Plan Review Details - Permit 05070236
Plan Review Stops For Permit 05070236
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-30 Cont ID  
Sent By jwitmer Date 2005-07-30 Time 13:22 Rev Time 0.77
Received By jwitmer Date 2005-07-30 Time 13:22 Sent To PC
Notes
2005-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070236
 ADDRESS: 1400 PALM BCH LK BLVD
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1 ) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 2) EXISTING DOOR IS INDICATED AS A
 2'-8" WIDE DOOR. 11-4.13.5 CLEAR WIDTH.
 DOORWAYS SHALL HAVE A MINIMUM CLEAR
 OPENING OF32 INCHES (815 MM) WITH THE
 DOOR OPEN 90 DEGREES, MEASURED BETWEEN
 THEFACE OF THE DOOR AND THE OPPOSITE
 STOP (SEE FIGURE 11-24(A),FIGURE
 11-24(B), FIGURE 11-24(C), AND FIGURE
 11-24(D)).OPENINGSMORE THAN 24
 INCHES (610 MM) IN DEPTH SHALL COMPLY
 WITH 11-4.2.1 AND 11-4.3.3 (SEE FIGURE
 11-24(E)
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-13 Cont ID  
Sent By jleahy Date 2005-07-13 Time 10:52 Rev Time 0.30
Received By jleahy Date 2005-07-13 Time 10:52 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-29 Cont ID  
Sent By mwennerg Date 2005-07-29 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2005-07-29 Time 15:14 Sent To  
Notes
2005-07-29 00:00:00******DENIED******
  
 1) DRAWINGS ARE REQUIRED TO PROVIDE THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. FBC SECTION
 104.2.1.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE HOOD AND
 SUPPRESSION SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-30 Cont ID  
Sent By jwitmer Date 2005-07-30 Time 13:22 Rev Time 0.00
Received By jwitmer Date 2005-07-07 Time 16:23 Sent To  
Notes
2005-07-07 00:00:00TO "BOB" #8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-28 Cont ID  
Sent By prafter Date 2005-07-28 Time 08:32 Rev Time 0.50
Received By prafter Date 2005-07-28 Time 08:32 Sent To FIRE
Notes
2005-07-28 00:00:00MECH.PLAN REVIEW:
  
 A/C CONTRACTOR TO SUBMIT A/C PLANS AND
 EQUIPMENT INFORMATION AT PERMIT TIME.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-30 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 08:56 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 08:56 Sent To B
Notes
2005-07-30 00:00:00SEPERATE FOR GAS

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-23 Cont ID  
Sent By pschmitz Date 2005-07-23 Time 14:45 Rev Time 0.00
Received By pschmitz Date 2005-07-23 Time 14:45 Sent To M
Notes
2005-07-23 00:00:00GAS PERMIT REQUIRED