Plan Review Stops For Permit 05060468 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2006-02-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-02-06 |
Time |
18:37 |
Rev Time |
0.40 |
Received By |
jgomez |
Date |
2006-02-06 |
Time |
18:37 |
Sent To |
PC |
|
Notes |
2006-02-06 00:00:00 | ENERGY CALCS AND BLDG REVISION. | | NEED TO APPLY FOR SHUTTERS PERMIT AS | | AGREED ON PROVISO. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2005-12-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-12-05 |
Time |
17:19 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2005-12-05 |
Time |
17:19 |
Sent To |
PC |
|
Notes |
2005-12-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- ENERGY CALCS SUBMITTED ARE DONE USING | | FBC 2004 FORM. NEED TO USE FBC 2001 FORM | | WHICH WAS THE CODE PLANS WERE REVIEWED | | FOR. | | | | 2- APPLY FOR STORM SHUTTERS UNDER A | | SEPARATE PERMIT AS AGREED ON PROVISO. | | AVOID DELAYS OR CONFLICTS GIVEN THE | | LARGE VOLUMNE OF PERMIT APPLICATIONS THE | | CITY IS RECEIVING. | | | | 2- PROVIDE PRODUCT APPROVAL FOR | | INSWING, ONE HR FIRE RATED AND8'-0" | | HIGH DOOR AT ATRIUM AS SPECIFIED ON | | PLANS. PRODUCT APPROVAL SUBMITTED IS FOR | | 7'-0" HIGH DOORS. | | | | 3- OWES #70.00 FOR REVISION FEES AS | | NOTED ON CHECKLIST DATED 9-22--05. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-09-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-09-22 |
Time |
13:30 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2005-09-22 |
Time |
13:30 |
Sent To |
PC |
|
Notes |
2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- ACCORDING TO ROBIN FROM KENCO COMM. | | ENERGY CALCS WILL BE REVISED AGAIN TO | | SPECIFIC HOUSE ORIENTATION. RE-SUBMIT | | RE-REVISED ENERGY CALCS. | | | | 2- NEED TO APPLY FOR SHUTTERS PERMIT. | | | | 3- NEED TO REVISE ROOF FRAMING PLAN BY | | ENTRY PORCH ROOF. CONCRETE BEAM DOESN'T | | EXTEND ALL THE WAY TO THE FOYER AREA. | | ALSO, KNEEWALL DOESN'T HAVE CONCRETE | | BEAM. REVISE AS REQUIRED AND SPECIFY | | CORRESPONDING TRUSS CONNECTOR. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001 | | | | 4- TRUSS ANCHOR SCHEDULE: REVISE # OF | | NAILS SPECIFIED FOR HUS26. SEE 2005 | | CATALOGUE. | | | | 5- WINDOW MULLION SIZE SPECIFIED FOR | | FIXED WINDOWS AT GREAT ROOM DOESN'T | | RESIST THE DESIGN PRESSURES. REVISE SIZE | | OF MULLION AS REQUIRED. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | | | 6- PROVIDE PRODUCT APPROVAL FOR: | | A) 1HR FIRE RATED INSWING DOOR AS SHOWN | | IN PLANS BY ATRIUM AREA. | | | | B) WINDOW MULLION SIZE AT GREAT ROOM | | FIXED WINDOWS SPECIFIED IN RE-REVISED | | ITEM #5 ABOVE. | | | | ***NOTE: REVISION FEES WILL APPLY. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER. | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2005-07-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-07-19 |
Time |
10:51 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2005-07-19 |
Time |
10:51 |
Sent To |
PC |
|
Notes |
2005-07-19 00:00:00 | BUILDING REVIEW PROVISO: | | 1- NEED WORST CASE SCENARIO ENERGY CALCS | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT FRONT PORCH. SEE DETAILS | | 4/D1 AND 5/D1. | | 4- REVISE NAIL SIZE FOR HUS26 CONNECTOR. | | 5- SPECIFY SIZE AND ANCHORS FOR LARGE | | FIXED WINDOWS AT GREAT ROOM AREA. | | 6- RE-SUBMIT PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED ATRIUM DOOR ASSEMBLY. | | B) FIXED WINDOWS. | | C) SINGLE HUNG WINDOWS. | | D) ROOF TILE. | | E) LARGE WINDOW MULLION FOR LARGE FIXED | | WINDOWS AT GREAT ROOM. | | 7- PROVIDE CLEAR DOOR AND WINDOW | | SCHEDULE. SYMBOLS USED FOR DOORS AND | | WINDOWS ARE MIXED TOGETHER. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-02-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-02-10 |
Time |
07:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-02-10 |
Time |
07:30 |
Sent To |
PC |
|
Notes |
2006-02-10 00:00:00 | REDLINED: | | | | | | 250.52A5 GRND ROD SHALL BE A MIN OF 8' | | | | VIF OCP FOR CU, SHOWS 9.8KW ON 40A OCP |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2005-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-06-15 |
Time |
15:37 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2005-06-15 |
Time |
15:31 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2006-02-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-03 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-03 |
Time |
15:51 |
Sent To |
B |
|
Notes |
2006-02-03 00:00:00 | TO "JGOMEZ" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-01 |
Time |
18:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-01 |
Time |
18:05 |
Sent To |
E |
|
Notes |
2006-02-01 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-10-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-19 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-19 |
Time |
08:51 |
Sent To |
B |
|
Notes |
2005-10-19 00:00:00 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-08-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-24 |
Time |
18:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-24 |
Time |
18:26 |
Sent To |
B |
|
Notes |
2005-08-24 00:00:00 | TO "JGOMEZ" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-15 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-15 |
Time |
14:10 |
Sent To |
E |
|
Notes |
2005-06-15 00:00:00 | TO RES RACK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-06-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
|
Time |
13:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-06-07 |
Time |
13:11 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-06-17 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-06-17 |
Time |
18:09 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-06-17 |
Time |
17:53 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2005-06-18 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-06-18 |
Time |
08:57 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-06-18 |
Time |
08:57 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-06-14 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-06-14 |
Time |
18:04 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-06-14 |
Time |
18:04 |
Sent To |
I |
|
Notes |
|
|