2005-07-25 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 1606.1.4SHUTTERS. |
| INSTALLATION/DESIGN INFORMATION |
| REQUIRED.SUBMIT AN INSTALLATION |
| SCHEDULE INCLUDING THE FOLLOWING |
| DETAILS: |
| (A) BUILDING CONSTRUCTION TYPE (EG CBS) |
| (B) BUILDING (OR INSTALLATION) HEIGHT |
| (C) DESIGN PRESSURE FOR EACH OPENING |
| (D) OPENING SIZES |
| (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?) |
| (F) ANCHOR TYPE, SIZE AND SPACING |
| A FORM IS AVAILABLE FROM THIS OFFICE |
| GIVING THE RECOMMENDED INSTALLATION |
| SCHEDULE FORMAT.SUBMIT THE ABOVE |
| INFORMATION WHICH IS REQUIRED FOR |
| REVIEW.A COPY OF THE RECOMMENDED |
| INSTALLATION SCHEDULE FORM IS ATTACHED. |
| |
| 2) THE SUBMITTED STATEWIDE PRODUCT |
| APPROVAL FL1850 REFERS TO DRAWING |
| 03-0135.THE VERSION OF THAT DRAWING ON |
| THE STATEWIDE PRODUCT APPRVAL WEBSITE |
| INCLUDES THE SIGNATURE AND SEAL OF |
| WALTER A. TILLIT JR. P.E.THE TWO |
| COPIES SUBMITTED FOR REVIEW DO NOT |
| INCLUDE THE SIGNATURE AND SEAL AND SO |
| CANNOT BE VERIFIED AS HAVING BEEN |
| PREPARED/REVIEWED BY THE ENGINEER. |
| DOWNLOAD AND SUBMIT TWO COPIES OF |
| DRAWING 03-0135 SO THAT THEY ARE AN |
| EXACT MATCH FOR THAT APPROVED BY THE |
| STATE. |
| |
| 3) SOME THE OPTIONS COVERED BY THE |
| SUBMITTED PRODUCT APPROVALS MAY NOT BE |
| CODE COMPLIANT IF USED FOR THIS PROJECT. |
| THE PRODUCT APPROVAL SHEETS SHALL BE |
| MARKED, AS APPROPRIATE, TO IDENTIFY |
| WHICH PRODUCT OPTIONS/SPANS/FASTENERS |
| AND ANCHORING CONDITIONS ARE TO BE USED. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |
| E-MAIL: [email protected] |