Plan Review Details - Permit 05061434
Plan Review Stops For Permit 05061434
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-12-26 Cont ID  
Sent By lursu Date 2007-12-26 Time 12:57 Rev Time 0.00
Received By lursu Date 2007-12-26 Time 12:57 Sent To  
Notes
2007-12-26 13:06:14ONE NEW SITE ADDRESS IS BEING ISSUED FOR THE NEW
 BUILDING AS 1634 CLARE AVE , WEST PALM BEACH, FL
 33401.THE SECOND NEW BUILDING MAINTAINS THE EXISTING
 SITE ADDRESS AS 1630 CLARE AVE.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-03 Cont ID  
Sent By jwitmer Date 2006-04-03 Time 11:51 Rev Time 0.55
Received By jwitmer Date 2006-04-03 Time 11:51 Sent To B
Notes
2006-04-03 00:00:004-03-06 FORM BOARD SURVEYOK!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-30 Cont ID  
Sent By jwitmer Date 2006-01-30 Time 09:43 Rev Time 3.33
Received By jwitmer Date 2006-01-10 Time 09:11 Sent To PC
Notes
2006-01-30 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 05061434
 ADDRESS: 1630 CLARE AVE
 CONT:MURPHY CONSTRUCTION
 TELL # (561)635-6935
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
  
 BUILDING PROVISO:
 BEFORE FIRST BUILDING INSPECTION TIE IN
 SURVEY TO INDICATIE THE NEW BUILDING TO
 BE BUILT ON (74-43-43-28-09-013-0320)
 LEGAL DESCRIPTION SADLERS BONNYVIEW ADD
 LTS 32 THRU 34 (LESS SELY 12.5 FT)
 JOHNSON BLK & LTS 1-16 (LES 12.5
 CLEVLAND)
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
 ROOF INFO:
 FL 735
 TAMKO ROOFING MODIFIED BITUMEN ROOF SYS
 MIAMI-DADE NOA 02-0221.05
  
 SYSTEM: DECK TYPE 31 CONCRETE INSULATED
 2500 PSI STRUCTURAL CONCERETE
  
  
2006-01-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061434
 ADD: 1630 CLARE AVENUE
 CONT: THE MURPHY CONSTRUCTION CO
 TEL: (561)719-0117
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)COMMENT# 6 FROM THE PREVIOUS REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) IT APPEARS THAT 2 LOTS ARE GOING TO
 BE COMBINED INTO ONE LOT OVER A CITY
 RIGHT OF WAY.SENT TO ADDRESSING TO
 RESEARCH.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-30 Cont ID  
Sent By jwitmer Date 2005-07-30 Time 13:54 Rev Time 2.22
Received By jwitmer Date 2005-07-30 Time 13:54 Sent To PC
Notes
2005-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061434
 ADD: 1630 CLARE AVENUE
 CONT: THE MURPHY CONSTRUCTION CO
 TEL: (561)719-0117
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 2) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 X- BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 3)CHANGE THE DESCRIPTION OF PROJECT ON
 THE PERMIT APPLICATION TO INCLUDE (2)
 NEW WAREHOUSES.
  
 4)THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE. LOCATED IN A A9
 FLOOD ZONE. MINIMUM ELEVATION 13.5'.
 FINISH FLOOR.
  
 5) 1A6.0 RESTROOMS:1204.2 SURROUNDING
 MATERIALS; THE WALLS & FLOORS OF ALL
 PUBLIC REST- ROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4'-0" ABOVE THE FLOOR.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) ROOFING APPROVAL INDICATE ON PAGE 9
 OF NOA WHICH SYSTEM WILL BE USED SO ROOF
 PRESSURES CAN BE REVIEWED FOR
 COMPLIANCE.
  
