Plan Review Details - Permit 05060722
Plan Review Stops For Permit 05060722
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2006-05-15 Cont ID  
Sent By mperson Date 2006-05-15 Time 16:36 Rev Time 0.33
Received By mperson Date 2006-05-15 Time 16:36 Sent To PC
Notes
2006-05-15 00:00:00REVISION: CHANGED SIZE OF FUTURE
 GENERATOR FROM 1-1/4" TO 1" AND MADE
 UPSTAIRS FIREPLACE A FUTURE FIREPLACE
  
 ******PROVISO******
 FUTURE GENERATOR GAS PIPING AT OWN RISK,
 SEPERATE GEN/RES PERMIT REQUIRED WITH
 ZONING APPROVAL OF GENERATOR PLACEMENT.
 NOTE:PER 404.12 OUTLET CLOSURES. GAS
 OUTLETS THAT DO NOT CONNECT TO
 APPLIANCES SHALL BE CAPPED GAS TIGHT.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-04-21 Cont ID  
Sent By mperson Date 2006-04-21 Time 16:35 Rev Time 0.33
Received By mperson Date 2006-04-21 Time 16:34 Sent To PC
Notes
2006-04-21 00:00:00REVISION: ADDED 2"X2"X1-1/4" TEE, 1-1/4"
 VALVE, 1-1/4" NIPPLE AND CAP FOR FUTURE
 GENERATOR.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-04-17 Cont ID  
Sent By mperson Date 2006-04-17 Time 13:10 Rev Time 0.45
Received By mperson Date 2006-04-17 Time 13:10 Sent To PC
Notes
2006-04-17 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS, AND CITY
 OF WEST PALM BEACH, AMENDMENTS TO
 FBC-2004, CHAPTER 1, ADMINISTRATION:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR THE GAS REVISION:
  
 1. PER CITY AMENDMENTS SECTION 106
 CONSTRUCTION DOCUMENTS: 106.1 SUBMITTAL
 DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS, AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNITURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 2. PER FBC 2004 FUEL GAS, INDICATE ON
 THE REVISION THE TYPE OF PIPING MATERIAL
 BEING USED.
 3. PLEASE CLARIFY DELIVERY PRESSURE, RE-
 VISION INDICATES 2.5 LB PSI. DELIVERY
 PRESSURE IS EITHER A 0.5 LB PSI OR A 2
 LB PSI SYSTEM. CLEARLY INDICATE ON THE
 DRAWING THE DELIVERY PRESSURE. NOTE: IF
 SYSTEM IS BEING REVISED TO A 2 LB PSI
 SYSTEM SUBMIT MANUFACTURE SHEETS FOR 2LB
 PSI REGULATORS, AND INDICATE THEIR
 LOCATION ON THE DRAWING PER FBC-2004
 FUEL GAS SEC. 402.2
 4. FUTURE GENERATOR INDICATED ON DRAWING
 NEEDS TO HAVE A SHUT OFF VALVE AND A
 HARD CAP (PRESSURE CAP) INDICATED ON
 DRAWING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-07-18 Cont ID  
Sent By jleech Date 2005-07-18 Time 08:16 Rev Time 0.50
Received By jleech Date 2005-07-18 Time 08:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-06-23 Cont ID  
Sent By pschmitz Date 2005-06-23 Time 10:35 Rev Time 0.00
Received By pschmitz Date 2005-06-23 Time 10:35 Sent To PC
Notes
2005-06-24 00:00:00DENIED
 GAS: PLAN REVIEW:FBC 2001 FUEL GAS
 FBC 2001 CHAPTER 1
  
 GENERATOR PERMITTING CHECKLIST
 (1 ) NO PERMIT PERTAINING TO A GENERATOR
 SHALL BE ISSUED UNTIL AN APPLICATION FOR
 THE GENERATOR IS APPLIED FOR.
 A REVIEW FOR THE GENERATOR IS REQUIRED.
 BUILDING,ELECTRIC,MECHANICAL, FUEL GAS,
 AND ZONING.
 THE BUILDING: REVIEW WILL BE FOR SLAB
 AND ANCHORING, FBC WIND LOADS 140 MPH.
 ELECTRICAL: RISER DRAWING, SIZE OF
 TRANSFERE SWITCH AND GENERATOR, SUBMIT
 MANFACTURES SPECIFICATION SHEETS.
 MECHANICAL: EXHAIST SYSTEM, CLEARANCES.
 FUEL GAS: GAS PERMIT APPLICATION
 REQUIRMENTS.
 ZONING: SITE SURVEY, SHOW LOCATION OF
 GENERATOR.
 (2) SECTION 104.2.1
 ALL INFORMATION, DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 (3)DISCRIPTION OF WORK ON THE
 APPLICATION: DESCRIBE PROJECT IN DETAIL.
 (3) SHOW THE TYPE OF PIPING MATERIAL
 BEING INSTALLED.
 (4)TYPE OF GAS ( L-P OR NATURAL)
 (5)SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMATION OF THE GAS
 VENTS PER.
 SEC 502 THRU 506.
 (6) SUBMIT MANFACTURE SHEETS FOR 2# PSI
 GAS REGULATORS, AND LOCATION.
 END OF COMMENTS, QUESTIONS CONTACT
 PAUL SCHMITZ 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 09:52 Sent To G
Notes
2006-04-21 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-04-11 Time 08:55 Rev Time 0.00
Received By adarroug Date 2006-04-11 Time 08:55 Sent To G
Notes
2006-04-11 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 15:04 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 15:04 Sent To G
Notes
2005-07-01 00:00:00TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 15:41 Rev Time 0.00
Received By shill Date 2005-06-08 Time 15:41 Sent To G
Notes
***NONE***