Plan Review Details - Permit 05070207
Plan Review Stops For Permit 05070207
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-29 Cont ID  
Sent By jwitmer Date 2006-09-29 Time 07:45 Rev Time 1.22
Received By jwitmer Date 2006-09-29 Time 07:45 Sent To PC
Notes
2006-09-29 00:00:009-29-06 REV# 3, OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 07:27 Rev Time 1.11
Received By jwitmer Date 2006-05-08 Time 07:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-25 Cont ID  
Sent By jwitmer Date 2006-01-25 Time 16:24 Rev Time 1.55
Received By jwitmer Date 2006-01-25 Time 16:24 Sent To PC
Notes
2006-01-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070207
 ADD: 3712 BROADWAY
 CONT: K& M COMMERCIAL CONSTRUCTION
 TEL: (561)248-9648
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PERMIT APPLICATION INDICATES WORK IS
 TO BE COMPLETED AT 3712 BROADWAY. WORK
 TO BE COMPLETED AT 3702 BROADWAY.
 CORRECT APPLICATION AND PROPERTY CONTROL
 NUMBER.
  
 2) PROVIDE A SURVEY FOR 3702 BROADWAY.
 THE NORTH SIDE OF BUILDING MAY HAVE
 TABLE 600 ISSUES.WE UNDERSTAND THAT
 ZONING IS ASKING FOR A UNITITY OF TITLE.
 PROVIDE THE BUILDING DEPARTMENT WITH A
 COPY THAT HAS STAMPED BY THE CLERK OF
 THE COURT.
  
 3)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
 THE NOC PROVIDED IS FOR 3712 BROADWAY
 SEE ADDRESS AND PCN. NOC IF WORK HAS NOT
 STARTED WITHIN 90 DAYS OF RECORDING NOC
 BECOMES VOID!
  
 4) COMMENT# 12 FROM THE PREVIOUS REVIEW,
 12) PLANS DO NOT INDICATE FLOOR LEVEL ON
 THE EXTERIOR OF THE EXTERIOR DOORS,
 INDICATE GRADE IN RELATIONSHIP TO FINISH
 FLOOR LEVEL. 11-4.3.2(3) AT LEAST ONE
 ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS AND WITH ALL ACCESSIBLE
 DWELLING UNITS WITHIN THE BUILDING OR
 FACILITY.THE FRONT ENTRY OF THE OFFICE
 AND EACH UNIT MUST NOT HAVE A CHANGE IN
 GRADE GREATER THAN 1/2".
  
 ****CONTRACTOR ISSUE*******
 5) COMMENT# 14 FROM THE PREVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 16:32 Rev Time 1.11
Received By jwitmer Date 2005-08-07 Time 16:26 Sent To  
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070207
 ADD: 3712 BROADWAY
 CONT: K& M COMMERCIAL CONSTRUCTION
 TEL: (561)248-9648
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PERMIT APPLICATION INDICATES WORK IS
 TO BE COMPLETED AT 3712 BROADWAY. WORK
 TO BE COMPLETED AT 3702 BROADWAY.
 CORRECT APPLICATION AND PROPERTY CONTROL
 NUMBER.
  
 2) PROVIDE A SURVEY FOR 3702 BROADWAY.
 THE NORTH SIDE OF BUILDING MAY HAVE
 TABLE 600 ISSUES.
  
 3)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 4)3401.2.2.1 IF THE OCCUPANCY
 CLASSIFICATION OR OCCUPANCY
 SUBCLASSIFICATIONS OF ANY EXISTING
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL
 AND PLUMBING SYSTEMS SHALL BE MADE TO
 CONFORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING
 OFFICIAL.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 7) 1203.1.3 ATTICS NOT USED FOR
 HABITATIONAL PURPOSES SHALL HAVE
 PROVISIONS FOR THE EMISSION OF EXCESS
 HEAT.
  