 8) STRUCTURAL PLANS LOOK AS IF FOR
 BUILDING# 2, NO STRUCTURAL PLANS ARE
 LOCATEDFOR BUILDING# 1?????
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-12 Cont ID  
Sent By dpalmer Date 2007-09-12 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2007-09-12 Time 16:58 Sent To PC
Notes
2007-09-12 17:00:00** REDLINED PLANS.
  
 NO *EQUIPMENT GROUNDING CONDUCTOR* IS PERMITTED TO BE
 INSTALLED BEFORE MAINS PER 250.6 AND 250.24B.
 THIS WAS REDLINED TO BE REMOVED IF INSTALLED AS SHOWN.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 15:00 Sent To PC
Notes
2007-08-27 15:17:11*** DENIED REVISIONS***
  
 ** PLEASE SEE SOME RELINED ITEMS WHICH WERE PLACED ON
 PLANS FROM DECEMBER 05 HAVE NOT BEEN CORRECTED OR
 CHANGED.
  
 1) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 SIZE REDLINED AS THE MINIMUM OF 1/0 HAS NOT BEEN
 CORRECTED. STILL SHOWS #2.
 250.66, 250.50
  
 2) NOTE: PLEASE CLARIFY THE #2 BEING SHOWN AS THE
 EQUIPMENT GROUNDING CONDUCTORS FROM MAINS TO PANELS.
 THIS SIZE IS OK, HOWEVER MUCH LARGER THAN NEEDED.
 PLEASE BE SURE THIS IS WHAT IS INSTALLED IN THE FIELD.
  
 3) NOTE: PLEASE SEE THE SERVICES WITH TWO RISER
 REQUIRES BOTH OF THESE TO BE BONDED AS PART OF THE SAME
 GROUNDING ELECTRODE SYSTEM.
 250.50,250.66 AND 250.58
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-09 Cont ID  
Sent By dpalmer Date 2005-12-09 Time 06:59 Rev Time 0.00
Received By dpalmer Date 2005-12-09 Time 06:52 Sent To  
Notes
2005-12-09 00:00:00**** PLANS REDLINED ****
  
 ** PLEASE INFORM ENGINEER OF NOTE AND
 REVISE WHEN MAKING ANY OTHER CHANGES TO
 PLANS AND WHEN SUBMITTED FOR PLAN
 REVIEW.
  
  
 1)NOTE: PLEASE SEE THE PREVIOUS NOTE#4
 WAS FOR THE "EQUIPMENT GROUNDING
 CONDUCTOR", HOWEVER CHANGES TO THE
 "GROUNDING ELECTRODE CONDUCTOR" WERE
 MADE INSTEAD.
 PLEASE SEE 250.66, THE MIN SIZE FOR THE
 GEC IS 1/0.
 PLEASE SEE 250.6.250.24 FOR PERMITTED
 ATTACHMENT LOCATIONS.
  
 PLEASE SEE THE "EQUIPMENT GROUNDING
 CONDUCTORS" FROM THE FIRST MEANS OF
 DISCONNECT TO PANEL ARE OK.
  
  
 PLEASE MAKE ANY CHANGES TO THE GEC FOR
 BOTH SERVICES WITH ANY OTHER REVISIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By dpalmer Date 2005-07-07 Time 07:16 Rev Time 0.75
Received By dpalmer Date 2005-07-06 Time 20:52 Sent To  
Notes
2005-07-07 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEEBLDH #2 APPEARS TO
 HAVE OFFICES. PLEASE PROVIDE SIGN
 CIRCUIT PER 600.5
  
 2)NOTE: PLEASE CLARIFY OF INDEED THESE
 WILL BE OFFICES, WILL THERE BE ANY A/C
 UNITS? IF SO PLEASE SHOW.
 THIS IS ONLY A NOTE:
  
 3)NOTE: PLEASE SEE ROOM AT LOCATION OF
 PANEL "J" IS LABELED AS STORAGE ON
 A-PLANS. PLEASE ADJUST RM DESIGNATION AS
 ELECTRICAL RM/ NO STORAGE ON PLANS AT
 BOTH LOCATION. 110.26,408.7
  
