Plan Review Details - Permit 05061479
Plan Review Stops For Permit 05061479
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 12:57 Rev Time 1.00
Received By alange Date 2005-09-19 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-16 Cont ID  
Sent By alange Date 2005-08-16 Time 07:29 Rev Time 0.75
Received By alange Date 2005-08-16 Time 07:14 Sent To  
Notes
2005-08-16 00:00:00DENIED
  
 2.FBC 1804.1.3 THE BOTTOM OF
 FOUNDATIONS SHALL EXTEND NO LESS THAN
 12"BELOW FINISH GRADE.
  
 3.MIAMI-DADE PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.WINDOW AT TUB AREA SHALL HAVE SAFTEY
 GLAZING.FBC 2405.2.1
  
 5.SEE SETBACK NOTES FROM ZONING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By alange Date 2005-07-28 Time 15:43 Rev Time 1.50
Received By alange Date 2005-07-28 Time 15:43 Sent To  
Notes
2005-07-28 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.FBC 1804.1.3 THE BOTTOM OF
 FOUNDATIONS SHALL EXTEND NO LESS THAN
 12"BELOW FINISH GRADE.
  
 3.MIAMI-DADE PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.WINDOW AT TUB AREA SHALL HAVE SAFTEY
 GLAZING.FBC 2405.2.1
  
 5.SEE SETBACK NOTES FROM ZONING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-04-20 Cont ID  
Sent By dpalmer Date 2006-04-20 Time 07:58 Rev Time 0.00
Received By dpalmer Date 2006-04-20 Time 07:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-18 Cont ID  
Sent By dpalmer Date 2006-04-18 Time 10:43 Rev Time 0.00
Received By dpalmer Date 2006-04-18 Time 09:00 Sent To PC
Notes
2006-04-18 00:00:00********** UNSAT **********
  
 PLEASE SEE THE FOLLOWING COMMENTS AS
 PLANS ARE COMING IN WITH A COMPLETE;Y
 DIFFERENT RISER FROM PREVIOUS PLANS
 SUBMITTED.
  
  
 1) NOTE: PLEASE BE SURE SEAL FROM
 ARCHITECT IS CLEAR AND VISABLE WITH ALL
 INFORMATION ON SIAD SEAL. PLEASE SEE
 SEAL IS UNREADABLE AT THIS TIME.
 FS 481.221,FAC 61G1-16.003
  
 2) NOTE: PLEASE CORRELATE RISER WITH NEW
 PANEL "B". (MISPRINT ON RISER.
 215.5
  
 3) NOTE: PLEASE SEE A NEW PANEL IS BEING
 SHOWN FROM EXISTING PLANS WHICH NOW
 SHOWS PANELS BEING SUB-FED FROM THIS NEW
 PANEL, HOWEVER OCP CAN NOT VERIFIED AT
 THIS TIME AND NO PANEL SCHEDULE WAS
 SUBMITTED FOR THIS NEW PANEL.
 215.5
 PLEASE PROVIDE PANEL SCHEDULE AND
 INDICATE ALL NEW OCP FOR PANELS "B" AND
 PANEL "OLD EXISTING".
 PLEASE LABEL ALL PANELS.
  
 4) NOTE: PLEASE SEE "OLD" PANEL IS SHOWN
 AS 50A ON RISER AND 60A ON PANEL
 SCHEDULE?
 215.5
  
 5) NOTE: PLEASE SHOW THE LOCATION OF THE
 NEW SERVICE ON PLANS. METER/MAIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 18:19 Rev Time 0.30
Received By dpalmer Date 2005-09-09 Time 18:19 Sent To P
Notes
2005-09-09 00:00:00****** PROVISO/ REVISION ************
  
 1)NOTE: PLEASE SHOW THE SERVICE ENTRANCE
 CONDUCOTR AND SIZEOF RISER.
 240.4,310.15B6,310.16,215.5
  
 2)NOTE: PLEASE CORRELATE FEEDERS ON
 RISER TO EXSITNG PANEL "A" WITH FEEDERS
 SHOWN ON NEW MCB PANEL.
 PLEASE SEE ONE SHOWS #2 AND THE OTHER AS
 #1.
  