 8)2309.6 ACCESS TO ATTIC SPACE. ATTIC
 SPACES SHALL BE PROVIDED WITH AN
 INTERIOR ACCESS OPENING NOT LESS THAN
 20X36 INCHES (508X914 MM).ACCESS
 OPENING SHALL BE ACCESSIBLE AND PROVIDED
 WITH A LID OR DEVICE THAT MAY BE
 EASILY REMOVED OR OPERATED.WHEN
 MECHANICAL EQUIPMENT IS TO BE INSTALLED
 IN THE ATTIC, IT SHALL BE INSTALLED IN
 ACCORDANCE WITH ?M306.3 OF FLORIDA
 BUILDING CODE, MECHANICAL.ACCESS IS
 NOT REQUIRED WHEN THE CLEAR HEIGHT
 OF THE ATTIC SPACE, MEASURED AT THE ROOF
 PEAK, IS LESS THAN 24 INCHES (610
 MM).
  
 9) PROVIDE CALCULATIONS:1203.1.4 EXCEPT
 AS OTHERWISE PROVIDED HEREIN, REQUIRED
 WINDOWS SHALLHAVE GLAZED OPENINGS OF
 CLEAR GLASS OF AREA NOT LESS THAN 8% OF
 THE FLOOR AREA OF THE ROOM SERVED.
  
 10) DOORS SEE LABEL "C": 11-4.13.5 CLEAR
 WIDTH. DOORWAYS SHALL HAVE A MINIMUM
 CLEAR OPENING OF32 INCHES (815 MM)
 WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THEFACE OF THE DOOR AND THE
 OPPOSITE STOP (SEE FIGURE 11-24(A),
 FIGURE 11-24(B), FIGURE 11-24(C), AND
 FIGURE 11-24(D)).OPENINGSMORE THAN
 24 INCHES (610 MM) IN DEPTH SHALL COMPLY
 WITH 11-4.2.1 AND 11-4.3.3 (SEE FIGURE
 11-24(E)).
  
 11)11-9.1.2 ACCESSIBLE UNITS, SLEEPING
 ROOMS, AND SUITES. ACCESSIBLESLEEPING
 ROOMS OR SUITES THAT COMPLY WITH THE
 REQUIREMENTS OF ?11-9.2.1TO ?11-9.2.2
 (REQUIREMENTS FOR ACCESSIBLE UNITS,
 SLEEPING ROOMS, ANDSUITES) SHALL BE
 PROVIDED IN CONFORMANCE WITH THE TABLE
 BELOW.INADDITION, IN HOTELS, OF 50
 OR MORE SLEEPING ROOMS OR SUITES,
 ADDITIONALACCESSIBLE SLEEPING ROOMS
 OR SUITES THAT INCLUDE A ROLL-IN SHOWER
 SHALL ALSO BE PROVIDED IN CONFORMANCE
 WITH THE TABLE BELOW.SUCH
 ACCOMMODATIONS SHALL COMPLY WITH THE
 REQUIREMENTS OF ?11-9.2, ?11-4.21,
 AND FIGURE 11-57(A) OR FIGURE 11-57(B).
  
 12) PLANS DO NOT INDICATE FLOOR LEVEL ON
 THE EXTERIOR OF THE EXTERIOR DOORS,
 INDICATE GRADE IN RELATIONSHIP TO FINISH
 FLOOR LEVEL. 11-4.3.2(3) AT LEAST ONE
 ACCESSIBLE ROUTE SHALL CONNECT
 ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS AND WITH ALL ACCESSIBLE
 DWELLING UNITS WITHIN THE BUILDING OR
 FACILITY.
  
 13) 11-4.6.1 MINIMUM NUMBER. PARKING
 SPACES REQUIRED TO BE ACCESSIBLE BY
 11-4.1 SHALL COMPLY WITH ?11-4.6.2
 THROUGH ?11-4.6.5.PASSENGER LOADING
 ZONES REQUIRED TO BE ACCESSIBLE BY
 11-4.1 SHALL COMPLY WITH 11-4.6.5 AND
 11-4.6.6.
  
