Plan Review Details - Permit 05060663
Plan Review Stops For Permit 05060663
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-28 Cont ID  
Sent By jgomez Date 2006-02-28 Time 09:20 Rev Time 0.33
Received By jgomez Date 2006-02-28 Time 09:20 Sent To P
Notes
2006-02-28 00:00:00DRAWING A-1.0 SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-14 Cont ID  
Sent By jgomez Date 2006-02-14 Time 12:42 Rev Time 0.40
Received By jgomez Date 2006-02-14 Time 12:42 Sent To P
Notes
2006-02-14 00:00:00BUILDING REVISION CHECKLIST:
 1- PLUMBING RISER DIAGRAM ON SHEET A-1.0
 WAS CROSSED OUT BY HAND. PLUMBING RISER
 DIAGRAM IS PART OF THE CONSTRUCTION
 DOCUMENTSSUBMITTED BY THE ARCHITECT
 AND IT CAN'T BE CROSSED OUT. SUBMIT
 CLEAN DRAWING FOR PROPER TRADE REVIEW
 ROUTING.
  
 2- APPLY FOR SHUTTERS UNDER A SEPARATE
 PERMIT AS AGREED ON PROVISO TO AVOID
 DELAYS OR CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-19 Cont ID  
Sent By jgomez Date 2006-01-19 Time 08:00 Rev Time 0.50
Received By jgomez Date 2006-01-19 Time 07:57 Sent To PC
Notes
2006-01-19 00:00:00BUILDING REVISION CHECKLIST:
 1- PLUMBING RISER DIAGRAM IN DRAWING
 A-1.0 WAS CROSSED OUT. PLUMBING RISER
 DIAGRAM IS PART OF THE CONSTRUCTION
 DOCUMENTS AND IT CAN'T BE CROSSED OUT.
 RE-SUBMIT CLEAN DRAWINGS.
  
 2- PRODUCT APPROVAL SUBMITTED FOR
 SLIDING GLASS DOORS IS INCOMPLETE. THE
 FLORIDA PRODUCT APPROVAL REPORT AND THE
 DADE NOA REPORT ARE MISSING PAGES.
 RE-SUBMIT COMPLETE PACKAGE.
  
 3- APPLY FOR STORM SHUTTERS AS AGREED ON
 PROVISO TO AVOID DELAYS OR CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By jgomez Date 2005-09-22 Time 10:47 Rev Time 0.50
Received By jgomez Date 2005-09-22 Time 10:47 Sent To PC
Notes
2005-09-22 00:00:00CORRECTED DRAWINGS AND REQUESTED PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-07-25 Cont ID  
Sent By jgomez Date 2005-07-25 Time 11:54 Rev Time 2.00
Received By jgomez Date 2005-07-25 Time 11:54 Sent To PC
Notes
2005-07-25 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- NEED WORST CASE SCENARIO ENERGY CALCS
 3- CLARIFY DOOR/WINDOW SCHEDULE. DON'T
 MIX TOGETHER DOOR/WINDOW SYMBOLS.
 4- REVISE DETAIL 5/D1: CONNECTOR HTS20
 CAN'T SUPPORT BEAM.
 5- UPDATE HUS26 NAIL SIZE.SEE CATALOGUE
 6- REVISE CONNECTOR SPECIFIED AT ENTRY
 PORCH TO MATCH DETAILS 5/D1 AND 6/D1
 7- RE-SUBMIT PRODUCT APPROVAL FOR:
 A)ROOF TILE, B)SINGLE HUNG WINDOWS,
 C)FIXED WINDOWS.
 8- SHEET A-5 SHEAR VALUES NOTE: PROVIDE
 HAND CALCULATIONS. WHY USING TIMBER
 CONSTRUCTION MANUAL FOR TAPCON VALUES?

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 07:05 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 21:49 Sent To B
Notes
2006-02-09 00:00:00** REDLINED **
  
 VERIFY OCP FOR CU, SHOWS 9.8KW, 40A OCP
  
 MIN 8' GROUND ROD REQUIRED PER 250.52A
  
 VERIFY MIN OCP FOR AHU#2, PER 424.3B,
 MIN OCP 125%.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 19:07 Sent To PC
Notes
2006-02-03 00:00:00**** REDLINED
  
  
 424.3B , MIN OCP FOR AHU #2 SHALL BE
 SIZED AT 125% MIN.
  
 GRND ROD TO BE A MIN OF 8' PER 250.52A5

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-10 Cont ID  
Sent By dpalmer Date 2006-01-10 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2006-01-10 Time 10:56 Sent To B
Notes
2006-01-10 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE PANEL "A" IS MISSING
 LOAD FROM PANEL "B"AND "C".
 PLEASE ALSO SEE LOADS ON PANEL "B" AND
 "C". SOME ARE SHOWN WITH 83 KW, 96, KW
 ETC.
 PLEASE ADJUST LOADS AND CALCUALTIONS.
 220, 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
 3)NOTE: PLEASE SEE SOME CIRCUITING SHOWN
 ON PLANS AND OTHERS NOT SHOWN. PLEASE
 SEE CIRCUIT A-38 ON PLANS AND BLANK ON
 SCHEDULE.
 EITHER SHOW ALL CIRCUITING AND CORRELATE
 WITH PANEL SCHEDULE OR DO NOT SHOW ANY
 CIRCUITING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 08:03 Rev Time 0.20
Received By dpalmer Date 2005-06-24 Time 08:03 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 18:13 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 18:13 Sent To E
Notes
2006-02-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:54 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:54 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 09:41 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 09:41 Sent To E
Notes
2005-12-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 10:27 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 10:27 Sent To B
Notes
2005-08-24 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 10:37 Sent To E
Notes
2005-06-21 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-25 Cont ID  
Sent By shill Date 2005-07-25 Time 13:24 Rev Time 0.00
Received By jgomez Date 2005-06-10 Time 09:42 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By pkrauss Date 2005-07-06 Time 10:57 Rev Time 0.35
Received By pkrauss Date 2005-07-06 Time 10:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-28 Cont ID  
Sent By jleech Date 2006-02-28 Time 18:00 Rev Time 0.00
Received By jleech Date 2006-02-28 Time 17:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-17 Cont ID  
Sent By jleech Date 2006-02-17 Time 07:25 Rev Time 0.25
Received By jleech Date 2006-02-17 Time 07:25 Sent To B
Notes
2006-02-17 00:00:00PLEASE DO NOT "X" OUT PARTS OF THE PLAN.
 IF REVISIONS ARE REQUIRED THE PLANS NEED
 TO BE REVIEWED AND RESTAMPED BY ALL
 TRADES INVALVED.
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-25 Cont ID  
Sent By jleech Date 2005-06-25 Time 06:51 Rev Time 0.25
Received By jleech Date 2005-06-25 Time 06:51 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By jgomez Date 2005-07-25 Time 13:24 Rev Time 0.00
Received By mmclean Date 2005-06-20 Time 16:37 Sent To I
Notes
***NONE***