1.
  
 4. SHT P3 A VENT IS REQUIRED FOR THE WATER CLOSET NEXT
 TO WATER HEATER 1A. TABLE 906.1.
  
 5. SHT P4 DETAIL 1 SEE PREVIOUS COMMENT #4.
  
 6. SHT P4 DETAIL 3 SEE COMMENT #3.
  
 7. SHT P4 DETAIL 5 SHOW STUB-OUTS FOR THE URINALS.
 SECTION 104.2.1.
  
 8. SHT P6 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. IN THE GIRLS TOILET ROOM AT THE LAVS, 4
 W/C'S & FLOOR DRAIN, IN THE BOYS TOILET ROOM 1 URINAL
 IS MISSING. ALSO THE FLOOR PLAN IN THE BOYS SHOWER AT
 THE W/C AND THE GIRLS SHOWER THE W/C'S FACING EACH
 OTHER.--SINK-3, (NEXT TO W/H-3),IS MISSING
 BETWEEN TOILET ROOMS--THE WASTE ARMS FOR THE
 DRINKING FOUNTAINS AS INDICATED ARE "S" TRAPS AND SHALL
 STUB OUT STRAIGHT FROM THE FIXTURE BRANCH ARM.--
 SINK-4'S SHALL NOT DRAIN THRU THE WET VENT OF THE
 TOILET ROOMS. SECTION 909.1 (THESE ARE LOCATED AT THE
 WEST SIDE OF THE FLOOR PLAN AND NEAR THE GREAS
 INTERCEPTOR).--INDICATE 2-WAY CLEANOUTS ON EACH
 SIDE OF THE GREASE INTERCEPTOR. --REMOVE ALL TRAPS AT
 THE WATER CLOSETS ON THE RISER DIAGRAM. THE WATER
 CLOSETS HAVE INTEGRAL TRAPS AND DOUBLE TRAPING IS NOT
 APPROVED. SECTIONS 104.2.1, 1002.1. (SEE RED LINE
 CORRECTIONS ON ONE SET OF PLANS).
  
 9. SHT P8WATER HEATER DETAIL. SHOW THERMAL EXPANSION
 CONTROL AS REQUIRED IN SECTION 607.3.2.--FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS.
 DELETE FROM DETAIL REFERENCE. SECTIONS 802.3 & 802.3.2.
 --DIELECTRIC UNIONS ARE NOT ANAPPROVED FITTING FOR
 USE IN THEWATER SYSTEM. CHANGE REFERENCE TO
 "COUPLING".
  
 10. A LETTER INDICATING THAT AN ELECTRIC WATER HEATER
 HAS BEEN CHANGED TO A GAS WATER HEATER. A SEPARATE GAS
 PERMIT IS REQUIRED AND THE FOLLOWING INFORMATIO IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-23 Cont ID  
Sent By choops Date 2007-08-23 Time 10:57 Rev Time 0.00
Received By choops Date 2007-08-23 Time 10:57 Sent To  
Notes
2007-08-23 10:58:15USED ORIGINAL SITE PLAN/LANDSCAPE PLAN ON CITY FILE