 14) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 15)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) DOORS
 B) WINDOWS
  
 15) BATHROOMS:1204.2 SURROUNDING
 MATERIALS; THE WALLS & FLOORS OF ALL
 PUBLIC REST- ROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4'-0" ABOVE THE FLOOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
2005-07-07 00:00:00WAITING FOR "COMM" BD

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-06-24 Cont ID  
Sent By dpalmer Date 2007-06-24 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2007-06-24 Time 10:40 Sent To PC
Notes
2007-06-24 10:40:54STAMPED ELEC REV SHEETS E-3 AND 4

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 14:53 Sent To PC
Notes
2007-05-17 15:40:08** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULES HAVE NOW
 REMOVED THE REQUIRED ARC FAULT PROTECTION FROM BREAKERS
 TO A/C UNITS.
 PLEASE CLARIFY THIS AS AFCI PROTECTION IS REQUIRED ON
 ALL 15/20AMP BRANCH CIRCUITS IN BEDROOM/SLEEPING
 ROOMS.
 PLEASE KNOW IF THIS IS INDEED A 2-POLE UNIT, PLEASE
 REVISE PANEL SCHEDULE TO INCLUDE THE 1/3 SPACES AND THE
 2/4 SPACES. ON EACH PANEL.
  
 2) NOTE: PLEASE SEE PREVIOUS PLANS WERE REDLINED AS
 RISER NOTE #2 INDICATES AN *EQUIPMENT GROUNDING
 CONDUCTOR* BEFORE THE FIRST MEANS OF DISCONNECT WHICH
 IS NOT PERMITTED. 250.6, 250.24.
 PLEASE REVISE AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 11:38 Sent To PC
Notes
2006-10-27 11:38:59REV FOR E-3 AND E-4

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 19:36 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 19:24 Sent To PC
Notes
2006-10-25 19:40:04**** UNSAT ******
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS FOR
 REVIEW AND STAMPING.
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-07 Cont ID  
Sent By btrobaug Date 2006-06-07 Time 14:31 Rev Time 1.00
Received By btrobaug Date 2006-06-07 Time 14:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-19 Cont ID  
Sent By dpalmer Date 2006-04-19 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2006-04-19 Time 12:38 Sent To  
Notes
2006-04-19 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE FAC 61G15-23.001
 WHICH RULED IN FEB, 2004 THAT ALL SEALS
 FOR ENGINEERS MAY NO LONGER USE SEALS
 CONTAING THE WORDS "CERTIFICATE" AND
 SHALL OBTAIN NEW SEALS WITH THE WORDING
 OF "LICENSE".. PLEASE KNOW, AND
 EXTENSION WAS GIVEN BY THE STATE TO
 ALLOW PLANS UP TO THE DATE OF 12/31/05 .
 PLEASE KNOW, AS OF JAN 1ST, 2006, PLANS
 MUST USE THE NEW SEAL AND WE CAN NO
 LONGER ACCEPT THE OLD SEAL.
 PLEASE OBTAIN NEW SEAL AND RE- SIGN,
 DATE AND SEAL PLANS.
  
 IT APPEARS OTHER EELCTRICLA COMMENTS
 HAVE BEEN ADDRESSED.
 IF ALL COMMENTS FROM ALL OTHER TRADES
 HAVE BEEN CCORECTED AND ALL OTHER
 REVIEWS PASS, IT MAY BE POSSIBEL FOR THE
 ENGINEER OF RECORD TO SET UP A MEETING
 ATO ACCOMPLISH THIS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-05 Cont ID  
Sent By dpalmer Date 2005-12-05 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2005-12-05 Time 10:48 Sent To  
Notes
2005-12-05 00:00:00***UNSAT 2ND REVIEW *****
  
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NO, ALTHOUGH REPSONSE LTR
 MENTIONS THIS SHALL BE UNDER A SEPARATE
 PERMIT, THE PLANS DO NOT NOTE THIS.
 IF UNDER THIS PERMIT. PLEASE INCLUDE
 WIND LOADING FOR SITE LIGHTING POLES.
 PLEASE SEE THE WIND LOAD CALCS ARE
 REQUIRED AT THIS TIME AND SHALL BE
 REVIWED BY BLDG PLAN REVIEW.
  
