Plan Review Details - Permit 05070247
Plan Review Stops For Permit 05070247
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By mwennerg Date 2005-07-15 Time 14:31 Rev Time 0.00
Received By mwennerg Date 2005-07-15 Time 14:30 Sent To  
Notes
2005-07-15 00:00:00******DENIED******
  
 1) PERMIT APPLICATION REFERENCES FUEL
 PIPING ONLY. A DETAIL OF THE NEW
 GENERATOR IS SHOWN ON THE DRAWINGS.
 SEPARATE SHOP DRAWINGS AND PERMITS FOR
 THE GENERATOR AND FUEL SUPPLY ARE
 REQUIRED. PLEASE PROVIDE ADDITIONAL
 INFORMATION AND CLARIFICATION IN REGARDS
 TO SCOPE OF WORK.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 13:22 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 13:22 Sent To FIRE
Notes
2005-07-08 00:00:00TO "F" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-18 Cont ID  
Sent By pkrauss Date 2005-07-18 Time 08:12 Rev Time 0.55
Received By pkrauss Date 2005-07-18 Time 08:12 Sent To  
Notes
2005-07-18 00:00:00DENIED:
 1.PROVIDE MANUFACTURER'S SUBMITTAL
 DATA FOR THE GENERATOR.
  
 2.PROVIDE ELEVATION TO BOTTOM OF THE
 MUFFLER EXHAUST PIPE RUNNING THROUGH THE
 PARKING GARAGE.
  
 3.PROVIDE DISTANCE PROPERTY LINES.
 SHOW COMPLIANCE WITH 2001 FBC(M)401.5
  
 4.EXHAUST OPENINGS SHALL NOT BE
 DIRECTED ONTO WALKWAYS PER 2001
 FBC(M)401.5.2.PLEASE NOTE, EXHAUST
 SHALL TERMINATE IN SUCH A MANNER THAT IT
 WILL NOT RECIRCULATE INTO THE GARAGE,
 FRESH AIR INTAKES, WINDOWS, DOORS, OR
 VENTILATING SYSTEMS.
  
 5.PLAN INDICATES FUEL PIPING THROUGH
 THE ELECTRICAL VAULT, PLEASE CLARIFY.
  
 6.PLEASE CLARIFY AREA IN WHICH EF-3
 TERMINATES.IS THIS A PARKING AREA?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  