Plan Review Details - Permit 05070295
Plan Review Stops For Permit 05070295
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status N Date 2007-05-08 Cont ID  
Sent By jwitmer Date 2007-05-08 Time 08:14 Rev Time 3.33
Received By jwitmer Date 2007-05-08 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-03-01 Cont ID  
Sent By jwitmer Date 2007-03-01 Time 14:46 Rev Time 0.77
Received By jwitmer Date 2007-03-01 Time 14:46 Sent To PC
Notes
2007-03-01 14:53:05BUILDING PLAN REVIEW
 PERMIT: 05070295
 ADD: 1256 PALM BEACH LAKES BLVD
 CONT: MASTER CONTRACTORS
 TEL: (561)502-7209
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 DUPLICATE PLANREVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-12-10 Cont ID  
Sent By rnuquist Date 2006-12-10 Time 13:23 Rev Time 0.00
Received By rnuquist Date 2006-12-10 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-13 Cont ID  
Sent By jwitmer Date 2006-04-13 Time 07:29 Rev Time 2.22
Received By jwitmer Date 2006-04-13 Time 07:09 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-11 Cont ID  
Sent By jwitmer Date 2006-01-11 Time 13:17 Rev Time 2.22
Received By jwitmer Date 2006-01-11 Time 13:17 Sent To PC
Notes
2006-01-11 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070295
 ADD: 1256 PALM BEACH LAKES BLVD
 CONT: MASTER CONTRACTORS
 TEL: (561)712-8898
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
  
 1) COMMENET# 3 FROM THE PREVIOUS REVIEW:
 705.7.1 JOINTS INSTALLED IN OR BE- TWEEN
 FIRE RESISTANT WALLS, FIRE RESIS- TANT
 FLOORS OR FLOOR/ CEILING ASSEMBLIES AND
 FIRE RESISTANT ROOFS OR ROOF/ CEIL- ING
 ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 THE AREA OF CONCERN IS BETWEEN THE
 RATED WALL AND THE ROOF ASSEMBLY.
 705.7.2. AND TABLE 705.7 WILL REQUIRE A
 SYSTEM THAT WILL COMPLY WITH 500 CYCLES
 OF EXPANSION AND CONTRACTION WITHOUT
 FAILURE.
 (UL OR EQUIVALENT) PROVIDE A FLEXIBLE
 JOINT FIRE AND SMOKE ASSEMBLY AT THE
 TENANT SEPERATION BETWEEN WALL A
 ROOF DECK.
  
 2) COMMENT# 4 FROM THE PREVIOUS
 REVIEW,DISCREPANCY BETWEEN A-2 & THE
 MEP-1, THE NEW OFFICE DOORS ARE IN
 DIFFERENT LOCATIONS OR MISSING , PLEASE
 CORRECT.
  
 3) COMMENT 6A) FROM THE PREVIOUS REVIEW,
 6A) PRODUCT APPROVALS, THE ARCH EXTERIOR
 DOORS(01-0226.05) AND STOREFRONT)
 SYSTEMS (00-1220.05)SUBMITTED WILL
 REQUIRE A HURRICANE PROTECTIVE SYSTEM.
 PROVIDE PRODUCT APPROVAL REPORT
 FOR STORM SHUTTERS WITH A FL COVER
 SHEET.
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 6B) YKK EXTERIOR DOOR, SUPPLY THE DADE
 COUNTY NOA MENTIONED IN THE FLORIDA
 REPORT:
 04-0227.02 LARGE MISSLE
 04-0227.03 SMALL MISSLE
 IF THE REPORT THAT WILL BE SUBMITTED IS
 FOR SMALL MISSLE IMPACT, PROVIDE THE
 INFORMATION THAT IS LISTED ABOVE FOR
 STORM SHUTTER REQUIREMENTS.
  
 4)COMMENT 6B) FROM THE PREVIOUS REVIEW,
 6B) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE DOOR SCHEDULE INDICATES DOOR# 3 TO
 BE A HOLLOW CORE METAL CLAD DOOR, WHERE
 AS THE FLOOR PLAN & ELEVATIONS INDICATE
 GLASS DOORS WITH SIDE LIGHTS.
 6C) 2405.2.1 THE FOLLOWING SHALL BE
 CONSIDERED SPECIFIC HAZARDOUS LOCATIONS
 FOR THE PURPOSES OF GLAZING:
 3. GLAZING IN AN INDIVIDUAL FIXED OR
 OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE
 IS WITHIN A 24-INCH (610 MM) RADIUS
 OF THE DOOR IN A CLOSED POSITION
 AND WHOSE BOTTOM EDGE IS LESS THAN
 60 INCHES (1524 MM) ABOVE THE
 FLOOR OR WALKING SURFACE.
  