 4)NOTE: PLEASE SEE 250.6,250.24.
 EQUIPMENT GROUNDING CONDUCTORS SHALL NOT
 BE INSTALLED UNTIL AFTER THE FIRST MEANS
 OF DISCONNECT. PLEASE SEE RISER SHOWS A
 1/0 AS AN EQUIPMENT GROUNDING CONDUCTOR
 FROM GUTTER TO METER AND METER TO FIRST
 MEANS OF DISC.
  
 5)NOTE: PLEASE SEE PLUMB REVIEW NOTES
 FOR ENGINEER'S SIGNATURE OF RECORD ON
 PLUMB SHEETS.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEWL. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
2005-07-06 00:00:00IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-01-13 Cont ID  
Sent By mamini Date 2006-01-13 Time 10:10 Rev Time 1.00
Received By mamini Date 2006-01-13 Time 10:09 Sent To  
Notes
2006-01-13 00:00:00PASSED WITH PROVISOS:
  
 1. SEE REVIEW COMMENTS FROM PBLIC
 UTILITIES.
 2. SEE REPONSE LETTER (ATTACHED TO THE
 CIVIL PLANS) FROM MR. DOUG WINTER,P.E
 CIVIL ENGINEER OF RECORD DATED 8-8-05.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-06-30 Cont ID  
Sent By mamini Date 2005-06-30 Time 11:02 Rev Time 1.00
Received By mamini Date 2005-06-30 Time 11:02 Sent To  
Notes
2005-06-30 00:00:00FAILED:
  
 1. PLEASE SUBMIT CIVL PLANS ONLY TO THE
 PUBLIC UTILITIES AND ENGINEERING ATT;
 MANNY GONZALEZ, 494-1085
 VERIFY;
 A. EXISTING METERS AND DOMESTIC WATER
 FOR THE PROPOSED BUILDINGS.
 B. NO DOMESTIC WATER TO BUILDING # 1
 C. NO SEWER LATERALS SHOWN.
 D. PARALLEL PARKINGS AS PROPOSED ON
 CLARE AVE. BRIAN COLLINS, 494-1076.
 2. NOTE THAT APPROACH MUST BE
 CONSTRUCTED PER CITY OF WPB' STANDARD.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-19 Cont ID  
Sent By mcarsill Date 2005-12-19 Time 11:11 Rev Time 0.00
Received By mcarsill Date 2005-12-19 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By mwennerg Date 2005-07-21 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2005-07-21 Time 14:26 Sent To  
Notes
2005-07-21 00:00:00******DENIED******
  
 1) DRAWINGS ILLUSTRATE 2 BUILDINGS, AND
 THE PERMIT APPLICATION REFERENCES 1 IN
 PROJECT DESCRIPTION. PLEASE CLARIFY.
  
