Plan Review Details - Permit 05061446
Plan Review Stops For Permit 05061446
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-18 Cont ID  
Sent By jwitmer Date 2005-07-18 Time 09:29 Rev Time 0.77
Received By jwitmer Date 2005-07-18 Time 09:29 Sent To PC
Notes
2005-07-18 00:00:00REVISION- BUR ROOFING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-29 Cont ID  
Sent By jwitmer Date 2005-06-29 Time 07:51 Rev Time 55.00
Received By jwitmer Date 2005-06-29 Time 07:51 Sent To R
Notes
2005-06-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061446
 ADD: 1500 ELIZABETH AVE
 CONT: THERMA SEAL
 TEL: (561)719-2653
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 REVISION CHANGE FROM A TEAR OFF TO A
 ROOF OVER OF A CONCRETE DECK.
  
 1) FOR A ROOFOVEROF AN EXISTING
 CONCRETE DECK A PULL TEST IS REQUIRED.
  
 2) A PREINSPECTION WILL BE REQUIRED TO
 INDICATE HOW MANY EXISTING ROOFS ARE
 THERE.
  
 3) PAGES 6-20 ARE VARIOUS SUB SYSTEMS,
 NONE ARE HIGHLIGHTED, INDICATE WHICH
 SYSTEM WILL BE USED, DEPENDING ON THE
 SYSTEM NEG VALUES FROM 445 TO 240 ARE
 PRESENT. IF A SYSTEM IS PICKED WITH
 VALUES LESS THAN -83.7 SEE LIMITATION
 7 OR 9. PROVIDE ENHANCED FASTENING IF
 REQUIRED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-06-22 Cont ID  
Sent By lsmith Date 2005-06-22 Time 12:14 Rev Time 0.25
Received By lsmith Date 2005-06-22 Time 12:14 Sent To  
Notes
***NONE***