 5) COMMENT# 7 FROM THE PREVIOUS REVIEW
 THE INTERIOR DEMO PERMIT TO BE
 SATISFIED.COMMENT FROM FIELD INSPECTOR
 ABOUT FIRE DAMAGE, ENGINEERS LETTER
 REQUIRED FOR ROOF FRAMING MEMBERS AND
 DECK.PULLED THE PERMIT 05120051 AND
 FOUND NO REPORT, THIS WAS PART OF THE
 FIELD INSPECTORS REQUIREMENTS!!!!!!!!
  
 6) COMMENT# 8 FROM THE PREVIOUS REVIEW,
 PLANS INDICATE EXISTING HANDICAPPED
 RAMP PROVIDE HEIGHT OF THE EXISTING
 RAMP AND CONFIGURATION. MAY REQUIRE
 UPGRADES, SEE 11-4.8 SLOPE, RISE,
 LANDINGS AND HANDRAILS.
 11-4.8.8 OUTDOOR CONDITIONS. OUTDOOR
 RAMPS AND THEIR APPROACHES SHALL
 BE DESIGNED SO THAT WATER WILL NOT
 ACCUMULATE ON WALKING SURFACES.
 6A)
 THE FRONT OF THE DOLLAR STORE INDICATES
 A RAMP WITH A FORWARD APPROACH ON SHEET
 A-2 WHERE AS SHEET A-3 INDICATES ANOTHER
 DETAIL SHOWING A COMMON LANDING AND 2
 RAMPS AT A 180 DEGREES FROM EACH OTHER.
 THESE 2 RAMPS APPEAR TO HAVE RUNS LONGER
 THAN 6'-0" REQUIRING A RAILING. NO LOWER
 LANDING IS PROVIDED. THIS SAME DETAIL
 INDICATES IN THE LEGEND SCALE 1/4" AND
 N. T. S. "NOT TO SCALE"WITH NO
 DIMENSION PROVIDED FOR THE RUN OF THE
 RAMP.
 6B)
 THE SAME PROBLEMS ARISE ON THE SIDE
 OF THE BUILDING WHERE RAMPS APPEAR NO
 INFORMATION PROVIDED.
 11-4.8.3. CLEAR WIDTH. THE MINIMUM
 CLEAR WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 6C)
 NOTE:
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
  
 7) SEE THE ELECTRICAL REVIEWERS COMMENTS
 THAT DEAL WITH PHOTOCOPIED PLANS,
 ASSUMING WORK OF ONOTHER DESIGN
 PROFESSIONAL,AND AFFIXING ONES SEAL TO
 PLANS THAT WERE NOT PREPARED BY OR UNDER
 THIER SUPERVISING CONTROL. ONE SET OF
 PLANS HAS BEEN RETAINED FOR REVIEW BY
 THE FLORIDA STATE BOARD OF ARCHITECTURE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By jwitmer Date 2005-10-14 Time 15:19 Rev Time 0.77
Received By jwitmer Date 2005-10-14 Time 15:12 Sent To PC
Notes
2005-10-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070295
 ADD: 1256 PALM BEACH LAKES BLVD
 CONT: MASTER CONTRACTORS
 TEL: (561)712-8898
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PLANS NOW INDICATE A TRUE TENENT
 SEPERATION WALL. PROVIDE A 1HR RATED
 WALL ASSEMBLY (UL OR EQUIVALENT)TO THE
 METAL ROOF DECK.704.1.1.
  
 2)PROVIDE THIS INFORMATION ON PLAN.
 704.2.1.4 CORRIDOR PARTITIONS, SMOKESTOP
 PARTITIONS, HORIZONTAL EXIT PARTITIONS,
 EXIT ENCLOSURES, AND FIRE RATED WALLS
 REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A
 MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION.SUCH
 IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED
 SPACES.SUGGESTED WORDING:FIRE AND
 SMOKE BARRIER PROTECT ALL OPENINGS.
  
 3)ND ROOF DECK.(UL OR
 EQUIVALENT) PROVIDE A FLEXIBLE JOINT
 FIRE AND
 SMOKE ASSEMBLY AT THE TENANT SEPERATION
 BETWEEN WALL A
 705.7.1 JOINTS INSTALLED IN OR BETWEEN
 FIRE RESISTANT WALLS, FIRE RESIS- TANT
 FLOORS OR FLOOR/ CEILING ASSEMBLIES AND
 FIRE RESISTANT ROOFS OR ROOF/ CEILING
 ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE REQUIRED
 FIRE RESISTANCE RATING OF THE WALL,
 FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 4) DISCREPANCY BETWEEN THE A-2 & THE
 MEP-1 SHEET THE NEW OFFICE DOORS ARE IN
 DIFFERENT WALLS, PLEASE CORRECT.
  