 2) AN ADDRESS IS REQUIRED ON BUILDING(S)
 THAT IS A MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
 3) PLEASE INDICATE WHAT TYPE OF CONTENTS
 ARE PLANNED TO BE STORED. WILL THERE BE
 RACK STORAGE, AND IF SO PLEASE PROVIDE
 RACK HEIGHTS.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 5) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 6) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 7) IF BUILDING 2 MEETS THE DEFINITION OF
 MIXED OCCUPANCY, THE MOST RESTRICTIVE
 CODE REQUIREMENTS SHALL APPLY.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 12:31 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 12:31 Sent To Z
Notes
2008-01-23 12:31:45TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 11:15 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 11:15 Sent To M
Notes
2007-11-06 11:15:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 14:13 Sent To E
Notes
2007-09-10 14:14:06TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 14:06 Sent To Z
Notes
2007-10-01 10:02:11TO "COMM" BD#17
2007-09-10 14:06:45WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 14:36 Sent To E
Notes
2007-08-22 14:37:10TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 14:35 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 14:35 Sent To M
Notes
2007-08-22 14:35:25TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 14:33 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 14:33 Sent To P
Notes
2007-08-22 14:33:59TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 12:16 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 12:16 Sent To B
Notes
2006-03-28 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 15:58 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 15:58 Sent To  
Notes
2005-12-09 00:00:00MOVED TO SPACE #60
2005-11-22 00:00:00TO "COMM" BD#43
2005-10-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 15:46 Sent To ENG
Notes
2005-07-21 00:00:00TO "MAMINI" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-30 Cont ID  
Sent By jwitmer Date 2005-07-30 Time 14:33 Rev Time 0.00
Received By jwitmer Date 2005-06-23 Time 15:09 Sent To  
Notes
2005-06-27 00:00:00TO "COMM" BD#59
2005-06-23 00:00:00WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-01-25 Cont ID  
Sent By rkussner Date 2008-01-25 Time 13:33 Rev Time 0.00
Received By rkussner Date 2008-01-25 Time 13:32 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-10 Cont ID  
Sent By rregueir Date 2007-11-10 Time 12:35 Rev Time 0.00
Received By rregueir Date 2007-11-10 Time 12:08 Sent To Z
Notes
2007-11-10 12:35:12M1, M2 AND ENERGY CALCS REVISED. SENT TO ZONING FOR
 SITE PLAN REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-10-11 Cont ID  
Sent By rregueir Date 2007-10-11 Time 10:35 Rev Time 0.00
Received By rregueir Date 2007-10-11 Time 09:54 Sent To PC
Notes
2007-10-11 10:34:24REVIEW #: 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. AS STATED IN PREVIOUS COMMENT, THE FLA/COM ENERGY
 CALCULATIONS SHALL BE REVISED USING THE PROGRAM WHICH
 WAS IN EFFECT AT THE TIME OF PERMIT APPLICATION. MIXING
 OF CODES IS PROHIBITED. PLEASE SUBMIT REVISED
 CALCULATIONS USING FORM 400A-2001.
 NOTE: BE SURE TO CHECK THE INPUT DATA REPORT AND VERIFY
 COMPLIANCE AND ACCURACY OF ALL ELEMENTS LISTED IN THE
 REPORT. EXAMPLE: LIGHTING DATA INDICATES ONE 2000 WATT
 FIXTURE FOR ALLL INTERIOR LIGHTING. INFORMATION IN THE
 REPORT SHALL ACCURATELY REFLECT THE INFORMATION SHOWN
 ON PLANS IN ACCORDANCE WITH FBC 13-400.3.ABCD.1.
  
 2. OK
  
 3. NOTES AND PLANS REGARDING CONDENSATE DISPOSAL
 INDICATE TRAPS AT EACH AHU AS WELL AS UNDERGROUND DRAIN
 LINES CREATING A DOUBLE TRAP. CONDENSATE DRAINS SHALL
 BE TRAPPED AS REQUIRED BY THE
 EQUIPMENT OR APPLIANCE MANUFACTURER. PLEASE CONFIRM
 THAT THIS METHOD IS IN COMPLIANCE WIITH MANUFACTURER'S
 INSTRUCTIONS AND PROVIDE SUPPORTING DOCUMENTATION.
  
