Plan Review Details - Permit 05060675
Plan Review Stops For Permit 05060675
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-28 Cont ID  
Sent By jgomez Date 2006-02-28 Time 07:55 Rev Time 0.33
Received By jgomez Date 2006-02-28 Time 07:55 Sent To P
Notes
2006-02-28 00:00:00DRAWING A-1.0 SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-02-14 Cont ID  
Sent By jgomez Date 2006-02-14 Time 08:05 Rev Time 0.00
Received By jgomez Date 2006-02-16 Time 14:57 Sent To P
Notes
2006-02-14 00:00:00BUILDING REVISION CHECKLIST:
 1- PLUMBING RISER DIAGRAM WAS CROSSED
 OUT ON DRAWING A-1.0. PLUMBING RISER
 DIAGRAM IS PART OF THE CONSTRUCTION
 DOCUMENTS SUBMITTED BY THE ARCHITECT FOR
 APPROVAL AND CAN'T BE ARBITRARILY
 CROSSED OUT TO AVOID REVIEWS. PROVIDE
 CLEAN DRAWINGS.
  
 2- REMAINDER: APPLY FOR STORM SHUTTERS
 AS AGREED ON PROVISO TO AVOID DELAYS OR
 CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-01-19 Cont ID  
Sent By jgomez Date 2006-01-19 Time 13:54 Rev Time 0.50
Received By jgomez Date 2006-01-19 Time 13:54 Sent To PC
Notes
2006-01-19 00:00:00BUILDING REVISION CHECKLIST:
 1- PLUMBING RISER DIAGRAM IN DRAWING
 A-1.0 WAS CROSSED OUT. PLUMBING RISER
 DIAGRAM IS PART OF THE CONSTRUCTION
 DOCUMENTS AND IT CAN'T BE CROSSED OUT.
 RE-SUBMIT CLEAN DRAWINGS.
  
 2- PRODUCT APPROVAL FOR 12'-0" SLIDING
 GLASS DOORS IS INCOMPLETE. FLORIDA
 PRODUCT APPROVAL REPORT AND DADE COUNTY
 NOA ARE MISSING PAGES. PROVIDE COMPLETE
 PACKAGE.
  
 3- APPLY FOR STORM SHUTTERS PERMIT AS
 AGREED ON PROVISO TO AVOID DELAYS OR
 CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2006-01-10 Time 10:13 Rev Time 0.50
Received By jgomez Date 2005-11-15 Time 11:22 Sent To PC
Notes
2005-11-15 00:00:00NEED TO PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT
 AS AGREED ON PROVISO DATED 7-25-05.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-23 Cont ID  
Sent By jgomez Date 2005-09-23 Time 17:58 Rev Time 0.33
Received By jgomez Date 2005-09-23 Time 17:58 Sent To PC
Notes
2005-09-23 00:00:00REVISED SURVEY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-07-25 Cont ID  
Sent By jgomez Date 2005-07-25 Time 13:57 Rev Time 2.00
Received By jgomez Date 2005-07-25 Time 13:57 Sent To PC
Notes
2005-07-25 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- CLARIFY DOOR/WINDOW SCHEDULE. DON'T
 MIX TOGETHER DOOR/WINDOW SYMBOLS.
 3- REVISE DETAIL 5/D1: HTS20 CONNECTOR
 CAN'T SUPPORT GIRDER TRUSS.
 4- UPDATE HUS26 NAIL SIZE.SEE CATALOGUE
 5- REVISE CONNECTOR SPECIFIED AT ENTRY
 PORCH TO MATCH DETAILS 5/D1 AND 6/D1.
 6- RE-SUBMIT PRODUCT APPROVAL FOR:
 A)ROOF TILE, B)SINGLE HUNG WINDOWS,
 C)FIXED WINDOWS.
 7- SHEET A-5 SHEAR VALUES NOTE: PROVIDE
 HAND CALCULATIONS. WHY USING TIMBER
 CONSTRUCTION MANUAL FOR TAPCON VALUES.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-09-30 Cont ID  
Sent By dpalmer Date 2006-09-30 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 19:30 Sent To PC
Notes
2006-09-30 00:00:00REVOK,
 REDLINED A LT FIXTURE OF SOME SORT
 REQUIRED FOR REAR EGRESS, SHOWS ONLY A
 J-BOX.
 LS 101 7.8, 210.70 NEC.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 07:56 Sent To B
Notes
2006-02-09 00:00:00** REDLINED **
  
 VERIFY OCP FOR CU, SHOWS 9.8KW, 40A OCP
  
 MIN 8' GROUND ROD REQUIRED PER 250.52A
  
 VERIFY MIN OCP FOR AHU#2, PER 424.3B,
 MIN OCP 125%.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 19:36 Sent To PC
Notes
2006-02-03 00:00:00REDLINED:
  
 MIN GRND ROD 8" PER 250.52A5
  
 MIN OCP FOR AHU#2, 125% MIN. (60A'S)

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-10 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2006-01-09 Time 09:18 Sent To B
Notes
2006-01-09 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE PANEL "A" IS MISSING
 LOAD FROM PANEL "B"AND "C".
 PLEASE ALSO SEE LOADS ON PANEL "B" AND
 "C". SOME ARE SHOWN WITH 83 KW, 96, KW
 ETC.
 PLEASE ADJUST LOADS AND CALCUALTIONS.
 220, 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 09:08 Rev Time 0.25
Received By dpalmer Date 2005-06-24 Time 09:08 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 14:07 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 14:07 Sent To E
Notes
2006-09-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 18:23 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 18:23 Sent To E
Notes
2006-02-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:56 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:56 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 09:17 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 09:17 Sent To E
Notes
2005-12-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 10:37 Sent To B
Notes
2005-10-14 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 08:04 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 08:04 Sent To B
Notes
2005-09-23 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 14:36 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 14:36 Sent To B
Notes
2005-09-15 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 10:38 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 10:38 Sent To E
Notes
2005-06-21 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-25 Cont ID  
Sent By shill Date 2005-07-25 Time 14:10 Rev Time 0.00
Received By jgomez Date 2005-06-10 Time 09:41 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By pkrauss Date 2005-07-06 Time 10:13 Rev Time 0.35
Received By pkrauss Date 2005-07-06 Time 09:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-28 Cont ID  
Sent By jleech Date 2006-02-28 Time 18:18 Rev Time 0.00
Received By jleech Date 2006-02-28 Time 18:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-16 Cont ID  
Sent By jleech Date 2006-02-16 Time 15:02 Rev Time 0.25
Received By jleech Date 2006-02-16 Time 15:02 Sent To B
Notes
2006-02-16 00:00:00PLEASE DO NOT "X" OUT PARTS OF THE PLAN.
 IF REVISIONS ARE REQUIRED THE PLANS NEED
 TO BE REVIEWED AND RESTAMPED BY ALL
 TRADES INVALVED.
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-06-25 Cont ID  
Sent By jleech Date 2005-06-25 Time 07:12 Rev Time 0.25
Received By jleech Date 2005-06-25 Time 07:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By mmclean Date 2005-09-22 Time 14:53 Rev Time 0.00
Received By mmclean Date 2005-09-22 Time 14:53 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By jgomez Date 2005-07-25 Time 14:10 Rev Time 0.00
Received By mmclean Date 2005-06-20 Time 14:42 Sent To I
Notes
***NONE***