 5) NEW OFFICE LOOKS LIKE THERE IS A
 KITCHEN AREA, IF SO COMPLY WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 6A) PRODUCT APPROVALS, THE ARCH EXTERIOR
 DOORS AND PANEL WALL SYSTEMS SUBMITTED
 WILL REQUIREA HURRICANE PROTECTIVE
 SYSTEM. PROVIDE PRODUCT APPROVAL REPORT
 FOR STORM SHUTTERS WITH A FL COVER
 SHEET.
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 6B) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE DOOR SCHEDULE INDICATES DOOR# 3 TO
 BE A HOLLOW CORE METAL CLAD DOOR, WHERE
 AS THE FLOOR PLAN & ELEVATIONS INDICATE
 GLASS DOORS WITH SIDE LIGHTS.
 6C) 2405.2.1 THE FOLLOWING SHALL BE
 CONSIDERED SPECIFIC HAZARDOUS LOCATIONS
 FOR THE PURPOSES OF GLAZING:
  
 1. GLAZING IN SWINGING DOORS AND
 FIXED AND SLIDING PANELS OF SLIDING
 (PATIO) DOOR ASSEMBLIES.
  
 2. GLAZING IN DOORS AND WALLS OF
 ENCLOSURES FOR HOT TUBS, WHIRLPOOLS,
 SAUNAS, STEAM ROOMS, BATHTUBS,
 SHOWERS AND OTHER SUCH FACILITIES
 WHERE SUCH GLAZING IS LOCATED 36
 INCHES (914 MM) OR LESS, MEASURED
 HORIZONTALLY, FROM A STANDING OR
 WALKING SURFACE WITHIN THE ENCLOSURE
 AND WHERE THE BOTTOM EDGE OF THE
 EXPOSED GLAZING IS LESS THAN 60
 INCHES (1524 MM), MEASURED
 VERTICALLY, ABOVE SUCH STANDING OR
 WALKING
 SURFACES.
  
 3. GLAZING IN AN INDIVIDUAL FIXED OR
 OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE
 IS WITHIN A 24-INCH (610 MM) RADIUS
 OF THE DOOR IN A CLOSED POSITION
 AND WHOSE BOTTOM EDGE IS LESS THAN
 60 INCHES (1524 MM) ABOVE THE
 FLOOR OR WALKING SURFACE.
  
  
  
 7)BEFORE THIS PERMIT IS ISSUED,TO
 PERMITS HAVE TO BE ISSUED, SEE
 ATTACHMENTS:
 7A) INTERIOR DEMO PERMIT
 7B) EXTERIOR STUCCO
 IN BOTH CASES THE WORK HAS BEEN
 COMPLETED WITHOUT THE BENIFET OF A
 PERMIT!!!!!!!!
  
 8) PLANS INDICATE EXISTING HANDICAPPED
 RAMP PROVIDE HEIGHT OF THE EXISSTING
 RAMP AND CONFIGURATION. MAY REQUIRE
 UPGRADES, SEE 11-4.8 SLOPE, RISE,
 LANDINGS AND HANDRAILS.
 11-4.8.8 OUTDOOR CONDITIONS. OUTDOOR
 RAMPS AND THEIR APPROACHES SHALL
 BE DESIGNED SO THAT WATER WILL NOT
 ACCUMULATE ON WALKING SURFACES.
 NOTE:
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By jwitmer Date 2005-08-08 Time 07:20 Rev Time 1.55
Received By jwitmer Date 2005-08-08 Time 07:20 Sent To  
Notes
2005-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05081225
 ADD: 5809 CHURCHILL CT
 CONT: O/B ALBITE, ODALYS
 TEL: (561)493-4508
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 THE STATE APPROVED SHED THROUGH DCA
 ( DEPARTMENT OF COMMUNITY AFFAIRS) DOES
 NOT REQUIRE SEALED PLANS BUT THE TIE
 DOWN SYSTEMS (ANCHORING PLAN) OR
 FOUNDATION PACKAGE IS REQUIRED TO BE
 RAISED SEAL AND ORIGINAL SIGNATURE. SEE
 THE LETTER FROM DCA NEXT TO BOTTOM
 PARAGRAPH SITE RELATED REQUIREMENTS
 FOUNDATION BY LOCAL AUTHORITY.
  
 FL S S 553 PARTI MANUFACTURED BUILDINGS
 RULE 9B-1PRINTED FROM STATE WEBSITE
 THE MOST FREQUENTLY ASKED QUESTIONS,
 Q/A (3) DEALS WITH THE SAME ISSUE THE
 LOCAL BUILDING DEPARTMENT SITE -RELATED
 INSTALLATION REQUIREMENTS (FOUNDATION)
 ARE SPECIFICALLY AND ENTIRELY RESERVED
 TO THE LOCAL AUTHORITY.
  