 PLEASE SUBMIT THE ABOVE ALONG WITH ANY
 OTHER REVISIONS, BEFORE ANY ROUGH
 ELECTRICAL INSPECTIONS ARE CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 19:15 Rev Time 0.00
Received By dpalmer Date 2005-09-08 Time 19:05 Sent To P
Notes
2005-09-08 00:00:00****** PROVISO/ REVISION ************
  
 1)NOTE: PLEASE SHOW THE SERVICE ENTRANCE
 CONDUCOTR AND SIZEOF RISER.
 240.4,310.15B6,310.16,215.5
  
 2)NOTE: PLEASE CORRELATE FEEDERS ON
 RISER TO EXSITNG PANEL "A" WITH FEEDERS
 SHOWN ON NEW MCB PANEL.
 PLEASE SEE ONE SHOWS #2 AND THE OTHER AS
 #1.
  
 PLEASE SUBMIT THE ABOVE ALONG WITH ANY
 OTHER REVISIONS, BEFORE ANY ROUGH
 ELECTRICAL INSPECTIONS ARE CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 *** UNSAT ***
  
 PLEASE SEE PLANS NOT SEALED BY ARCHITECT
 FS 481.221

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2005-08-09 Time 15:05 Sent To P
Notes
2005-08-09 00:00:00*********** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE ZONING COMMENTS,
 PLEASE SEE BLDG COMMENTS IN REFERENCE TO
 SUREVEY. SURVEY IS REQUIRED TO BE
 SIGNED, DATED AND SEALED . MUST CONTAIN
 ORIGINAL SIGNATURE, ALL LICENSE
 INFORMATION FOR COMAPNY ETC.
 FS 472.025,471.021,FAC 61G17-7.002
 PLEASE SEE SURVEY SUBMITTED CONTAINS A
 RAISED SEAL OVER A PHOTOCOPIED
 SIGNATURE.
  
 2)NOTE: PLEASE SEE NOTES IN TWO
 LOCATIONS ON PLANS MENTIONS SERVICE TO
 BE UPGRADE "IF" REQUIRED. PLEASE SEE
 PLANS NOW SUBMITTED INDICATE A NEW
 SERVICE BEING INSTALLED?
 PLEASE SHOW NEW SEC'S IN RISER AND SIZE
 OF RISER.
 215.5,310.15B6,310.16, ETC.
  
 3)NOTE: PLEASE SEE RISER NOW SHOWS AN
 "EQUIPMENT GROUNDING" CONDUCTOR FROM
 METER TO MAIN. PLEASE SEE 250.6,250.24,
 AN "EQUIPMENT GROUNDING" CONDUCTOR IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 4)NOTE:PLEASE SEE FBC CHAPTER 34,
 EXSITING HOUSE SHOWS NEW SD'S, HOWEVER,
 PLEASE SEE ALL EXISTING LOCATION WHICH
 REQUIE GFI UNDER THE 2002 NEED TO BE
 SHOWN. (BATHS) ETC.
 210.8
  
 5)NOTE: PLEASE SEE 210.52D,210.11C3, ALL
 BATH DEDICATED CIRCUITS ARE REQUIRED TO
 BE 20A AND #14. PLEASE SEE #14, 15A
 SHOWN.
  
 6)NOTE: PLEASE SEE SD'S ARE STILL BEING
 NOTED TO BE CIRCUITED TO KITCHEN AND
 BATH LT CIRCUITS.
 PLEASE KNOW THAT ALL SD'S ARE REQUIRED
 TO BE WIRED "INLINE". PLEASE ALSO SEE
 THAT UNDER THE 2002 NEC 210.12, THEY ARE
 ALSO REQUIRED TO HAVE ARC FAULT
 PROTECTION. ARC FAULT PROTECTION IS
 NOTED ON PLANS, HOWEVER IF THE SD'S ARE
 WIRED TO KIT/BATH LIGHTING CIRCUITS,
 THIS WOULD MOST LIKLEY REQUIRED RE-WIRE
 OF THOSE EXISTING CIRCUITS IN ORDER TO
 PROVIDE ARC FAULT PROTECTION.
 PLEASE CALL TO GO OVER THIS SCENERIO.
  