 3)NOTE: NOTE #3 NO, PLEASE INCLUDE
 SIZING FOR ALL EXISTING SEC'S.
 215.5
 PLEASE SEE 240.4,310.16
 PLEASE SEE RESPONSE LTR MENTIONS, LOAD
 CALCUALTIONS PROVIDED, HOWEVER EXISTING
 SEC'S COULD NOT BE LOCATED.
  
 4)NOTE: NOTE#4
 ** MOTEL OCCUPANCY**
 PLEASE SUBMIT LOAD CALCULATIONS PER
 2002 NEC.
 PLEASE ALSO SEE LOAD CALCS FOR SERVICE
 ARE TO MEET 220.3,220.10,220.11 ETC.
 PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS
 WHICH ARE NOW SHOWN NEED TO BE SHOWN PER
 NEC.
 PLEASE INCLUDE ALL LOADS OF EXISTING AND
 NEW.
 215.5
  
 5)NOTE:NOTE #5 NO, PLEASE CORRELATE
 LOADS SHOWN ON PANEL PH WITH LOADS
 INDICATED ON PANEL SCHEDULES FOR UNITS.
 215.5
 PLEASE SEE LAODS FOR PANELS,P8,P9 AND
 P10 DO CORRELATE. (4.4, 4.6)
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE:NOTE # 7 NO, PLEASE SEE
 RESPONSE MENTIONS SEE REVISED E-1 AND
 E-4, HOWEVER E-1 INDICATES ARC FAULT FOR
 RECEPTS ONLY. PLEASE SEE "ALL OUTLETS"
 PER PLEASE SEE ARC FAULT PROTECTION
 WILL BE REQUIRED UNDER 2002 NEC 210.12
  
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK.
  
  
 10)NOTE: NOTE #10 OK, HOWEVER NO
 VERIFICATION OF SIZING CAN BE DONE, AS
 SEC'S ARE NOT SHOWN.PLEASE PROVIDE SIZE
 OF EXSITNG TAP/GUTTER BOX. ( LENGTH)?
 SIZE SHALL BE VERIFIED FOR NEW OR
 EXISTING SEC'S.
 366.6
  
 11)NOTE: PLEASE NOTE,, TYPE OF CONDUIT
 FOR FEEDERS TO UNITS IS NOT SHOWN, IF
 PVC AND SCH 80, PLEASE SEE CONDUIT FILL
 WILL EXCEED PERMITTED FILL FROM TABLES
 IN CHAPTER 9. THIS IS ONLY A NOTE:
  
 PLEASE BE SURE TO SEE ANY POSSIBEL
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE BE SURE TO SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-22 Cont ID  
Sent By dpalmer Date 2005-07-22 Time 10:53 Rev Time 2.00
Received By dpalmer Date 2005-07-22 Time 10:53 Sent To  
Notes
2005-07-22 00:00:00************* UNSAT ***********
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G15-23.002, PLEASE SEE MISSING PRINTED
 NAME.
  
 2)NOTE: PLEASE INCLUDE WINDING LOADING
 FOR SITE LIGHTING POLES.
 PLEASE SEE THE WIND LOAD CALCS ARE
 REQUIRED AT THIS TIME AND SHALL BE
 REVIWED BY BLDG PLAN REVIEW.
  
 3)NOTE: PLEASE INCLUDE SIZING FOR ALL
 EXISTING SEC'S.
 215.5
 PLEASE SEE 240.4,310.16
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 2002 NEC. PLEASE SEE HOUSE LOADS ARE
 SHOWN BEING DERATED WITH DWELLING UNIT
 LOADS WHICH IS NOT PERMITTED.
 PLEASE ALSO SEE LOAD CALCS FOR SERVICE
 ARE TO MEET 220.3,220.10,220.11 ETC.
 PLEASE SEE OTHER HOUSE/OFFICE UNIT LOADS
 ARE NOT SHOWN AND/OR ARE NOT INCLUDED IN
 SERVICELOAD CALCS.
 PLEASE INCLUDE ALL LOADS OF EXISTING AND
 NEW.
 215.5
  
 5)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 PANEL PH WITH LOADS INDICATED ON PANEL
 SCHEDULES FOR UNITS.
 215.5
 PLEASE SEE LAODS FOR PANELS,P8,P9 AND
 P10 DO CORRELATE.
  
