Plan Review Details - Permit 05060882
Plan Review Stops For Permit 05060882
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-17 Cont ID  
Sent By shill Date 2005-08-17 Time 09:34 Rev Time 0.50
Received By shill Date 2005-08-17 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-05 Cont ID  
Sent By shill Date 2005-08-05 Time 07:08 Rev Time 0.50
Received By shill Date 2005-08-05 Time 07:08 Sent To  
Notes
2005-08-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS LIST, ITEM #1.
 BREAKROOM SINK SHOWN ON A2 AND A3 IS TO
 COMPLY WITH FBC11-4.24.COMMENT NOT
 ADDRESSED (SAME SHEETS DATED 5/3/05
 SUBMITTED).
  
 2.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF THE COMMENT IS NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By shill Date 2005-07-13 Time 16:16 Rev Time 0.00
Received By shill Date 2005-07-13 Time 16:16 Sent To PC
Notes
2005-07-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE BREAK ROOM SINK IS TO COMPLY
 WITH FBC11-4.24.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-22 Cont ID  
Sent By dpalmer Date 2005-09-22 Time 10:57 Rev Time 0.50
Received By dpalmer Date 2005-09-22 Time 10:42 Sent To  
Notes
2005-09-22 00:00:00********** NOTES REDLINED**************
  
 PLEASE KNOW, GENERATOR AS SHOWN ON RISER
 DIAGRAM ALONG WITH ALL CONDUITS AND
 CONDUCTORS UP TO ATS SWITCH IS NOT
 INCLUDED ON THIS PERMIT.
 WHEN GENERATOR IS PERMITTED IN THE
 FUTURE, ALL DISCONNECTING MEANS FOR
 GENERATOR FEEDERS INTO THE BUILDING
 SHALL BE GROUPED WITH EXISTNG MAINS.
 225.31-225.36

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 21:05 Rev Time 0.75
Received By dpalmer Date 2005-08-10 Time 20:36 Sent To  
Notes
2005-08-10 00:00:00********** NOTES REDLINED**************
  
 PLEASE KNOW, GENERATOR AS SHOWN ON RISER
 DIAGRAM ALONG WITH ALL CONDUITS AND
 CONDUCTORS UP TO ATS SWITCH IS NOT
 INCLUDED ON THIS PERMIT.
 WHEN GENERATOR IS PERMITTED IN THE
 FUTURE, ALL DISCONNECTING MEANS FOR
 GENERATOR FEEDERS INTO THE BUILDING
 SHALL BE GROUPED WITH EXISTNG MAINS.
 225.31-225.36
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-02 Cont ID  
Sent By dpalmer Date 2005-08-02 Time 14:01 Rev Time 0.75
Received By dpalmer Date 2005-08-02 Time 13:53 Sent To  
Notes
2005-08-02 00:00:00********** UNSAT *********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SEE PREVIOUS NOTE #1
 WHICH REQUIRED THE ENGINEER TO SIGN
 PLANS. THIS WAS DONE ONLY ON NEW REVISED
 ELECTRICAL SHEETS AND NOT FOR OLD SHEETS
 IN SETS. PLEASE ALSO SEE FP SHEETS.
 THIS IS REQUIRED OF ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER TRADES.
 FS 471.025
  
 2)NOTE: PLEASE SEE ONLY ONE COPY OF
 SPECS FO ATS WERE SUBMITTED.
  
 3)NOTE: PLEASE KNOW, GENERATOR IS NOTED
 ON PLANS "BY OTHERS", PLEASE KNOW, NO
 CONDUITS, CONDUCTOS, MAINS ETC SHALL BE
 PERMITTED AT THIS TIME. ONLY THE ATS MAY
 BE INSTALLED AND NORMAL LINE AND LOAD.
 215.5
  
  
 PLEASE REMOVE OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF ANY OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR REFERENCE
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By dpalmer Date 2005-06-27 Time 11:02 Rev Time 0.75
Received By dpalmer Date 2005-06-27 Time 11:02 Sent To  
Notes
2005-06-27 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE ELECTRICAL SHEETS ARE
 TO BE SIGNED BY THE ENGINEER OF RECORD.
 INITIALS ARE NOT ACCEPTIBLE.
 FS 471.025
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 CUT/SPEC SHEETS FOR ATS (S) TO BE
 INSTALLED.
 PLEASE SEE 225.36, THIS SHALL BE SERVICE
 ENT RATED. PLEASE SEE GEN IS NOT PART OF
 THIS PERMIT APPLICATION. PLEASE SEE
 GROUPING OF DISCONNECTING MEANS WILL BE
 REQUIRED WITH EXISTING MAINS ETC.
 225.34
 GEN IS TO BE SUBMITTED UNDER SEPARATE
 PERMIT IF NOT IN THIS SCOPE OF WORK.
 GEN WILL NOT BE PERMITTED AT LOCATION
 /FLR AS SHOWN ON PLANS FOR FUTURE
 PERMIT.
  