 7)NOTE: PLEASE SEE A COPY OF FS
 553.80(2)(B) IS NOW ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONAL. PLEASE
 SEE THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE SURE TO SEE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By dpalmer Date 2005-07-11 Time 18:28 Rev Time 1.00
Received By dpalmer Date 2005-07-11 Time 18:28 Sent To P
Notes
2005-07-11 00:00:00************ UNSAT ***************
  
 1)NOTE: PELASE SEE ZONING COMMENTS
 PERTAINING TO MIN SET-BACKS REQUIRED.
 PLEASE SEE THIS WILL AFFECT ALL PLANS
 FOR ALL TRADES.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER DIAGRAM.
 PLEASE SEE PANEL "B" SHOWS # 1 ON NEW
 MDP AND 1/0'S ON RISER.
 PLEASE SEE NEW PANEL "B" IS SHOWN AS
 PANEL "E" ON RISER.
 PLEASE ALSO SEE LABELING OF PANELS ON
 LOAD CALCULATIONS.
 215.5
  
 3)NOTE: PLEASE SEE PLANS ARE NOTED TO
 MENTION "UPGRADE EXISTING ELECTRICAL
 SERIVCE IF REQUIRED".
 PLEASE SEE THAT DETERMINATIONIS TO BE
 MADE AT THIS TIME. PLEASE INDICATE SIZE
 OF EXISTING METER-CAN,SEC'S IN RISER AND
 CONDUCTORS FROM METER TO NEW MCB PANEL.
 PLEASE SEE 310.16,310.15B6,240.4 ETC.
 215.5
  
 4)NOTE: PLEASE SEE LOAD CALCULATIONS ARE
 TO DONE PER 220.31B FOR ADDITIONS TO
 EXSITING.
 PLEASE ALSO SEE A/C LOADS MUST BE
 FIGURED ON LARGEST LOADS NOT ON SMALLER
 OF THE TWO BETWEEN AHU(HEAT) AND CU.
 PLEASE SEE A/C LOADS FOR PANEL "B" AND
 SERVICE WERE TAKEN FROM LOWER COOLING
 LOADS. PLEASE SEE 220.31B, 65% MAY NOT
 BE TAKEN FOR A/C LOADS. MUST BE 100%.
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDTIONS TO EXSITING DWELLINGS. PLEASE
 SHOW ALL EXISTING OR NEW SD'S AND GFI'S
 TO MEET 2002 NEC AND NFPA-72 IN EXISTING
 DWELLING.
  
 6)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 7)NOTE: PLEASE SEE ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE ARE TO BE GFI/GFI
 PROTECTED. 210.8A6
  
 8)NOTE: PLEASE SEE ONLY ONE SMALL
 APPLIANCE CIRCUIT INDICATED ON PANEL
 SCHEDULE. PLEASE SEE 210.52B1, 210.11C1
 FOR A MIN OF TWO AND A MIN OF 1500VA PER
 CIRCUIT.
  
 9)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT PER 210.11C3,
 210.52D. MUST BE 20A AND #12.
  
 10)NOTE: PLEASE SEE 20A OCP ON #14 AWG
 FOR GDO ON NEW PANEL "B".
 310.16,240.4
  
 11)NOTE:PLEASE SEE BOTH PANELS REFERENCE
 ARC FAULT PROTECTION FOR RECEPTS ONLY.
 PLEASE SEE 2002 210.12 FOR PROTECTION OF
 ALL OUTLETS IN BEDROOMS. LTS, FANS, SD'S
 RECEPTS ETC.
 PLEASE SEE NEXT NOTE ALSO.
  
 12)NOTE: PLEASE SEE SD'S ARE NOTED ON
 PLANS HOWEVER THESE ARE NOT ON PLANS.
 PLEASE SEE PREVIOUS NOTE FOR REQUIRED
 SD'S AND PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION. IF WIRED AS NOTED, THIS
 WOULD PLACE ARC FAULT PROTECTION FOR
 OTHER CIRCUITS.
  