 6)NOTE: PLEASE SEE MIN CIRCUIT FOR BATHS
 ARE TO MEET 210.52,210.11C3, MUST BE 20A
 AND #12.
  
 7)NOTE: PLEASE SEE ARC FAULT PROTECTION
 WILL BE REQUIRED UNDER 2002 NEC 210.12
 PLEASE SEE "ALL OUTLETS" , SD'S, LTS,
 FANS, RECEPTS ETC ARE TO AHVE ARC FAULT
 PROTECTED CIRCUITS.
  
 8)NOTE: PLEASE A MIN OF 1500 VA SHALL
 APPLY TO LAUNDRY CIRCUIT.
 PLEASE SEE 210.11C2, 220.16B
  
 9)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMENT GROUNDING CONDUCTORS SHALL NOT
 BE INSTALLED UNTIL AFTER THE FIRST MEANS
 OF DISCONNECT.
 PLEASE SEE #3 EG SHOWN FROM GUTTER TO
 NEW METER/ MAIN.
  
 10)NOTE: PLEASE PROVIDE SIZE OF EXSITNG
 TAP/GUTTER BOX.
 SIZE SHALL BE VERIFIED FOR NEW OR
 EXISTING SEC'S.
 366.6
  
 PLEASE BE SURE TO SEE ANY POSSIBEL
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE BE SURE TO SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-18 Cont ID  
Sent By mwennerg Date 2006-05-18 Time 15:51 Rev Time 0.00
Received By mwennerg Date 2006-05-18 Time 15:51 Sent To  
Notes
2006-05-18 00:00:00A SIGN SHALL BE PLACED ON THE EXTERIOR
 PART OF THE STORAGE DOOR INDICATING FIRE
 EXTINGUISHER INSIDE. FIRE EXTINGUISHER
 SHALL BE ACCESSIBLE TO ALL OCCUPANTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By mwennerg Date 2005-08-09 Time 13:04 Rev Time 0.00
Received By mwennerg Date 2005-08-09 Time 13:04 Sent To  
Notes
2005-08-09 00:00:00******DENIED******
  
 1) AN ADDRESS NUMBER IS REQUIRED AND
 MUST BE AT LEAST 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND. IF
 EXISTING OR NEW, PLEASE SHOW ON
 DRAWINGS.
  
 2) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 5) PLEASE SHOW LOCATION OF 2A- 10B,C
 RATED FIRE EXTINGUISHERS.
  
  
 6) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FAC REQUIREMENTS FOR PLANS.
  
 7) PLEASE CORRELATE THE ACTUAL ADDRESS
 WHERE WORK WILL TAKE PLACE WITH THE
 PERMIT APPLICATION.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-01-21 Cont ID  
Sent By pschmitz Date 2006-01-21 Time 10:17 Rev Time 0.00
Received By pschmitz Date 2006-01-21 Time 10:16 Sent To  
Notes
2006-01-21 00:00:00SEPERATE PERMIT FOR GAS.
 INSPECTOR TO CHECK GAS APPLIANCE DATA
 BTU'S.
 ALSO CHECK FOR COMBUSTION AIR.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 14:45 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 14:45 Sent To E
Notes
2007-06-22 14:45:46TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 11:34 Sent To E
Notes
2007-05-14 11:35:06TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:30 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:30 Sent To M
Notes
2006-12-17 13:31:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 09:05 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 09:05 Sent To E
Notes
2006-10-18 09:06:07TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 18:32 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 18:32 Sent To B
Notes
2006-09-08 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 08:52 Sent To  
Notes
2006-06-02 00:00:006/2/06-TAKEN OFF "COMM" BD#60-PLANS ARE
 IN ZONING WHICH IS THE LAST REVIEW
2006-04-12 00:00:00TO "COMM" BD#60
2006-03-23 00:00:00WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-10-17 Time 12:56 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 12:55 Sent To  
Notes
2005-11-16 00:00:00TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-09 Cont ID  
Sent By mwennerg Date 2005-08-09 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2005-07-07 Time 16:20 Sent To  
Notes
2005-07-18 00:00:00TO "COMM" BD#26
2005-07-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-04 Cont ID  
Sent By pkrauss Date 2007-01-04 Time 08:17 Rev Time 0.00
Received By pkrauss Date 2007-01-04 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-25 Cont ID  
Sent By pkrauss Date 2005-12-03 Time 15:14 Rev Time 0.00
Received By pkrauss Date 2005-12-03 Time 10:01 Sent To  
Notes
2006-05-25 00:00:00PLANS APPROVED & STAMPED BY RON REGUEIRO
 12-3-05PHK
2005-12-03 00:00:00ALL COMMENTS FROM PREVIOUS REVIEW HAVE
 BEEN ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-27 Time 07:09 Rev Time 0.55
Received By pkrauss Date 2005-07-27 Time 06:48 Sent To  
Notes
2005-07-27 00:00:00DENIED:
 1.PLAN SHEET M-1 EXHAUST DUCTS
 PENETRATING RATED PARTITIONS SHALL
 COMPLY WITH 2001 FBC(M)607.1.3 #3 ITEMS
 1 THROUGH 4 OR FIRE DAMPERS WILL BE
 REQUIRED.
  
