Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-08 Cont ID  
Sent By rregueir Date 2005-07-08 Time 15:32 Rev Time 0.00
Received By rregueir Date   Time   Sent To PC
Notes
2005-07-08 00:00:00----------------PROVISO-----------------
 1)AUXILIARY DRAIN PAN W/ FLOAT SWITCH OR
 SECONDARY DRAIN LINE REQUIRED PER FBC,M
 307.2.3
 2)WIRE TIE-DOWNS A=SHALL NOT INTERFERE
 WITH ACCESS TO SERVICE PANEL ON
 CONDENSING UNIT.
  
 RONALD J REGUEIRO
 561-805-6734