Plan Review Details - Permit 05060616
Plan Review Stops For Permit 05060616
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-13 Cont ID  
Sent By btrobaug Date 2005-07-13 Time 13:24 Rev Time 0.50
Received By btrobaug Date 2005-07-13 Time 13:09 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By btrobaug Date 2005-06-22 Time 10:33 Rev Time 0.50
Received By btrobaug Date 2005-06-21 Time 12:40 Sent To M
Notes
2005-06-22 00:00:00 
 PLEASE INDICATE THE RATING AND OCP OF
 THE DISCONNECT AND SUB-PANEL FOR THE
 GENERATOR.
  
 SHOW THE LOCATION OF ALL EQUIPMENT ON A
 SITE PLAN.
  
 INDICATE THE PRIME MOVER IN THE SPEC OR
 ON THE DRAWING.
  
 THE FEEDERS ARE # 6 FROM A 100AMP
 GENERATOR. PLEASE SEE 445.13,
 310.15(B)(6) FOR CORRECT SIZING.
  
 CALL WITH ANY QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-07-13 Cont ID  
Sent By jleech Date 2005-07-13 Time 13:53 Rev Time 0.50
Received By jleech Date 2005-07-13 Time 13:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By jleech Date 2005-06-27 Time 09:01 Rev Time 0.50
Received By jleech Date 2005-06-27 Time 09:01 Sent To M
Notes
2005-06-27 00:00:00ZONING MUST APPROVE LOCATION OF
 GENERATOR BEFORE GAS PERMIT CAN BE
 ISSUED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:03 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:03 Sent To E
Notes
2005-07-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 11:04 Rev Time 0.00
Received By shill Date 2005-06-20 Time 11:04 Sent To E
Notes
2005-06-20 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 15:06 Rev Time 0.00
Received By shill Date 2005-06-08 Time 15:06 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By hmoser Date 2005-07-06 Time 10:28 Rev Time 0.00
Received By hmoser Date 2005-07-06 Time 10:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 09:23 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 09:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-17 Cont ID  
Sent By mmclean Date 2005-06-17 Time 17:46 Rev Time 0.00
Received By mmclean Date 2005-06-17 Time 17:46 Sent To I
Notes
2005-06-17 00:00:00DENIED,
 1. MUST PROVIDE THE DISTANCE THE
 GENERATOR WILL BE FROM THE STRUCTURE OF
 THE HOUSE, SIDE OF THE PROPERTY AND REAR
 OF PROPERTY.
 2. GENERATOR CANNOT BE IN THE 5FT
 UTILITY EASEMENT IN REAR OF PROPERTY
 3. MUST PROVIDE THE DIMENSION OF THE
 GENERAOR.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720