 104.3 EXAMINATION OF DOCUMENTS
 ?104.3.1 PLAN REVIEW. THE BUILDING
 OFFICIAL SHALL EXAMINE OR CAUSE TO BE
 EXAMINED EACH APPLICATION FOR A PERMIT
 AND THE ACCOMPANYING DOCUMENTS,
 CONSISTING OF DRAWINGS, SPECIFICATIONS,
 COMPUTATIONS AND ADDITIONAL DATA, AND
 SHALL ASCERTAIN BY SUCH EXAMINATIONS
 WHETHER THE CONSTRUCTION INDICATED AND
 DESCRIBED IS IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE TECHNICAL CODES AND
 ALL OTHER PERTINENT LAWS OR ORDINANCES.
 EXCEPTIONS:
 1. BUILDING PLANS APPROVED PURSUANT TO
 ?553.77(6) FLORIDA STATUTES AND
 STATE-APPROVED MANUFACTURED BUILDINGS
 ARE EXEMPT FROM LOCAL CODES ENFORCING
 AGENCY PLAN REVIEWS EXCEPT FOR
 PROVISIONS OF THE CODE RELATING TO
 ERECTION, ASSEMBLY OR CONSTRUCTION AT
 THE SITE. ERECTION, ASSEMBLY AND
 CONSTRUCTION AT THE SITE ARE SUBJECT TO
 LOCAL PERMITTING AND INSPECTIONS.
  
 2) ONLY 1 SET OF PLAN SUBMITTED. TWO (2)
  
 SETS OF PLANS ARE REQUIRED.
  
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 SEE GENERAL NOTE# 2, ANCHORING SYSTEM TO
 GROUND PER LOCAL CODE (BY DEALER).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 2A) 471.025 PLANS SHALL BE SIGNED, DATED
 AND SEALED BY THE ENGINEER RESPONSIBLE
 FOR THE DESIGN.
 2B) ARCHITECT MISSING CERTIFICATE OF
 AUTHERIZATION,481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) EXTERIOR DOORS
 C) SWING DOORS
 D) EFIS TRIM
 SOME REPORTS HAVE FL COVERSHEET BUT THE
 WRONG BACK UP REPORT (EFCO CORP)
  
 4) A2 PLANS INDICATE OFFICE SPACE AND
 ADDITIONAL STORAGE THAT DOES NOT
 COMMUNICATE WITH THE MERCANTILE AREA?
  
 5) DISCREPANCY BETWEEN A1 & A2, ONE HAS
 A BUILT UP ROOF WHILE THE OTHER THE DECK
 IS LOWER?
  
 6) WHAT TYPE OF OCCUPANCY WILL OCCUPY
 THIS SPACE? IF MERCANTILE 11-7.4
 SECURITY BOLLARDS.
 ANY DEVICE USED TO PREVENT THE REMOVAL
 OF SHOPPING CARTS FROM STORE
 PREMISES SHALL NOT PREVENT ACCESS OR
 EGRESS TO PEOPLE IN WHEELCHAIRS.AN
 ALTERNATE ENTRY THAT IS EQUALLY
 CONVENIENT TO THAT PROVIDED FOR THE
 AMBULATORY POPULATION IS ACCEPTABLE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-04-03 Cont ID  
Sent By dpalmer Date 2006-04-03 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2006-04-03 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-01-06 Cont ID  
Sent By dpalmer Date 2006-01-06 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2006-01-05 Time 15:12 Sent To I
Notes
2006-01-06 00:00:00********** UNSAT ***********
  
  
 1)NOTE: PLEASE KNOW, ELECTRICAL AND
 MECHANICAL AND PLUMBING PLANS ARE NOW
 COMING IN SIGNED,SEALED BY AN ARCHITECT.
 THIS IS ASSUMING THE WORK OF ANOTHER
 DESIGNER. PLEASE SEE THE ORIGINAL
 DESIGNER OF RECORD WHICH WAS AN ENGINEER
 IS STILL SHOWN ON PLANS AND ALSO
 CONTAINS A PHOTOCOPY OF THE ORIGINAL
 SIGNATURE AND SEALED BY SAID ENGINEER OF
 RECORD.
 PLEASE SEE FS 481.221 (5)(6) WHICH
 STATES:
 (5) NO REGISTERED INTERIOR DESIGNER
 SHALL AFFIX, OR PERMIT TO BE AFFIXED,
 HER OR HIS SEAL OR SIGNATURE TO ANY
 PLAN, SPECIFICATION, DRAWING, OR OTHER
 DOCUMENT WHICH DEPICTS WORK WHICH SHE OR
 HE IS NOT COMPETENT OR LICENSED TO
 PERFORM.
  
