Plan Review Stops For Permit 05061193 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-07-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-07-22 |
Time |
15:11 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2005-07-18 |
Time |
11:43 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-30 |
Time |
12:48 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-06-30 |
Time |
11:46 |
Sent To |
M |
|
Notes |
2005-06-30 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SUBMIT GENERATOR AND TRANSFER SWITCH | | MANUFACTURERS SPECIFICATIONS. 2 COPIES. | | | | 2} THE #3 FEEDERS MAY NOT BE LARGE | | ENOUGH TO COMPLY WITH 445.13 NEC.(115%). | | DON'T KNOW NAMEPLATE RATING WITHOUT | | SPEC'S AND PRIME MOVER. | | | | 3} CALCULATED LOAD PER 702.5. WILL | | ACCEPT OPTIONAL CALCULATION 220.31(B) | | FOR EMERGENCY PANEL. | | | | 4} PLEASE SHOW THE LOCATION OF THE | | TRANSFER SWITCH ON THE FLOOR PLAN | | DRAWING SO COMPLIANCE WITH 225.32 CAN BE | | DETERMINED. | | | | 5} DESIGNER MUST PRINT NAME AND SIGN | | PLANS, 104.2.1 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-07-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-20 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-20 |
Time |
16:18 |
Sent To |
E |
|
Notes |
2005-07-20 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-07-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-14 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-14 |
Time |
11:21 |
Sent To |
B |
|
Notes |
2005-07-14 00:00:00 | TO "MISC" BOX #3 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-07-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-11 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-11 |
Time |
10:01 |
Sent To |
Z |
|
Notes |
2005-07-11 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-06-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-23 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-06-23 |
Time |
10:41 |
Sent To |
E |
|
Notes |
2005-06-23 00:00:00 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-06-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-17 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-17 |
Time |
09:11 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-07-08 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2005-07-08 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2005-07-08 |
Time |
11:31 |
Sent To |
|
|
Notes |
2005-07-08 00:00:00 | PROVISO:GENERATOR EXHAUST TO TERMINATE | | MINIMUM 10' FROM OPENINGS INTO BUILDING | | STRUCTURE (DOORS,WINDOWS). |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-07-27 |
Time |
07:52 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-07-27 |
Time |
07:52 |
Sent To |
|
|
Notes |
2005-07-27 00:00:00 | GAS PERMIT APPLICATION HAS BEEN RECIEVED | | ON 7/8/05 #05070285 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-07-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-07-09 |
Time |
09:14 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-07-09 |
Time |
09:14 |
Sent To |
B |
|
Notes |
2005-07-09 00:00:00 | GAS PERMITAPPLICATION APPLIED FOR ON | | 7/8/05. #05070285 GEN RES REQUIRED TO | | PASS ZONING BEFORE GAS PLANS CAN BE | | REVIEW. | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-07-20 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-07-20 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-07-20 |
Time |
11:35 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-06-22 |
Time |
18:53 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-06-22 |
Time |
18:53 |
Sent To |
B |
|
Notes |
2005-06-22 00:00:00 | DENIED, | | 1. MUST PROVIDE THE DIMENSION OF THE | | GENERATOR ON (2) COPY OF SURVEY | | 1. MUST PROVIDE THE DIMENSION/SETBACK OF | | THE GENERATOR FROM PROPERTY LINE AND | | FROM THE STRUCTURE. | | | | **GENERATOR CAN ONLY ENROACH 4FT INTO | | SETBACK.*** | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|