 3)NOTE: PLEASE SEE ELECTRICAL ROOM DOES
 NOT SEEM TO SHGOW MIN CLEARENCE REQUIRED
 UNDER 110.26.
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42, ETC.
  
 5)NOTE: PLEASE SHOW GROUNDING FOR
 TRANSFORMER 250.30
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-08-17 Cont ID  
Sent By mwennerg Date 2005-08-17 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2005-08-17 Time 10:39 Sent To  
Notes
2005-08-17 00:00:00******APPROVED******
  
 AS PREVIOUSLYNOTED, IN ACCORDANCE WITH
 LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL BE WIRED TO CAUSE A GENERAL FIRE
 ALARM CONDITION UPON ACTIVATION.
  
  
 MIKE WENNERGREN,CAPTAIN/WPBFR
 FIRE PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-08-03 Cont ID  
Sent By mwennerg Date 2005-08-03 Time 10:06 Rev Time 0.00
Received By mwennerg Date 2005-08-03 Time 10:05 Sent To  
Notes
2005-08-03 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT THE PREVIOUS FIRE
 REVIEW COMMENTS HAVE NOT BEEN ADDRESSED
 BY LETTER OR REVISIONS ON DRAWINGS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By mwennerg Date 2005-08-03 Time 10:13 Rev Time 0.00
Received By mwennerg Date 2005-07-11 Time 09:31 Sent To  
Notes
2005-07-11 00:00:001. SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 2. FIRE ALARM NOTES ON PAGE FA0.1 ARE
 INCORRECT. NOTES # 17 AND 19 ARE NOT
 CORRECT. PLEASE REVISE NOTES.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT REMODEL.
  
 4. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUMS.
  
 5. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 6. COULD NOT LOCATE ANY INFORMATION
 REGARDING FIRE RATING FOR DOORS INTO
 COMMON AREAS OF THE BUILDING. PLEASE
 PROVIDE DETAILS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 11:52 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 11:51 Sent To M
Notes
2005-11-22 00:00:00TO "PKRAUSS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 09:09 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 09:09 Sent To E
Notes
2005-09-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 08:53 Sent To  
Notes
2005-08-10 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 08:50 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 08:50 Sent To  
Notes
2005-08-01 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-13 Cont ID  
Sent By shill Date 2005-07-13 Time 16:23 Rev Time 0.00
Received By shill Date 2005-06-13 Time 09:23 Sent To  
Notes
2005-07-12 00:00:00MOVED TO "BOB" BD#9
2005-06-17 00:00:00COMM BOARD #63
  
2005-06-13 00:00:00ON TABLE WAITING TO GO ON COMM BD.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-11-22 Cont ID  
Sent By pkrauss Date 2005-11-22 Time 13:55 Rev Time 0.45
Received By pkrauss Date 2005-11-22 Time 12:56 Sent To  
Notes
2005-11-22 00:00:00PROVISO:
 PLAN INDICATES FIRE DAMPERS REMOVED ON
 PENETRATIONS TO THE EQUIPMENT RM #102 &
 THE SERVER RM #109.PLEASE REVISE
 ARCHITECTURAL PLANS TO CORRELATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 16:19 Rev Time 0.25
Received By pkrauss Date 2005-08-16 Time 16:14 Sent To  
Notes
2005-08-16 00:00:00NO CHANGE FROM PLANS APPROVED BY H.
 MOSER ON 8/3/05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By hmoser Date 2005-08-03 Time 17:30 Rev Time 0.00
Received By hmoser Date 2005-08-03 Time 17:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By pkrauss Date 2005-07-12 Time 14:18 Rev Time 0.45
Received By pkrauss Date 2005-07-12 Time 14:11 Sent To  
Notes
2005-07-12 00:00:00DENIED:
 1.PLAN SHEET M6.1 DETAIL FOR THE
 CEILING UNIT INSTALLATION; AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED PER 2001 FBC(M)307.2.3.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN ACCORDANCE WITH WITH 2001
 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-06 Cont ID  
Sent By pschmitz Date 2005-08-06 Time 08:30 Rev Time 0.00
Received By pschmitz Date 2005-08-06 Time 08:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By kstevens Date 2005-07-09 Time 11:28 Rev Time 1.00
Received By kstevens Date 2005-07-09 Time 11:28 Sent To  
Notes
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-2 & A-3 SHOW THE FOLLOWING FOR
 THE SINK:
 A. KNEE CLEARANCE 11-4.24.3
 B. SINK DEPTH 11-4.24.4
 C. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 PROVIDED WITH FORWARD APPROACH AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. CABINET DOOR SHALL NOT BE IN THE
 CLEAR FLOOR SPACE.
 D. FAUCETS 11-4.24.7
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  