 (6)NO REGISTERED ARCHITECT SHALL AFFIX
 HER OR HIS SIGNATURE OR SEAL TO ANY
 FINAL CONSTRUCTION DOCUMENT OR
 INSTRUMENT OF SERVICE WHICH INCLUDES
 DRAWINGS, PLANS, SPECIFICATIONS, OR
 ARCHITECTURAL DOCUMENTS WHICH WERE NOT
 PREPARED BY HER OR HIM OR UNDER HER OR
 HIS RESPONSIBLE SUPERVISING CONTROL OR
 BY ANOTHER REGISTERED ARCHITECT AND
 REVIEWED, APPROVED, OR MODIFIED AND
 ADOPTED BY HER OR HIM AS HER OR HIS OWN
 WORK ACCORDING TO RULES ADOPTED BY THE
 BOARD.
  
 ** PLEASE KNOW THE ORIGINAL DESIGNER'S
 OF RECORD HAVE BEEN CONTACTED AND ONE
 COPY OF SAID PLANS ARE BEING RETAINED
 FOR FILE FOR REVIEW BY THE STATE BOARD
 OF ARCHITECT'S.
 THIS HAS BEEN CONFIRMED WITH THE
 BUILDING OFFICAL.
 IT WAS MENTIONED TO THE ELECTRICAL
 CONTRACTOR AND OWNER OF RECORD IN A
 MEETING BEFORE PLANS WERE RE-SUBMITTED
 THE PLANS NEEDED TO GO BACK TO THE
 ORIGINAL DESIGNER OF RECORD FOR CHNAGES
 TO PLANS AND BE SIGNED, DATED AND SEALED
 BY THAT DESIGNER.
  
 *********
 PLEASE SEE THE FOLLOWING COMMENTS, SOME
 FROM PREVIOUS REVIEWS AND SOME FROM THIS
 REVIEW.
  
 1)NOTE: PLEASE SEE ROOM/AREA
 DESIGNATIONS WERE ADDED TO PLANS,
 HOWEVER PLEASE SEE MAIN ELECTRICAL RM IS
 SHOWN AS "STOCKRM". PLEASE SEE
 110.26,408.7, 240.24 ETC WHICH DOES NOT
 PERMIT STORAGE WITH THIS ELECTRICAL
 EQUIPMENT.
  
 2)NOTE: PLEASE CORRELATE PANELS WITH
 RISER DIAGRAM, ONE SHOWS 125A AND OTHERS
 SHOW 100A.
 215.5
 PREVIOUS NOTES.
  
 3)NOTE: PLEASE SEE RISER IS NOW SHOWING
 CONDUCTORS BEING INSTALLED TO THE
 "FUTURE" METERS AND MAINS? THESE WOULD
 NO LONGER BE "FUTURE". PLEASE ADJUST AND
 COMPLETE RISER ACCORDINGLY.
  
 4)NOTE: PLEASE SEE KITCHEN/BREAK AREA
 SHALL HAVE GFI PROTECTION FOR ALL 15/20A
 120V RECEPTS.
  
 5)NOTE: PLEASE SEE FS 553.80(2)(B) WHICH
 IS STILL IN EFFECT.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWERS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 20:53 Rev Time 1.05
Received By dpalmer Date 2005-09-10 Time 20:13 Sent To  
Notes
2005-09-10 00:00:00*********** UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE THERE ARE NUMEROUS CIRCUITS
 ON PLANS WHICH DO NOT CORRELATE.
 PLEASE SEE
 A-5 SHOWN AS SIGN CIR AND SHOWN AS
 RECEPTS ON PLANS.
 PLEASE SEE STORE AREA SHOWS CIRCUITS TO
 PANEL "A" FOR LIGHTING , HOWEVER PANEL
 "A" IF FOR A SEPRATE SPACE.
 PLEASE ALSO SEE 700.12E WHICH REQUIRES
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SE SOME CIRCUITS SHOWN ON PLANS,
 NOTHING IS SHOWN ON PANEL SCHEDULE.
 PLEASE SEE REDLINED PLANS FOR OTHER
 ITEMS.
  
 2)NOTE: PLEASE SEE PLANS STILL MISSING
 ROOM/ AREA DESIGNATIONS ON PLANS.
 OFFICE/STORAGE, BATHS, KITCHENS ETC.
  
 3)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15/20A 125V RECEPTS
 IN KTICHEN AREAS OFNON-DWELLING UNIT
 TO BE GFI/GFI PROTECTED. THIS IS
 REQUIRED WHETHER OR NOT RECEPT SERVES
 COUNTERSPACE.
  
