Plan Review Details - Permit 05061737
Plan Review Stops For Permit 05061737
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 09:40 Rev Time 0.50
Received By btrobaug Date 2005-08-01 Time 09:07 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By btrobaug Date 2005-07-21 Time 11:27 Rev Time 0.50
Received By btrobaug Date 2005-07-21 Time 10:49 Sent To PC
Notes
2005-07-21 00:00:00 
 PLEASE PROVIDE A PANEL DESIGNATION FOR
 THE CIRCUITS OF ORIGIN, BRANCH CIRCIUT
 NUMBERS AT THE POLES.
 ALSO PROVIDE LOAD CALCULATIONS FOR THE
 PANEL BEING USED INDICATING EXISTING AND
 PROPOSED LOADS.
  
 THE PERSON RESPONSIBLE FOR THE PLAN MUST
 PRINT NAME AND SIGN PLANS PER 104.2.1
 FBC. IF DESIGN PROFESSIONAL IS
 RESPONSIBLE SEE 471 OR 481 FS, WHICHEVER
 APPLIES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 13:47 Sent To E
Notes
2005-07-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-29 Cont ID  
Sent By adarroug Date 2005-06-29 Time 08:04 Rev Time 0.00
Received By adarroug Date 2005-06-29 Time 08:04 Sent To E
Notes
2005-06-29 00:00:00TO "E" BOX