 4. A "REVISED" SITE PLAN HAS BEEN PROVIDED. HOWEVER,
 THE FOLLOWING DEFICIENCIES EXIST:
 A. ONLY ONE COPY WAS PROVIDED. AT LEAST TWO COPIES ARE
 REQUIRED FOR ALL PLANS AND SPECIFICATIONS PER FBC
 104.2.1.
 B. PLANS HAVE BEEN PHOTOCOPIED. PLANS SHALL CONTAIN THE
 ORIGINAL SEAL, SIGNATURE AND DATE OF THE DESIGNER OF
 RECORD IN ACCORDANCE WITH FBC 104.2.2 AND FS 471. C.
 SIGNED AND SEALED PLANS SHALL NOT BE ALTERED BY HAND OR
 USE OF CORRECTION FLUID (SUCH AS WHITE-OUT). PROVIDE
 TWO SETS OF THE REVISED SITE PLANS WITH ALL INFORMATION
 LISTED ABOVE ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-08-23 Cont ID  
Sent By rregueir Date 2007-08-23 Time 20:13 Rev Time 0.00
Received By rregueir Date 2007-08-23 Time 20:05 Sent To  
Notes
2007-08-23 20:13:02REVIEW #: 1
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY W/ SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MECHANICAL EQUIPMENT HAS CHANGED FROM ONE 6-TON
 ROOFTOP PACKAGE UNIT TO TWO 3.5-TON SPLIT SYSTEMS.
 PROVIDE REVISED ENERGY CALCULATIONS WHICH REFLECT THIS
 CHANGE.
 NOTE: BE SURE TO USE THE SAME VERSION OF THE FLA/COM
 PROGRAM WHICH WAS USED AT TIME OF PERMITTING.
  
 2. THERE ARE TWO AIR HANDLERS WITH A COMBINED DESIGN
 CAPACITY ABOVE 2000 CFM SHARING A COMMON RETURN PLENUM.
 THE RETURN AND SUPPLY AIR SYSTEMS SHALL BE PROVIDED
 WITH SMOKE DETECTORS FOR FAN SHUT-DOWN. FBC,M 606.2.2.
  
 3. PLEASE SHOW ON PLANS THE MEANS AND LOCATION OF
 CONDENSATE DISPOSAL WHICH IS IN COMPLIANCE WITH FBC,M
 307.2.
  
 4. THE LOCATION OF CONDENSING UNITS AS SHOWN ON PLANS
 WILL INTERFERE WITH THE 5 FOOT WIDE SIDEWALK AS SHOWN
 ON PG SP-1. PROVIDE REVISED SITE PLAN OR ARCHITECTURAL
 PLAN SHOWING THE LOCATION OF CONDENSERS AND VERIFY THAT
 THEY DO NOT INTERFERE WITH ANY ACCESSIBLE ROUTE WHICH
 IS REQUIRED BY FBC CH.11.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-06 Cont ID  
Sent By pkrauss Date 2006-01-06 Time 10:53 Rev Time 0.00
Received By pkrauss Date 2006-01-06 Time 10:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 09:02 Rev Time 0.45
Received By pkrauss Date 2005-07-26 Time 09:02 Sent To  
Notes
2005-07-26 00:00:00DENIED:
 1.NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.MINIMUM VENTILATION IS REQUIRED
 PER 2001 FBC(M) TABLE 403.3.PROVIDE
 CALCULATIONS ACCORDINGLY.
  
 2.PROVIDE DETAIL FOR ANY ROOF CURBS
 THAT MAY BE INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-24 Cont ID  
Sent By kstevens Date 2007-09-24 Time 11:13 Rev Time 0.00
Received By kstevens Date 2007-09-24 Time 11:12 Sent To  
Notes
2007-09-24 11:13:39REVISION OK (AS-BUILTS)--SHTS P-1 & P-2

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-17 Cont ID  
Sent By pschmitz Date 2005-12-17 Time 12:36 Rev Time 0.00
Received By pschmitz Date 2005-12-17 Time 12:36 Sent To  
Notes
2005-12-17 00:00:00RE-SUB: SEE TRANSMITTAL DATED 10-19-05