 4)NOTE: PLEASE SEE MIN VA FOR WINDOW
 LINEAR FT. 200 VA PER FT. SCALE SEEMS TO
 INDICATES 22' +/-. 220.12
  
 5)NOTE: PLEASE CORRELATE PANELS ON RISER
 WITH PANEL SCHEDULES. 100A/125A,
 100A/125A??
 215.5
  
 6)NOTE: PLEASE INDICATE CONDUCTORS FROM
 GUTTER TO EACH NEW METER AND FROM METER
 TO MAINS.
 215.5,215.3,240.4,310.16, ETC
 PLEASE BE SURE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. 250.6
  
 7)NOTE: PLEASE SEE RISER INDICATES
 GROUNDING ELECTRODE TO FOOTER STEEL. ??
 THIS SEEMS TO BE AN EXISTING BLDG AND
 FOOTER STEEL WOULD NOT BE REQUIRED TO AN
 EXISTING BLDG, HOWEVER MAY BE DONE.
 IF THIS IS SHOWN, THEN IT WILL BE
 REQUIRED.
 PLEASE SEE THAT 2-GRND RODS WILL BE
 REQUIRED.
 250.50
  
  
 8)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONALS AND PLANS WITH
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
  
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEW(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By dpalmer Date 2005-07-25 Time 13:43 Rev Time 1.25
Received By dpalmer Date 2005-07-25 Time 13:43 Sent To  
Notes
2005-07-25 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 215.5
 PLEASE BES URE TO SEE 700.12E FOR
 CIRCUITING OF EM.EXT LTS.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS SUBMITTED. 400A? 150A?
 215.5
  
 3)NOTE: PLEASE SEE 240.4,310.16 FOR MIN
 SIZE OF FEEDERS TO PANEL "L" WHICH IS
 SHOWN BEING FED FROM 400A OCP.
 PLEASE SEE OTHER TWO FEEDERS TO SUB
 PANELS INDICATE #3 MCM? PLEASE SEE AWG
 FOR SIZES AND DISCRIPTION OF CONDUCTORS.
 THERE IS NO #3 MCM.
  
 4)NOTE: PLEASE SEE 250.122 FOR SIZING OF
 EQUIPMENT GROUNDING CONDUCTORS.
 PLEASE SEE MAIN TO PANEL "L".
  
 5)NOTE: PLEASE SEE PLANS SHALL BE
 SIGNED, DATED AND SEALED BY THE ENGINEER
 RESPONSIBLE FOR DESIGN.
 FS 471.025
  
 6)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED IN TITLE BLOCK FOR ARCHITECT.
 PLEASE SEE SEAL SHALL BE CLEAR AND
 VISABLE AS REQUIRED UNDER FS 481.221.
 PLEASE SEE FAC 61G1-16.004 FOR MISSING
 INFORMATION.
  
 7)NOTE: PLEASE CLARIFY IF SERVICE SHOWN
 IS NEW OR EXSITNG??
 PLEASE SEE ONE MAIN IS SHOWN FOR
 "FUTURE", HOWEVER PANEL IS BEING SHOWN
 AS NEW AT THIS TIME. HOW IS THIS PANEL
 FED IF MAIN/ METER IS "FUTURE"
  
 8)NOTE: PLEASE SEE 250.66 FIR MIN
 GROUNDING ELECTRODE CONDUCTOR.
 2/0MIN.
  
 9)NOTE: PLEASE SHOW ALLELECTRICAL
 EQUIPMENT ON PLANS. ALL MAINS, PANELS
 NEED TO BE SHOWN AT LOCATIONS ON PLANS.
 215.5
  
 10)NOTE: PLEASE SEE AREAS ON PLANS WHERE
 NO ELECTRICAL IS SHOWN? LTS?
  
 11)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
  
 12)NOTE: PLEASE SEE 210.62,220.12 FOR
 MIN "SHOW ROOM" WINDOW RECEPTS REQUIRED.
  
 13)NOTE: PLEASE SEE SOME ITEMS LISTED ON
 PANEL SCHEDULE, HOWEVER THESE ITEMS
 COULD NOT BE LCOATED ON PLANS?
 PARKING LTO LTS, IRRIGATION PUMP ETC.??
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-04-13 Cont ID  
Sent By mwennerg Date 2006-04-13 Time 09:50 Rev Time 0.00
Received By mwennerg Date 2006-04-13 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 13:41 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By mwennerg Date 2005-08-11 Time 10:57 Rev Time 0.00
Received By mwennerg Date 2005-08-11 Time 10:57 Sent To  
Notes
2005-08-11 00:00:00******DENIED******
  
 1) PLEASE SHOW ADDRESS ON BUIDING
 WHETHER NEW OR EXISTING THAT SHALL BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO
 THE BACKGROUND.
  
 2) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHERS THAT MUST BE
 MOUNTED DISTANCES THAT MEET THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 3) PLEASE PROVIDE OCCUPANCY
 CLASSIFICATION.
  
