Plan Review Details - Permit 05060616
Plan Review Stops For Permit 05060616 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2005-07-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-07-13 |
Time |
13:24 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-07-13 |
Time |
13:09 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-22 |
Time |
10:33 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-06-21 |
Time |
12:40 |
Sent To |
M |
|
Notes |
2005-06-22 00:00:00 | | | PLEASE INDICATE THE RATING AND OCP OF | | THE DISCONNECT AND SUB-PANEL FOR THE | | GENERATOR. | | | | SHOW THE LOCATION OF ALL EQUIPMENT ON A | | SITE PLAN. | | | | INDICATE THE PRIME MOVER IN THE SPEC OR | | ON THE DRAWING. | | | | THE FEEDERS ARE # 6 FROM A 100AMP | | GENERATOR. PLEASE SEE 445.13, | | 310.15(B)(6) FOR CORRECT SIZING. | | | | CALL WITH ANY QUESTIONS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2005-07-13 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-07-13 |
Time |
13:53 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2005-07-13 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2005-06-27 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-06-27 |
Time |
09:01 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2005-06-27 |
Time |
09:01 |
Sent To |
M |
|
Notes |
2005-06-27 00:00:00 | ZONING MUST APPROVE LOCATION OF | | GENERATOR BEFORE GAS PERMIT CAN BE | | ISSUED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-07-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-12 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-12 |
Time |
15:03 |
Sent To |
E |
|
Notes |
2005-07-12 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-20 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-20 |
Time |
11:04 |
Sent To |
E |
|
Notes |
2005-06-20 00:00:00 | TO ELEC BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-08 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-08 |
Time |
15:06 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2005-07-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-07-06 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-07-06 |
Time |
10:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-07-11 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-07-11 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-07-11 |
Time |
09:23 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-06-17 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-06-17 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-06-17 |
Time |
17:46 |
Sent To |
I |
|
Notes |
2005-06-17 00:00:00 | DENIED, | | 1. MUST PROVIDE THE DISTANCE THE | | GENERATOR WILL BE FROM THE STRUCTURE OF | | THE HOUSE, SIDE OF THE PROPERTY AND REAR | | OF PROPERTY. | | 2. GENERATOR CANNOT BE IN THE 5FT | | UTILITY EASEMENT IN REAR OF PROPERTY | | 3. MUST PROVIDE THE DIMENSION OF THE | | GENERAOR. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
|