Plan Review Details - Permit 05061193
Plan Review Stops For Permit 05061193
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-22 Cont ID  
Sent By btrobaug Date 2005-07-22 Time 15:11 Rev Time 0.75
Received By btrobaug Date 2005-07-18 Time 11:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-30 Cont ID  
Sent By btrobaug Date 2005-06-30 Time 12:48 Rev Time 0.50
Received By btrobaug Date 2005-06-30 Time 11:46 Sent To M
Notes
2005-06-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT GENERATOR AND TRANSFER SWITCH
 MANUFACTURERS SPECIFICATIONS. 2 COPIES.
  
 2} THE #3 FEEDERS MAY NOT BE LARGE
 ENOUGH TO COMPLY WITH 445.13 NEC.(115%).
 DON'T KNOW NAMEPLATE RATING WITHOUT
 SPEC'S AND PRIME MOVER.
  
 3} CALCULATED LOAD PER 702.5. WILL
 ACCEPT OPTIONAL CALCULATION 220.31(B)
 FOR EMERGENCY PANEL.
  
 4} PLEASE SHOW THE LOCATION OF THE
 TRANSFER SWITCH ON THE FLOOR PLAN
 DRAWING SO COMPLIANCE WITH 225.32 CAN BE
 DETERMINED.
  
 5} DESIGNER MUST PRINT NAME AND SIGN
 PLANS, 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 16:18 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 16:18 Sent To E
Notes
2005-07-20 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 11:21 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 11:21 Sent To B
Notes
2005-07-14 00:00:00TO "MISC" BOX #3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 10:01 Sent To Z
Notes
2005-07-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 10:41 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 10:41 Sent To E
Notes
2005-06-23 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 09:11 Rev Time 0.00
Received By shill Date 2005-06-17 Time 09:11 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-08 Cont ID  
Sent By lmartine Date 2005-07-08 Time 14:10 Rev Time 0.00
Received By lmartine Date 2005-07-08 Time 11:31 Sent To  
Notes
2005-07-08 00:00:00PROVISO:GENERATOR EXHAUST TO TERMINATE
 MINIMUM 10' FROM OPENINGS INTO BUILDING
 STRUCTURE (DOORS,WINDOWS).

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-27 Cont ID  
Sent By jleech Date 2005-07-27 Time 07:52 Rev Time 0.33
Received By jleech Date 2005-07-27 Time 07:52 Sent To  
Notes
2005-07-27 00:00:00GAS PERMIT APPLICATION HAS BEEN RECIEVED
 ON 7/8/05 #05070285

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 09:14 Rev Time 0.33
Received By jleech Date 2005-07-09 Time 09:14 Sent To B
Notes
2005-07-09 00:00:00GAS PERMITAPPLICATION APPLIED FOR ON
 7/8/05. #05070285 GEN RES REQUIRED TO
 PASS ZONING BEFORE GAS PLANS CAN BE
 REVIEW.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By mmclean Date 2005-07-20 Time 11:35 Rev Time 0.00
Received By mmclean Date 2005-07-20 Time 11:35 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By mmclean Date 2005-06-22 Time 18:53 Rev Time 0.00
Received By mmclean Date 2005-06-22 Time 18:53 Sent To B
Notes
2005-06-22 00:00:00DENIED,
 1. MUST PROVIDE THE DIMENSION OF THE
 GENERATOR ON (2) COPY OF SURVEY
 1. MUST PROVIDE THE DIMENSION/SETBACK OF
 THE GENERATOR FROM PROPERTY LINE AND
 FROM THE STRUCTURE.
  
 **GENERATOR CAN ONLY ENROACH 4FT INTO
 SETBACK.***
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720