 4) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 18:09 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 18:09 Sent To B
Notes
2007-02-22 18:09:56TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 17:31 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 17:31 Sent To  
Notes
2006-04-05 00:00:00TO "COMM" BD#28
2006-03-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 08:30 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 08:30 Sent To  
Notes
2006-01-09 00:00:00TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 15:43 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 15:43 Sent To  
Notes
2005-12-29 00:00:0012/29/05-(WAS SUBMITTED ON 12/5/05 AS A
 NEW PERMIT# 05120188 IN ERROR. SHOULD
 HAVE BEEN ENTERED AS RESUB. THAT PERMIT#
 HAS NOW BEEN VOIDED), PLANS ARE WAITING
 FOR "COMM BD"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 10:44 Sent To  
Notes
2005-09-08 00:00:00TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 13:13 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 13:13 Sent To  
Notes
2005-08-17 00:00:00TO "Z" BOX FROM "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-08-24 Time 15:48 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 11:06 Sent To  
Notes
2005-07-18 00:00:00TO "COMM" BD#1
2005-07-11 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-04-14 Cont ID  
Sent By pkrauss Date 2006-04-14 Time 09:20 Rev Time 0.00
Received By pkrauss Date 2006-04-14 Time 09:19 Sent To  
Notes
2006-04-14 00:00:00PROVISO:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 PRIOR TO ROUGH INSPECTION:
  
 1.RTU-6 IS NOT INDICATED ON THE
 EQUIPMENT SCHEDULE.PLEASE PROVIDE
 INFORMATION REQUIRED FOR RTU-6 ON THE
 SCHEDULE INDICATE NEW OR EXISTING.
  
 2.RTU-6 - PROVIDE MISSING DUCT SIZE
 FOR THE RETURN AIR.
  
 3.RTU-1 - PROVIDE MISSING DUCT SIZE
 FOR THE RETURN AIR JUMPER.
  
 4.RESPONSE TO COMMENT #3 FROM PREVIOUS
 REVIEW INDICATES A 20 FT LADDER TO BE
 PROVIDED FOR PERMANENT MEANS OF ACCESS.
 PLEASE PROVIDE SUBMITTAL DATA FOR THE
 LADDER AS WELL AS A DETAIL FOR THE
 ATTACHMENT OF THE LADDER TO THE
 BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-04-12 Cont ID  
Sent By hmoser Date 2006-04-12 Time 14:31 Rev Time 0.00
Received By hmoser Date 2006-04-12 Time 14:31 Sent To  
Notes
2006-04-12 00:00:00PLAN DENIED
 1) EQUIPMENT SCHEDULE SHOWS FIVE RTU
 MECHANICAL PLANS SHOW SIX RTU.
 2) MISSING SUPLY DUCT IN THE OFFICE OFF
 RTU #6.
 3) MISSING RETURN AIR DUCT SIZE OFF
 RTU #6
 4) PLEASE PROVIDE RETURN AIR DUCT AND
 GRILL SIZE FOR OFFICE OFF RTU #1
 5) PLEASE PROVIDE TWO COPYS OF ENERGY
 CALCULATIONS WITH PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By pkrauss Date 2005-10-12 Time 06:50 Rev Time 0.40
Received By pkrauss Date 2005-10-12 Time 06:44 Sent To  
Notes
2005-10-12 00:00:00PROVISO:
 RESPONSE TO COMMENT #3 FROM PREVIOUS
 REVIEW INDICATES A 20 FT LADDER TO BE
 PROVIDED FOR PERMANENT MEANS OF ACCESS.
 PLEASE PROVIDE SUBMITTAL DATA FOR THE
 LADDER AS WELL AS A DETAIL FOR THE
 ATTACHMENT OF THE LADDER TO THE
 BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-27 Time 18:32 Rev Time 0.55
Received By pkrauss Date 2005-07-27 Time 18:18 Sent To  
Notes
2005-07-27 00:00:00DENIED:
 1.PLAN SHEET MEP4 MOUNTING DETAIL FOR
 THE RTU.PER 2001 FBC 1511.7, CURB
 SHALL BE A MINIMUM OF 8" ABOVE THE
 FINISHED ROOF.
  
 2.OUTSIDE AIR CALCULATION INDICATES
 3260 CFM REQUIRED, EQUIPMENT SCHEDULE
 INDICATES ONLY 1128 CFM PROVIDED.
  
 3.CLARIFY ACCESS TOEQUIPMENT LOCATED
 ON THE ROOF.PER 2001 FBC(M) 306.5
 PERMANENT ACCESS REQUIRED FOR HEIGHTS
 GREATER THAN 16 FT.
  
