Plan Review Stops For Permit 05060508 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2005-10-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-10-05 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-10-05 |
Time |
12:23 |
Sent To |
B |
|
Notes |
2005-10-05 00:00:00 | ***LOCAL/SITE SPECIFIC PRODUCT APPROVAL | | SENT TO RB DESK*** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | A 4X FEE FOR WORKING WITHOUT A PERMIT | | HAS BEEN CHARGED, CALCULATED AS FOLLOWS: | | | | | | $ 38,500DECK VALUE($17500SF@$2.20/SF) | | | | $770FEE 2% FOR FIRST $50K | | X4FINE | | -------- | | $ 3,080TOTAL 4X FEE | | (50) LESS SUB PERMIT FEE PAID | | (700) LESS PERMIT FEE PAID | | -------- | | $ 2,330TOTAL DUE FOR 4X FEE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2005-10-04 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-10-04 |
Time |
11:41 |
Rev Time |
1.00 |
Received By |
alange |
Date |
2005-10-04 |
Time |
11:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2005-09-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-09-16 |
Time |
14:05 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-09-16 |
Time |
14:05 |
Sent To |
PC |
|
Notes |
2005-09-16 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | FROM PREVIOUS REVIEW - | | | | 1.)THE CERTIFICATE OF AUTHORIZATION | | NUMBER FOR C-BUCK ENGINEERING IS | | REQUIRED TO BE ON THE LETTERHEAD AND | | TITLE BLOCK, FAC61G15-23.002. | | | | NOT ADDRESSED.SAME PAPERWORK DATED | | 8/18/05 WAS SUBMITTED. | | | | 2.)ATTACHMENT OF THE STEEL DECK TO THE | | BAR JOISTS IS NOT WITHIN THE SCOPE OF A | | ROOFING CONTRACTOR'S LICENSE.A | | SEPARATE PERMIT OBTAINED BY A CONTRACTOR | | LICENSED TO DO THIS WORK IS REQUIRED.A | | STOP WORK ORDER HAS BEEN ISSUED. | | | | A PERMIT HAS BEEN APPLIED FOR. THIS SUB | | PERMIT CANNOT BE ISSUED UNTIL THE | | PAPERWORK IS COMPLIANT.A 4X FEE HAS | | BEEN CHARGED, CALCULATED AS FOLLOWS: | | | | $193,700VALUE OF CONTRACT | | ( 72,625)ROOF ($17500 SF X $4.15/SF) | | -------- | | $121,075STEEL DECK REMOVE/REPLACE | | | | $1,000FEE 2% FOR FIRST $50K | | $710FEE 1% AMOUNT OVER $50K | | -------- | | $1,710PERMIT FEE, DECK | | X4 | | -------- | | $6840TOTAL 4X FEE | | (50) LESS SUB PERMIT FEE PAID | | -------- | | $6790TOTAL DUE FOR 4X FEE | | | | | | 3.)AS YOU ARE INSTALLING THE ROOF | | SYSTEM NOT IN ACCORDANCE WITH THE STATE | | PRODUCT APPROVAL, A LOCAL PRODUCT | | APPROVAL IS REQUIRED FAC9B72. | | | | NOT ADDRESSED | | | | 4.)THIS IS A REVISION TO THE ISSUED | | PERMIT.INDICATE AS SUCH ON THE | | REVISION/SUBMITTAL FORM, AND SHOULD BE | | CHARGED AS ONE PAGE (LIKE A PRODUCT | | APPROVAL). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2005-08-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-08-27 |
Time |
18:00 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-08-27 |
Time |
18:00 |
Sent To |
|
|
Notes |
2005-08-27 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.)THE CERTIFICATE OF AUTHORIZATION | | NUMBER FOR C-BUCK ENGINEERING IS | | REQUIRED TO BE ON THE LETTERHEAD AND | | TITLE BLOCK, FAC61G15- | | | | 2.)ATTACHMENT OF THE STEEL DECK TO THE | | BAR JOISTS IS NOT WITHIN THE SCOPE OF A | | ROOFING CONTRACTOR'S LICENSE.A | | SEPARATE PERMIT OBTAINED BY A CONTRACTOR | | LICENSED TO DO THIS WORK IS REQUIRED.A | | STOP WORK ORDER HAS BEEN ISSUED. | | | | 3.)AS YOU ARE INSTALLING THE ROOF | | SYSTEM NOT IN ACCORDANCE WITH THE STATE | | PRODUCT APPROVAL, A LOCAL PRODUCT | | APPROVAL IS REQUIRED FAC9B72. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-06-15 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-06-15 |
Time |
13:18 |
Rev Time |
1.50 |
Received By |
mjacobs |
Date |
2005-06-15 |
Time |
13:18 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-06-10 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2005-06-10 |
Time |
12:35 |
Rev Time |
0.75 |
Received By |
mjacobs |
Date |
2005-06-10 |
Time |
12:34 |
Sent To |
PC |
|
Notes |
2005-06-10 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | MYRON JACOBS(561) 805 6726 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC 1606.2.5THE SYSTEM SELECTED | | FROM THE SUBMITTED FLAT ROOF PRODUCT | | APPROVAL NOA HAS A MAXIMUM DESIGN | | PRESSURE OF LESS THAN -89 PSF AND CITES | | GENERAL LIMITATION #9 (SEE PAGE 23 OF | | 31).GENERAL LIMITATION #9 PROHIBITS | | RATIONAL ANALYSIS OR EXTRAPOLATION TO | | ENHANCE THE UPLIFT PRESSURE AT PERIMETER | | AND CORNER AREAS BY REDUCING THE | | FASTENER SPACING IN THESE AREAS.EITHER | | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT | | APPROVAL) THAT DOES NOT CITE GENERAL | | LIMITATION #9.ALTERNATIVELY IF THE | | SELECTED SYSTEM DOES CITE GENERAL | | LIMITATION #9, IT MUST HAVE A MAXIMUM | | DESIGN PRESSURE THAT EXCEEDS THE | | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 | | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR | | LESS). SEE PAGES 24-26 FROM THE REPORT | | FOR MORE INFORMATION. | | | | BUILDING PLAN REVIEW | | MYRON JACOBS | | TEL: (561)805-6726 | | FAX: (561)659-8026 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-06-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2005-06-08 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2005-06-08 |
Time |
12:27 |
Sent To |
|
|
Notes |
2005-06-08 00:00:00 | DENIED | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | STRUCTURE ON THE APPLICATION. | | | | 2) THE DESIGN PRESSURES FOR THE APPROVED | | SYSTEMS THAT WERE SUBMITED WILL NOT MEET | | THE REQUIRED PRESSURES. ON A BUILDING UP | | TO 30 FEET IN HEIGHT WITH A BASIC WIND | | SPEED OF 140 MPH, THE REQUIRED DESIGN | | PRESSURE FOR A FLAT ROOF IN ZONE 3 IS | | -89 PSF. SEE FBC TABLE 1606.2B. | | | | IF YOU HAVE QUESTIONS CALL: | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-10-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-04 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-04 |
Time |
09:22 |
Sent To |
B |
|
Notes |
2005-10-04 00:00:00 | TO "ALANGE" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-09-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-16 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-16 |
Time |
10:50 |
Sent To |
B |
|
Notes |
2005-09-16 00:00:00 | TO "SHILL" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-08-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-08-22 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-08-22 |
Time |
09:01 |
Sent To |
B |
|
Notes |
2005-08-22 00:00:00 | TO SMH DESK |
|
|