Plan Review Details - Permit 05060659
Plan Review Stops For Permit 05060659
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-06 Cont ID  
Sent By jgomez Date 2006-02-06 Time 17:59 Rev Time 0.40
Received By jgomez Date 2006-02-06 Time 17:44 Sent To PC
Notes
2006-02-06 00:00:00ATRIUM DOOR REVISION AND PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-07 Cont ID  
Sent By jgomez Date 2005-12-07 Time 17:07 Rev Time 0.75
Received By jgomez Date 2005-12-07 Time 17:07 Sent To PC
Notes
2005-12-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENERGY CALCULATIONS SUBMITTED ARE FBC
 2004 FORMS. NEED TO PROVIDE FBC 2001
 FORMS, SINCE PLANS WERE REVIEWED UNDER
 FBC 2001.
  
 2- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ATRIUM DOOR AS REQUIRED BY
 RULE 9B-72 OF DCA.
 ***NOTE: SEE PLANS FOR SIZE AND SWING
 DIRECTION OF DOOR.
  
 3- OWES $70.00 FOR REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-22 Cont ID  
Sent By jgomez Date 2005-09-22 Time 11:31 Rev Time 0.50
Received By jgomez Date 2005-09-22 Time 11:31 Sent To PC
Notes
2005-09-22 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1- ENERGY CALCS: ROBIN FROM KENCO COMM.
 CALLED TO SAY THAT ENERGY CALCS WILL BE
 CHANGED AGAIN FROM WORST CASE TO
 SPECIFIC HOUSE ORIENTATION. SUBMIT
 REVISED CALCS.
  
 2- SEPARATE PERMIT FOR SHUTTERS IS NOT
 DONE YET.
  
 3- REVISE ROOF FRAMING PLAN AT ENTRY
 PORCH AREA. CONCRETE BEAM DOESN'T EXTEND
 TO THE FOYER AREA. ALSO, KNEEWALL IS NOT
 CONCRETE EITHER. REVISE FRAMING PLANS
 AND SPECIFY CORRESPONDING CONNECTORS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS SPECIFIED FOR HUS26. SEE 2005
 CATALOGUE.
  
 5- PROVIDE 1 HR FIRE RATED DOOR AT
 ATRIUM WITH SWING AS SHOWN ON PLANS.
  
 6- WINDOW MULLION SIZE SPECIFIED FOR
 FIXED WINDOWS AT GREAT ROOM DOESN'T
 RESIST THE DESIGN PRESSURES. REVISE AS
 REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLION SPECIFIED ABOVE FOR FIXED
 WINDOWS AT GREAT ROOM.
  
 ***NOTE:
 REVISED DRAWINGS WILL BE SUBJECT TO
 REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-26 Cont ID  
Sent By jgomez Date 2005-07-26 Time 10:32 Rev Time 0.33
Received By jgomez Date 2005-07-26 Time 10:32 Sent To PC
Notes
2005-07-26 00:00:00STAMPED PLANS BY PALM BEACH COUNTY FOR
 IMPACT FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date 2005-07-19 Cont ID  
Sent By jgomez Date 2005-07-19 Time 14:37 Rev Time 2.00
Received By jgomez Date 2005-07-19 Time 14:37 Sent To PC
Notes
2005-07-19 00:00:00BUILDING REVIEW PROVISO:
 1- NEED WORST CASE SCENARIO ENERGY CALCS
 2- SHUTTERS UNDER A SEPARATE PERMIT.
 3- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT FRONT PORCH TO MATCH
 DETAILS 4/D1 AND 5/D1.
 4- REVISE NAIL SIZE FOR HUS26 CONNECTOR.
 5- SPECIFY SIZE AND ANHORS FOR MULLION
 AT LARGE WINDOWS IN GREAT ROOM AREA.
 6- RE-SUBMIT PRODUCT APPROVAL FOR:
 A) 1 HR FIRE RATED ATRIUM DOOR ASSEMBLY.
 B) FIXED WINDOWS.
 C) SINGLE HUNG WINDOWS.
 D) ROOF TILE.
 E) WINDOW MULLION SPECIFIED FOR LARGE
 FIXED WINDOWS AT GREAT ROOM AREA.
 7- PROVIDE CLEAR DOOR/WINDOW SCHEDULES.
 NO MIXING DOOR & WINDOW SYMBOLS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-28 Cont ID  
Sent By dpalmer Date 2006-02-28 Time 18:30 Rev Time 0.00
Received By dpalmer Date 2006-02-28 Time 18:26 Sent To PC
Notes
2006-02-28 00:00:00REV OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 16:18 Sent To PC
Notes
2006-02-03 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE OCP HAS NOW BEEN
 INCREASED FOR PANEL "B" TO 125A'S,
 HOWEVER PLEASE SEE RISER HAS NOT
 INCREASED PANEL, FEEDERS AND PANEL
 SCHEDULE ALSO SHOWS 100A.
 PLEASE CORRELATE , UPGRADE PANEL,
 FEEDERS ETC.
  
 240.4,310.15B6, 215.5 ETC.
  
 2)NOTE: PLEASE SEE MIN GRND ROD AT 8'
 PER 250.52A5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 07:52 Rev Time 0.30
Received By dpalmer Date 2005-06-24 Time 07:52 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 09:48 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 09:48 Sent To E
Notes
2006-02-24 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 11:40 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 11:40 Sent To B
Notes
2006-02-06 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 13:10 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 13:10 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 09:13 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 09:13 Sent To B
Notes
2005-10-19 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 09:05 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 09:05 Sent To B
Notes
2005-10-19 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 10:44 Sent To B
Notes
2005-08-24 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 10:17 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 10:17 Sent To B
Notes
2005-07-26 00:00:00TO "JGOMEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 10:40 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 10:40 Sent To E
Notes
2005-06-21 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-19 Cont ID  
Sent By shill Date 2005-07-19 Time 15:44 Rev Time 0.00
Received By jgomez Date 2005-06-10 Time 09:37 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By pkrauss Date 2005-07-06 Time 10:42 Rev Time 0.35
Received By pkrauss Date 2005-07-06 Time 10:34 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-25 Cont ID  
Sent By jleech Date 2005-06-25 Time 06:43 Rev Time 0.25
Received By jleech Date 2005-06-25 Time 06:43 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By jgomez Date 2005-07-19 Time 15:44 Rev Time 0.00
Received By mmclean Date 2005-06-20 Time 14:19 Sent To I
Notes
***NONE***