2005-07-15 00:00:00 | ********** UNSAT ****************** |
| |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| NO ONLY RECEPTS WITHIN 6FT OF SINK AS |
| NOTED ON PLANS. |
| THAT CODE CHANGED FROM THE 1993 TO 1996 |
| NEC. |
| ALL MUST HAVE GFI PROTECTION. |
| |
| 3)NOTE: PLEASE SHOW GROUNDING ELETRODE |
| SYSTEM PER 250.50. FOOTER STEEL/COLD |
| WATER/ ETC. SIZE ALL PER 250.66 |
| |
| 4)NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 5)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2 |
| 8-1.4.2 |
| |
| 6)NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| PLEASE SEE NUMEROUS RECEPTS MISSING. |
| PLEASE ALSO SEE SOME RECEPTS WHICH |
| APPEAR TO BE SHOWN OUTSIDE OF WALLS AND |
| OUTSIDE HOUSE? |
| |
| 7)NOTE: PLEASE SEE 220V OUTLET WHICH IS |
| SHOWN IN REAR KITCHEN WHICH IS NOT |
| LISTEDON PANEL SCHEDULE OR LOAD |
| CALCULATIONS.? |
| 215.5 |
| |
| 8)NOTE: PLEASE SEE PLANS INDICATE |
| STACKABLE WASHER/DRYER UNITS, HOWEVER |
| PANEL SCHEDULES SHOW INDIVIDUAL UNITS?? |
| PLEASE CORRELATE. |
| 215.5 |
| |
| 9)NOTE: PLEASE SEE PANEL SCHEDULES AND |
| PLANS INDICATE MULTIPLE A/C SYSTEMS, |
| HOWEVER ONLY ONE IS FIGURED IN LOADS |
| CALCULATIONS. |
| 220.31 |
| |
| 10)NOTE: PLEASE 424.3 FOR MIN OCP FOR |
| AHU'S. 125% |
| |
| 11)NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| TWO CIRCUITS FOR GEN LIGHTING WHICH |
| SHOWS LOADS EXCEEDING BRANCH CIRCUIT |
| RATING AND RATING OF AWG. |
| 240.4,310.16,220.3 ETC |
| 4AND 5 KW ON 15A CIRCUIT(S). |
| |
| 12)NOTE: PLEASE LIST ALL ARC FAULT |
| PROTECTED CIRCUITS PER 2002 NEC 210.12. |
| THESE ARE BE LISTED ON PANEL SCHEDULE. |
| 215.5 |
| |
| 13)NOTE: PLEASE SEE MISSING CONDUCTORS |
| FROM METER TO MAIN DISCONNECT AND MAIN |
| DISC TO PANEL. |
| 215.5,310.15, 240.4. |
| PLEASE ALSO SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN DISCONNECT |
| TO PANEL.250.24,250.110,250.122 |
| |
| 14)NOTE: PLEASE SE GARAGE DOOR OPENER |
| SHOWN ON PLANS, HOWEVER NOT LISTED ON |
| PANEL SCHEDULE OR LOAD CALCS? |
| 220.31, 215.5 |
| |
| 15)NOTE: PLEASE KNOW, PLANS WHICH |
| CONTAIN A TITLE BLOCK FROM AN ENGINEER |
| OR ARCHITECT MUST BE SIGNED, DATED AND |
| SEALED BY SAID ENGINEER OR ARCHITECT. |
| FS 471.025,481.221 |
| |
| 16)NOTE: PLEASE SEE MISSING HALL RECEPT |
| AS REQUIRED PER 210.52H |
| |
| 17)NOTE: PLEASE SEE TWO RANGES/STOVES |
| BEING SHOWN ON PLANS, HOWEVER ONLY ONE |
| IS SHOWN ON PANEL SCHEDULE/LOAD |
| CALCULATIONS. |
| 215.5 |
| |
| 18)NOTE: PLEASE SEE ZONING COMMENTS |
| PERTAINING TO SECOND KITCHEN NOT BEING |
| PERMITTED. |
| THIS WILL HAVE A DIRECT AFFECT ON |
| ELECTRICAL PLANS. |
| |
| PLEASE KNOW, DUE TO THE EXTENT OF |
| ELECTRICAL COMMENTS ETC, ONE COPY OF |
| SAID ELECTRICAL PLANS SHALL BE RETAINED |
| FOR FILE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
2005-07-14 00:00:00 | IN ELEC FOR REVIEW. |