 2.PLEASE PROVIDE ADDTIONAL INFORMATION
 FOR THE LAUNDRY ROOM.PLAN SHEET P-3
 INDICATES GAS WATER HEATER AND DRYERS.
 PROVIDE COMBUSTION AIR CALCULATIONS.
  
 3.INDICATE TERMINATION OF THE DRYER
 EXHAUST.
  
 4.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA/INSTALLATION INSTRUCTIONS
 FOR THE A/C PACKAGE UNITS, WASHERS,
 DRYERS & WATER HEATER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-21 Cont ID  
Sent By pschmitz Date 2006-01-21 Time 09:38 Rev Time 0.00
Received By pschmitz Date 2006-01-21 Time 09:38 Sent To  
Notes
2006-01-21 00:00:00RE-SUB.
 NO WORK IN OFICE AREA

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-06 Cont ID  
Sent By kstevens Date 2005-08-06 Time 14:30 Rev Time 2.33
Received By kstevens Date 2005-08-06 Time 14:30 Sent To  
Notes
2005-08-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-1 TOILET ROOM FOR OFFICE SHALL
 BE ACCESSIBLE PER SECTION 11-4.1.6(1)(B)
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 2. PER TABLE 403.1 A DRINKING FOUNTAIN &
 A SERVICE SINK IS REQUIRED.
 3. SHT A-1 ROOM FINISH SCHEDULE, THE
 WALLS OF ALL PUBLIC RESTROOM SHALL BE
 LINED WITH NONABSORBENT MATERIAL TO
 HEIGHT OF 4' ABOVE THE FLOOR. SECTION
 1204.2. SUBMIT INFORMATION SHOWING
 COMPLIANCE.
 4. ENGINEER SHALL SHOW ALL REQUIRED
 INFORMATION IN THE TITLE BLOCK OF EACH
 SHEET. 61G15-23.002(2) & FS 471.025.
 (PRINTED NAME)
 5. SHT P-2 NO SANT. DRAINAGE PIPING
 SHOWN TO P-4 FIXTURE IN UNIT #3. SECTION
 104.2.1.
 6. SHTS P-2 & P-3 FLOOR DRAIN REQUIRED
 IN LAUNDRY ROOM. SECTION 412.4
 7. SHT P-3 WATER HAMMER ARRESTORS
 REQUIRED AT EACH WASH MACHINE PER
 SECTION 604.9. LOCATE NEXT TO FIXTURES.
 8. SEPARATE GAS PERMIT REQUIRED. SUBMIT
 THE FOLLOWING INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - THIS INCLUDES THE
 SECTION FROM THE METER TO THE FIRST RISE
 IN THE SYSTEM.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-07 Cont ID  
Sent By jroach Date 2006-06-07 Time 11:25 Rev Time 0.00
Received By jroach Date 2006-06-07 Time 11:25 Sent To  
Notes
2006-03-23 00:00:00NEW LANDSCAPE PLANS NOT PREVIOUSLY
 SUBMITTED.