 13)NOTE:PLEASE SEE PLANS ARE NOTED TO 99
 NEC. WE ARE UNDER THE 2002 NEC WHICH WAS
 ADOPTED ON JULY 1ST, 2003
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS. (ZONING).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-19 Cont ID  
Sent By adarroug Date 2006-04-19 Time 14:42 Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 14:42 Sent To E
Notes
2006-04-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 10:24 Sent To E
Notes
2006-04-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 10:58 Sent To E
Notes
2005-09-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 11:26 Sent To Z
Notes
2005-08-31 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 16:45 Sent To E
Notes
2005-08-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 11:42 Sent To Z
Notes
2005-07-29 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 10:13 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 10:13 Sent To E
Notes
2005-07-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-28 Cont ID  
Sent By alange Date 2005-07-28 Time 15:43 Rev Time 0.00
Received By alange Date 2005-06-23 Time 13:38 Sent To  
Notes
2005-06-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-13 Cont ID  
Sent By tgordon Date 2005-09-13 Time 14:50 Rev Time 0.20
Received By tgordon Date 2005-09-13 Time 14:50 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-08-12 Cont ID  
Sent By tgordon Date 2005-08-12 Time 16:03 Rev Time 0.00
Received By tgordon Date 2005-08-12 Time 16:02 Sent To  
Notes
2005-08-12 00:00:00DENIED:
 1. FL. ENERGY CAL. IS CALLING FOR 18,600
 BTU'S & 12 SEER, PLANS SHOW 36,000
 BTU'S & 11 EER TO BE INSTALLED. FL.
 ENERGY CAL. & PLANS NEED TO COINCIDE
 WITH EACH OTHER.
 2. AUXILIARY DRAIN PAN SHOULD BE PLACED
 BELOW A/H STAND AND HAVE A FLOAT SWITCH
 INSTEAD OF AN AUXILIARY DRAIN LINE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 10:14 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 09:45 Sent To B
Notes
2005-07-16 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 CRAIN PANS.
 2) PLEASE PROVIDE TWO SETS OF ENERGY
 CALCULATIONS AND MANUAL J
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-09-14 Cont ID  
Sent By jleech Date 2005-09-14 Time 13:06 Rev Time 0.00
Received By jleech Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 13:22 Rev Time 0.33
Received By jleech Date 2005-09-13 Time 13:22 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 19:38 Rev Time 0.33
Received By jleech Date 2005-08-10 Time 07:27 Sent To M
Notes
2005-08-10 00:00:00DENIED;
 1. SEE ZONING NOTES.
 2.SHOWER NOT SHOWN IN RISER DIADRAM,AND
 W/C SHOULD COME OFF THE BUILDING DRAIN
 NOT THE VENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-16 Cont ID  
Sent By pschmitz Date 2005-07-16 Time 06:33 Rev Time 0.00
Received By pschmitz Date 2005-07-16 Time 06:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 18:34 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 18:34 Sent To I
Notes
2005-09-06 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK
 MUST PULL A SEPERATE PERMIT FOR FENCE
 WITH EASEMENT APPROVAL FROM CITY OF WEST
 PALM BEACH UTILITY DEPT.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-08-04 Cont ID  
Sent By mmclean Date 2005-08-04 Time 16:52 Rev Time 0.00
Received By mmclean Date 2005-08-04 Time 16:52 Sent To I
Notes
2005-08-04 00:00:00DENIED,
 1. SITEPLAN & SURVEY DOES NOT
 MATCH.(SETBACKS).
 2. MUST UPDATE THE SURVEY TO REFLECT THE
 REQUIRED SIDE & REAR SETBACK OF NEW
 ADDITION.
 **NEW ADDITION MUST MEET THE SIDE
 SETBACK. BOTH SIDES MUST GIVE A TOTAL OF
 15FT.**
 **SETBACK IN REAR OF THE PROPERTY MUST
 BE 10% OF LOT DEPTH.**
 5.MUST PROVIDE THE LENGTH & WIDTH OF THE
 NEW BRICK PAVER WALKWAY.
  
 NOTE:
 - MUST PULL A SEPERATE PERMIT FOR THE
 FENCE WITH THE EASMENT APPROVAL FROM
 CITY OF WEST PALM BEACH UTILITY DEPT.
 - MUST PULL A SEPERATE PERMIT FOR THE
 POOL/SPA/DECK.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By mmclean Date 2005-07-01 Time 16:07 Rev Time 0.00
Received By mmclean Date 2005-07-01 Time 16:07 Sent To I
Notes
2005-07-01 00:00:00DENIED,
 1. NEW ADDITION MUST MEET THE SIDE
 SETBACK. BOTH SIDES MUST GIVE A TOTAL OF
 15FT.
 2. SETBACK IN REAR OF THE PROPERTY MUST
 BE 10% OF LOT DEPTH.
 3. MUST PULL A SEPERATE PERMIT FOR THE
 FENCE WITH THE EASMENT APPROVAL FROM
 CITY OF WEST PALM BEACH UTILITY DEPT.
 4. MUST PULL A SEPERATE PERMIT FOR THE
 POOL/SPA/DECK.
 5.MUST PROVIDE THE LENGTH & WIDTH OF THE
 NEW BRICK PAVER WALKWAY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720