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By kstevens Date 2005-07-21 Time 09:04 Rev Time 1.50
Received By kstevens Date 2005-07-20 Time 18:53 Sent To  
Notes
2005-07-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. APPLICATION DESCRIPTION OF PROJECT
 STATES NEW WAREHOUSE. PLANS SHOW 2 NEW
 WAREHOUSES. PLEASE CLARIFY. SECTION
 104.2.1.
 2. SHT C-1 AN RPZ BACKFLOW IS REQUIRED
 FOR EACH BUILDING. SECTION 608.13.2.
 3. SHT C-1 NO WATER SERVICE IS SHOWN TO
 BUILDING #2, AND THERE IS NO SANITARY
 SEWER SHOWN TO EITHER BUILDING. SECTION
 104.2.1.
 4. SHT A1.1 SCOPE OF WORK INDICATES 2
 TENANTS ONLY, AS ADDITIONAL TENANTS ARE
 ADDED, DRINKING FOUNTAINS AND SERVICE
 SINKS SHALL BE REQUIRED IN EACH SPACE
 PER TABLE 403.1
 5. SHTS 1A2.0 & 2A2.0 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW AREA OF ROOF AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO AREA OF ROOF IN
 CALCULATIONS. INDICATE TOTAL AREA
 DRAINED BY EACH ROOF DRAIN. SUBMIT A
 DETAIL OF THE PRIMARY AND SECONDARY ROOF
 DRAINS WITH SIZE OF EACH. SECTIONS 1106,
 AND 1107.
 6. SHTS 1A6.0 & 2A6.0 SHOW THE FOLLOWING
 ACCESSIBLITY REQUIREMENTS:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS:
 C. 11-4.19.3 CLEAR FLOOR SPACE
 D. 11-4.19.5 FAUCETS
 FOR DRINK FOUNTAINS:
 E. 11-4.15.2 SPOUT HEIGHT
 F. 11-4.15.3 SPOUT LOCATION
 G. 11-4.15.4 CONTROLS
 H. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE.
 I. 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 7. SHTA 1A6.0 & 2A6.0 INDICATE HOW THE
 GWB ON THE WALL FINISH WILL SATISFY THE
 REQUIREMENT OF SECTION 1204.2, WALLS
 SHALL HAVE NONABSORBENT MATERIAL UP TO 4
 FEET.
 8. SHTS P1 & P2 SIGNATURE ON SEAL DOES
 NOT MATCH THE LEGAL SIGNATURE ON FILE
 FOR THE ENGINEER. FAC 61G1-16.003 & FS
 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2007-11-14 Cont ID  
Sent By choops Date 2007-11-14 Time 09:01 Rev Time 0.00
Received By choops Date 2007-11-14 Time 09:01 Sent To PC
Notes
2007-11-14 09:03:11***APPROVED - REVISION - MOVE A/C CONDENSERS TO THE
 SIDEWALK***
  
 PROVISO:A/C CONDENSOR UNITS SHALL NOT INTERFERE WITH
 ADA ACCESSIBILITY REQUIREMENTS.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 16:33 Rev Time 0.00
Received By choops Date 2007-10-09 Time 16:33 Sent To  
Notes
2007-10-09 16:36:54***FAILED - REVISION - MOVE A/C CONDENSORS TO THE
 SIDEWALK***
  
  
 1)PROVIDE TWO (2) COPIES OF ALL PLANS (SITE PLAN).
  
 2)PLANS SHALL CONTAIN NO WHITE OUT.
  
 3)SEE BUILDING'S COMMENTS REGARDING 5' SIDEWALK
 ACCESSIBILITY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-26 Cont ID  
Sent By sgraham Date 2005-07-26 Time 15:56 Rev Time 0.00
Received By sgraham Date 2005-07-26 Time 15:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-22 Cont ID  
Sent By mmclean Date 2005-07-22 Time 14:55 Rev Time 0.00
Received By mmclean Date 2005-07-22 Time 14:55 Sent To  
Notes
2005-07-22 00:00:00DENIED,
 1. NEED TO RE-APPLY FOR A INFORMAL.
 INFORMAL FOR 2002 IS ONLY GOOD FOR
 12MTHS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720