 4.ARICHETECT SEAL IS NOT LEGIBLE AS
 REQUIRED BY FAC 61G1-16.004 & FS 481.221
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-14 Cont ID  
Sent By pschmitz Date 2006-04-14 Time 10:52 Rev Time 0.00
Received By pschmitz Date 2006-04-14 Time 10:52 Sent To  
Notes
2006-04-14 00:00:00RE-STAMP

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-14 Cont ID  
Sent By pschmitz Date 2005-10-14 Time 09:52 Rev Time 0.00
Received By pschmitz Date 2005-10-14 Time 09:52 Sent To  
Notes
2005-10-14 00:00:00RESUB FOR ROOF DRAINS AND SCUPPER
 DRAINS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-30 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 10:21 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 10:21 Sent To Z
Notes
2005-07-30 00:00:00PAUL SCHMITZ, PLUMBING & GAS
 PLANS EXAMINER
  
 561-805-6692
 [email protected]
 PLUMBING PLAN REVIEW FBC 2001 DENIED
 (1)
 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER ROOF EDGES,
 ROOF DRAINS SHALL BE INSTALLED AT EACH
 LOW POINT OF THE ROOF.WHERE
 REQUIRED FOR ROOF DRAINAGE, SCUPPERS
 SHALL BE PLACED LEVEL WITH THE ROOF
 SURFACE IN A WALL OR PARAPET.THE
 SCUPPER SHALL BE LOCATED AS DETERMINED
 BY THE ROOF SLOPE AND CONTRIBUTING ROOF
 AREA.
 (2)?1503.4.2 OVERFLOW DRAINS AND
 SCUPPERS. WHERE ROOF DRAINS ARE
 REQUIRED,
 OVERFLOW DRAINS HAVING THE SAME SIZE
 AS THE ROOF DRAINS SHALL BE INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2
 INCHES (51 MM) ABOVE THE LOW POINT OF
 THE ROOF, OR OVERFLOW SCUPPERS SHALL
 BE A MINIMUM OF 4 INCHES (102 MM) IN
 HEIGHT AND SHALL BE PLACED IN WALLS OR
 PARAPETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2 INCHES (51 MM) ABOVE
 THE ROOF SURFACE, EXCLUDING SUMPS, OR
 MORE THAN 4 INCHES (102 MM) ABOVE THE
 ROOF SURFACE AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL
 ANDPARAPET SCUPPERS.OVERFLOW DRAINS
 AND SCUPPERS SHALL ALSO COMPLY WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
 (3)?1503.4.3 SIZING AND DISCHARGE.
 ROOF DRAINS, GUTTERS, SCUPPERS AND
 LEADERS SHALL BE SIZED AND DISCHARGED
 IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING SEC 1106.
 (4)SHT A-2 FLOOR PLAN, DOES NOT MATCH
 SHT MEP-4, PLUMBING FIXTURE LOCATION.
 (5) SHT MEP-4 BACK TO BACK H/C REST RMS.
 DOORS NOT PERMITTED TO SWING IN TO CLEAR
 FLOOR SPACE, SEE FIG 30E FBC 2001 CH-11
 (5)SHT MEP-4, BREAK ROOM SINK:
 SINKS REQUIRED TO BE ACCESSIBLE
 SEC 11-4.24.2HEIGHT 34" FF
 SEC 11-4.24.5 CLEAR FLOOR SPACE:
 30" BY 48"
 SEC 11-24.24.4 SINK DEPTH: 6 1/2" MAX
 SEC 11-24.24.7 FAUCETS: LEVER TYPE.
 (6) BACK FLOW PREVENTERS REQUIRED,
 LOCAL ORDINANCE # 2853-95
 END OF COMMENTS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2005-10-17 Cont ID  
Sent By sgraham Date 2005-10-17 Time 16:00 Rev Time 0.00
Received By sgraham Date 2005-10-17 Time 16:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-09-12 Cont ID  
Sent By mmclean Date 2005-09-12 Time 19:36 Rev Time 0.00
Received By jwitmer Date 2005-10-14 Time 15:11 Sent To  
Notes
2005-09-12 00:00:00DENIED, 2 REQUEST.
 1. NEED TO PROVIDE TWO COPY OF LANDSCAPE
 & PARKING PLANS MEETING THE ZONING
 REQUIREMENTS.
  
 ANY QUESTIONS, PLEASE CALL ANGELLA
 JONES-VANN.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-08-24 Time 15:47 Rev Time 0.00
Received By mmclean Date 2005-08-24 Time 15:47 Sent To  
Notes
2005-08-24 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF LANDSCAPE
 & PARKING PLANS MEETING THE ZONING
 REQUIREMENTS.
  
 ANY QUESTIONS, PLEASE CALL ANGELLA
 JONES-VANN.