Plan Review Details - Permit 05060452
Plan Review Stops For Permit 05060452
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-07 Cont ID  
Sent By mjacobs Date 2005-06-07 Time 09:49 Rev Time 0.00
Received By mjacobs Date 2005-06-07 Time 09:49 Sent To M
Notes
2005-06-07 00:00:00TO 'M/AC' BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-24 Cont ID  
Sent By pkrauss Date 2005-06-24 Time 09:42 Rev Time 0.30
Received By pkrauss Date 2005-06-24 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By pkrauss Date 2005-06-07 Time 10:20 Rev Time 0.20
Received By pkrauss Date 2005-06-07 Time 10:17 Sent To  
Notes
2005-06-07 00:00:00DENIED:
 CALLED CONTRACTOR NO ANSWER MACHINE & NO
 ANSWER.
 1.PROVIDE FRESH AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) TABLE 403.3.
  
 2.PLEASE PROVIDE INFORMATION ON THE
 EXISTING WAREHOUSE; INDICATE WHAT IS
 STORED OR WHAT TYPE OF WORK WILL BE DONE
 IN THE WAREHOUSE AREA.
  
 3.INDICATE TERMINATION OF THE
 CONDESATE; MINIMUM OF 12" FROM THE
 BUILDING STRUCTURE PER 2001 FBC
 1503.4.4.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE PER
 2001 FBC(M)606.2.1 & 606.4.1(2).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.