Plan Review Details - Permit 05061533
Plan Review Stops For Permit 05061533
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-05 Cont ID  
Sent By jgomez Date 2006-04-05 Time 10:19 Rev Time 0.50
Received By jgomez Date 2006-04-05 Time 07:49 Sent To  
Notes
2006-04-05 00:00:00ENERGY CALCS AND ATRIUM DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-14 Cont ID  
Sent By jgomez Date 2006-03-14 Time 17:40 Rev Time 0.50
Received By jgomez Date 2006-03-14 Time 17:40 Sent To  
Notes
2006-03-14 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENERGY CALCULATIONS SUBMITTED SHOW
 THAT CREDIT IS TAKEN FOR CEILING FANS.
 REVISE ELECTRICAL PLANS AS REQUIRED TO
 SHOW CEILING FANS IN ALL ROOMS. SEE
 TABLE 6-6 OF CHAPTER 13 FBC 2001 FOR
 MINIMUM NUMBER AND SIZE OF CEILIG FANS
 REQUIRED FOR EACH ROOM. SHOW SIZE AND
 NUMBER REQUIRED IN ELECTRICAL PLAN.
  
 2- ARCHITECT SIGNED AND SEALED PRODUCT
 APPROVAL FOR ATRIUM DOOR. ARCHITECT IS
 NOT ALLOWED TO SIGN AND SEAL DOCUMENTS
 THAT HE DIDN'T DESIGNED OR PRODUCED
 UNDER HIS SUPERVISION. ARCHITECT TO SEE
 FLORIDA ADMINISTRATIVE CODE. RE-SUBMIT
 AS REQUIRED.
  
 NOTE:
 PLANS FOR THIS HOUSE WERE APPROVED UNDER
 FBC 2001, NOT FBC 2004. CITY AMENDMENTS
 TO FBC 2004 IS THE CODE THAT REQUIRES
 DESIGNER OF RECORD TO REVIEW AND APPROVE
 IN WRITTING (NOT SIGN AND SEAL) ALL
 PRODUCT APPROVALS.
  
 3- CONTRACTOR TO APPLY FOR STORM
 SHUTTERS PERMIT AS AGREED ON PROVISO AS
 SOON AS POSSIBLE TO AVOID CONFLICT OR
 DELAYS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-21 Cont ID  
Sent By jgomez Date 2005-12-21 Time 16:57 Rev Time 0.50
Received By jgomez Date 2005-12-21 Time 16:56 Sent To PC
Notes
2005-12-21 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED TO APPLY FOR STORM SHUTTERS
 UNDER A SEPARATE PERMIT AS AGREED ON
 PROVISO. APPLY AS SOON AS POSSIBLE TO
 AVOID DELAYS OR CONFLICTS GIVEN THE
 AMOUNT OF PERMIT APPLICATIONS THE CITY
 IS RECEIVING AT THIS TIME.
  
 2- ENERGY CALCULATIONS SUBMITTED ARE FBC
 2004 FORMS. PLANS WERE REVIEWED UNDER
 FBC 2001. REVISED AS REQUIRED. NEED FBC
 2001 FORMS.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR
 ATRIUM DOOR. SEE SPECIFICATIONS ON PLANS
 FOR SIZE AND SWING DIRECTION OF DOOR.
  
 4- OWES $70.00 FOR REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-07-20 Cont ID  
Sent By jgomez Date 2005-07-20 Time 11:52 Rev Time 2.00
Received By jgomez Date 2005-07-20 Time 11:51 Sent To PC
Notes
2005-07-19 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER SEPARATE PERMIT.
 2- NEED WORST CASE SCENARIO ENERGY CALCS
 3- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT FRONT PORCH TO MATCH
 DETAILS 4/D1 AND 5/D1.
 4- REVISE NAIL SIZE FOR HUS26 CONNECTOR.
 5- SPECIFY SIZE AND ANCHORS FOR WINDOW
 MULLION AT GREAT ROOM LARGE WINDOWS.
 6- RE-SUBMIT PRODUCT APPROVAL FOR:
 A) 1 HR FIRE RATED ATRIUM DOOR ASSEMBLY
 B) FIXED WINDOWS.
 C) SINGLE HUNG WINDOWS.
 D) ROOF TILE.
 E) LARGE WINDOW MULLION AT GREAT ROOM.
 7- PROVIDE CLEAR DOOR/WINDOW SCHEDULE.
 DON'T MIX DOOR AND WINDOW SYMBOLS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 20:26 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 20:25 Sent To PC
Notes
2006-02-03 00:00:00REDLINED;
  
 GRND ROD SHALL BE A MIN OF 8' 250.52A5

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 16:29 Rev Time 0.33
Received By dpalmer Date 2005-07-06 Time 15:47 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 18:25 Sent To B
Notes
2006-03-21 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-14 Cont ID  
Sent By adarroug Date 2006-03-14 Time 13:59 Rev Time 0.00
Received By adarroug Date 2006-03-14 Time 13:59 Sent To B
Notes
2006-03-14 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:57 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 14:08 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 14:08 Sent To B
Notes
2005-11-15 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 10:09 Sent To E
Notes
2005-07-06 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By jgomez Date 2005-07-20 Time 11:57 Rev Time 0.00
Received By jgomez Date 2005-06-24 Time 13:59 Sent To  
Notes
2005-06-24 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By prafter Date 2005-07-11 Time 12:04 Rev Time 0.50
Received By prafter Date 2005-07-11 Time 12:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By jleech Date 2005-07-06 Time 17:07 Rev Time 0.25
Received By jleech Date 2005-07-06 Time 17:07 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-05 Cont ID  
Sent By mmclean Date 2005-07-05 Time 13:51 Rev Time 0.00
Received By mmclean Date 2005-07-05 Time 13:51 Sent To I
Notes
***NONE***