Plan Review Details - Permit 05070004
Plan Review Stops For Permit 05070004
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By alange Date 2005-08-01 Time 15:28 Rev Time 2.00
Received By alange Date 2005-08-01 Time 14:24 Sent To  
Notes
2005-08-01 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 4.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE ARE REQUIRED FOR THE FOLLOWING
 ITEMS:
 ROOFING, EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION AMD STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE.SELECT THE DOOR TO BE USED
 IN THE JELD-WEN PRODUCT APPROVAL BOOK
 SUBMITTED.
  
 5.PLANS SHOW DOUBLE HUNG WINDOWS AND
 PRODUCT APPROVALS ARE FOR SINGLE HUNG
 WINDOWS?
  
 6.BASED ON SBCCI BUILDING VALUATION
 DATA THE PROJECT VALUE HAS BEEN ADJUSTED
 TO $158,075.00ADDITIONAL PERMIT FEES
 ARE DUE.
  
 7.MINIMUM FOOTING DEPTH BELOW GRADE ON
 A MONOLITHIC FOUNDATION SHALL BE 12"
 FBC 1804.1.3
  
 8.SMOKE DETECTOR SHALL COMPLY WITH FBC
 905.2.
  
 9.ALL PAGES SIGN BY THE ENGINEER SHALL
 BE SIGNED, SEALED AND DATED FS 471.025
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 07:36 Rev Time 1.50
Received By dpalmer Date 2005-07-14 Time 20:50 Sent To M
Notes
2005-07-15 00:00:00********** UNSAT ******************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 NO ONLY RECEPTS WITHIN 6FT OF SINK AS
 NOTED ON PLANS.
 THAT CODE CHANGED FROM THE 1993 TO 1996
 NEC.
 ALL MUST HAVE GFI PROTECTION.
  
 3)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 4)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 8-1.4.2
  
 6)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE NUMEROUS RECEPTS MISSING.
 PLEASE ALSO SEE SOME RECEPTS WHICH
 APPEAR TO BE SHOWN OUTSIDE OF WALLS AND
 OUTSIDE HOUSE?
  
 7)NOTE: PLEASE SEE 220V OUTLET WHICH IS
 SHOWN IN REAR KITCHEN WHICH IS NOT
 LISTEDON PANEL SCHEDULE OR LOAD
 CALCULATIONS.?
 215.5
  
 8)NOTE: PLEASE SEE PLANS INDICATE
 STACKABLE WASHER/DRYER UNITS, HOWEVER
 PANEL SCHEDULES SHOW INDIVIDUAL UNITS??
 PLEASE CORRELATE.
 215.5
  
 9)NOTE: PLEASE SEE PANEL SCHEDULES AND
 PLANS INDICATE MULTIPLE A/C SYSTEMS,
 HOWEVER ONLY ONE IS FIGURED IN LOADS
 CALCULATIONS.
 220.31
  
 10)NOTE: PLEASE 424.3 FOR MIN OCP FOR
 AHU'S. 125%
  
 11)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS
 TWO CIRCUITS FOR GEN LIGHTING WHICH
 SHOWS LOADS EXCEEDING BRANCH CIRCUIT
 RATING AND RATING OF AWG.
 240.4,310.16,220.3 ETC
 4AND 5 KW ON 15A CIRCUIT(S).
  
 12)NOTE: PLEASE LIST ALL ARC FAULT
 PROTECTED CIRCUITS PER 2002 NEC 210.12.
 THESE ARE BE LISTED ON PANEL SCHEDULE.
 215.5
  
 13)NOTE: PLEASE SEE MISSING CONDUCTORS
 FROM METER TO MAIN DISCONNECT AND MAIN
 DISC TO PANEL.
 215.5,310.15, 240.4.
 PLEASE ALSO SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISCONNECT
 TO PANEL.250.24,250.110,250.122
  
 14)NOTE: PLEASE SE GARAGE DOOR OPENER
 SHOWN ON PLANS, HOWEVER NOT LISTED ON
 PANEL SCHEDULE OR LOAD CALCS?
 220.31, 215.5
  
 15)NOTE: PLEASE KNOW, PLANS WHICH
 CONTAIN A TITLE BLOCK FROM AN ENGINEER
 OR ARCHITECT MUST BE SIGNED, DATED AND
 SEALED BY SAID ENGINEER OR ARCHITECT.
 FS 471.025,481.221
  
 16)NOTE: PLEASE SEE MISSING HALL RECEPT
 AS REQUIRED PER 210.52H
  
 17)NOTE: PLEASE SEE TWO RANGES/STOVES
 BEING SHOWN ON PLANS, HOWEVER ONLY ONE
 IS SHOWN ON PANEL SCHEDULE/LOAD
 CALCULATIONS.
 215.5
  
 18)NOTE: PLEASE SEE ZONING COMMENTS
 PERTAINING TO SECOND KITCHEN NOT BEING
 PERMITTED.
 THIS WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE KNOW, DUE TO THE EXTENT OF
 ELECTRICAL COMMENTS ETC, ONE COPY OF
 SAID ELECTRICAL PLANS SHALL BE RETAINED
 FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
2005-07-14 00:00:00IN ELEC FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 09:59 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 09:59 Sent To E
Notes
2005-07-14 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By alange Date 2005-08-01 Time 15:28 Rev Time 0.00
Received By alange Date 2005-07-01 Time 17:13 Sent To  
Notes
2005-07-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By hmoser Date 2005-07-20 Time 17:04 Rev Time 0.00
Received By hmoser Date 2005-07-20 Time 17:10 Sent To P
Notes
2005-07-20 00:00:00 
  
 PLAN DENIED
 PLEASE REFER TO SECTION 104.2 FBC
 DRAWINGS AND SPECIFICATIONS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-23 Cont ID  
Sent By hmoser Date 2005-07-20 Time 17:10 Rev Time 0.50
Received By jleech Date 2005-07-23 Time 10:46 Sent To B
Notes
2005-07-23 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE 15.
 2.PLUMBING LINE DRAWING NOT TO CODE.
 SUBMIT RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By mmclean Date 2005-07-13 Time 16:56 Rev Time 0.00
Received By mmclean Date 2005-07-13 Time 16:56 Sent To I
Notes
2005-07-13 00:00:00DENIED,
 1. MUST PROVIDE THE DIMENSION FOR THE
 NEW DRIVEWAY & WALKWAY (LENGTH & WIDTH).
  
 **NOTE: MUST MAINTAIN 1000SQ FT OR 75%
 OF LANDSCAPE WITHIN THE 25FT FRONT
 SETBACK**
  
 2. CAN ONLY HAVE 1 COOKING FACILITY FOR
 A SINGLE FAMILY HOUSE.MUST REMOVE ONE
 OF THE COOKING FACILITY. (MF14 - MUST
 HAVE 6000 SQ FT FOR ONE OR TWO
 DWELLINGS).
 3. MUST MEET THE 25FT FRONT SETBACK.
 FRONT PORCH MUST BE REDUCED OR STRUCTURE
 MOVED BACK TO MEET THE 25FT FRONT
 SETBACK.
 4 A/C EQUIPEMENT ETC CAN ONLY ENCROACH
 4FT INTO ANY SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720