Plan Review Details - Permit 05060716
Plan Review Stops For Permit 05060716
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-06 Cont ID  
Sent By shill Date 2005-09-06 Time 09:27 Rev Time 0.50
Received By shill Date 2005-09-06 Time 09:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-27 Cont ID  
Sent By shill Date 2005-08-27 Time 15:53 Rev Time 1.00
Received By shill Date 2005-08-27 Time 15:53 Sent To  
Notes
2005-08-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 COMMENTS FROM PREVIOUS REVIEW.
 NUMBERING HAS REMAINED THE SAME AS
 PREVIOUS REVIEW TO MAINTAIN CONSISTENCY:
  
 3.)THE TRUSS ENGINEERING AND TRUSS
 LAYOUT PREPARED BY HIRMET TUMAY, PE DO
 NOT HAVE A TITLE BLOCK FAC61G15-23.002.
  
 6.)HAVE THE TRUSS LAYOUT AND
 ENGINEERING REVIEWED BY ENGINEER OF
 RECORD FAC61G15-30.003(2).
 THE LAYOUT AND ENGINEERING WERE REVIEWED
 BY THE REVIEW LETTER REFERS TO THE WRONG
 BUILDING CODE.
  
 NEW COMMENT - TWO SIGNED SEALED
 ORIGINALS OF ALL DOCUMENTS REQUIRED.
 ONLY ONE SET SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-25 Cont ID  
Sent By shill Date 2005-07-25 Time 17:59 Rev Time 1.00
Received By shill Date 2005-07-25 Time 17:59 Sent To PC
Notes
2005-07-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CHANGES TO THE PLAN ARE TO BE
 CLOUDED AND, IF DONE IN INK, TO BE
 INITIALED BY THE ENGINEER.
  
 2.)THE WIND DESIGN CRITERIA
 FBC1606.1.7 IS TO BE A PART OF THE PLAN,
 NOT AN UNSIGNED AND UNSEALED SHEET.IT
 IS TO BE DONE BY THE ENGINEER.
  
 3.)THE TRUSS ENGINEERING AND TRUSS
 LAYOUT PREPARED BY HIRMET TUMAY, PE DO
 NOT HAVE A TITLE BLOCK FAC61G15-23.002.
  
 4.)THE TRUSS ENGINEERING HAS A STAMP
 INSTEAD OF A SIGNATURE.EACH SHEET IS
 TO BE SIGNED BY THE ENGINEER, NOT
 STAMPED.PLEASE CONTACT FBPE IF YOU ARE
 NOT IN AGREEMENT AND HAVE THEM EMAIL OR
 CALL ME.IN PRIOR CONVERSATIONS WITH
 FBPE THEY HAVE INSISTED ON A "WET
 SIGNATURE".
  
 5.)THE STANDARD GABLE END DETAIL,
 STGBL77 IS NOT SIGNED AND SEALED.
 INDICATE ON THAT SHEET THE WIND DESIGN
 CRITERIA AND THAT FBC2313.4.1 HAS BEEN
 MET.THIS IS BEING REQUESTED BECAUSE
 THE DETAIL DOES NOT INCLUDE BLOCKING AND
 ADDITIONAL BRACING SHOWN IN BCSI-B6
 PREPARED BY TPI AND WTCA.ALSO NOTE
 THAT THE SAMPLE PROVIDED WAS FOR 100MPH
 WIND ZONE, BUT HAD MORE BRACING.
  
 6.)HAVE THE TRUSS LAYOUT AND
 ENGINEERING REVIEWED BY ENGINEER OF
 RECORD FAC61G15-30.003(2).
  
 7.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF THE
 COMMENTS ARE NOT CORRECTLY ADDRESSED.
  
 8.)NEW COMMENT - THE APPLICATION
 STATES "WITH SCREEN".NO SCREEN IS
 SHOWN ON THE PLAN.EITHER INCORPORATE
 YOUR SCREEN STRUCTURAL DETAILS INTO YOUR
 PLAN OR REMOVE FROM THE APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By shill Date 2005-06-21 Time 15:13 Rev Time 1.00
Received By shill Date 2005-06-21 Time 15:02 Sent To E
Notes
2005-06-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A TITLE BLOCK IN COMPLIANCE WITH
 FAC61G15-23.002 IS REQUIRED.
  
 2.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 3.)SPECIFY CEILING FINISH.
  
 4.)SPECIFY WIND DESIGN CRITERIA
 FBC1606.1.7.
  
 5.)FBC2313.4.1, GABLE ENDWALLS SHALL
 BE STRUCTURALLY CONTINUOUS BETWEEN
 POINTS OF LATERAL SUPPORT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By jleahy Date 2005-07-25 Time 12:01 Rev Time 0.30
Received By jleahy Date 2005-07-25 Time 12:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-25 Cont ID  
Sent By jleahy Date 2005-06-25 Time 21:25 Rev Time 0.30
Received By jleahy Date 2005-06-25 Time 20:01 Sent To  
Notes
2005-06-26 00:00:00SEE NOTES FOR BUILDING PLANS EXAMINER.
  
 JL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 16:50 Sent To B
Notes
2005-09-02 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 13:41 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 13:41 Sent To B
Notes
2005-08-19 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 15:41 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 15:41 Sent To E
Notes
2005-07-21 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 11:06 Rev Time 0.00
Received By shill Date 2005-06-20 Time 11:06 Sent To B
Notes
2005-06-20 00:00:00TO MISC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 15:29 Rev Time 0.00
Received By shill Date 2005-06-08 Time 15:29 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-17 Cont ID  
Sent By mmclean Date 2005-06-17 Time 17:42 Rev Time 0.00
Received By mmclean Date 2005-06-17 Time 17:42 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved