Plan Review Details - Permit 05060428
Plan Review Stops For Permit 05060428
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-06 Cont ID  
Sent By shill Date 2005-08-06 Time 09:33 Rev Time 0.00
Received By shill Date 2005-08-06 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-02 Cont ID  
Sent By shill Date 2005-07-02 Time 11:41 Rev Time 0.50
Received By shill Date 2005-07-02 Time 11:26 Sent To PC
Notes
2005-07-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE A REASONABLE VALUE FOR THIS
 JOB OR AN ESTIMATE USING MARSHALL &
 SWIFT WILL BE DONE AND A VALUE ASSIGNED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-04 Cont ID  
Sent By btrobaug Date 2005-08-04 Time 07:08 Rev Time 0.33
Received By btrobaug Date 2005-08-04 Time 06:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-16 Cont ID  
Sent By btrobaug Date 2005-06-16 Time 11:32 Rev Time 0.33
Received By btrobaug Date 2005-06-16 Time 11:24 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-05 Cont ID  
Sent By adarroug Date 2006-01-05 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-01-05 Time 14:59 Sent To P
Notes
2006-01-05 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 10:02 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 10:02 Sent To P
Notes
2005-07-21 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 12:02 Rev Time 0.00
Received By shill Date 2005-06-15 Time 12:02 Sent To E
Notes
2005-06-15 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:19 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:19 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-23 Cont ID  
Sent By mperson Date 2006-01-23 Time 09:22 Rev Time 1.25
Received By mperson Date 2006-01-23 Time 09:22 Sent To PC
Notes
2006-01-23 00:00:00REVISION
  
 ADDING 400,000 BTU NATURAL GAS POOL
 HEATER

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By btrobaug Date 2005-08-04 Time 10:42 Rev Time 0.50
Received By jleech Date 2005-08-03 Time 14:19 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By kstevens Date 2005-06-22 Time 15:32 Rev Time 1.25
Received By kstevens Date 2005-06-22 Time 15:32 Sent To B
Notes
2005-06-22 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION SHALL BE
 INDICATED ON THE PLANS TO SHOW
 COMPLIANCE WITH SECTION 424:
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES).
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES).
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - NO INLETS ARE SHOWN FOR 2.5HP
 PUMP.
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES).
 5)FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES).
 6. FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLUMBING SEC. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPING AND
 FITTINGS. (ADD TO NOTES).
 B. PIPING SCHEMATIC: MORE INFORMATION IS
 REQUIRED ON SCHEMATIC. INDICATE THE
 INLET UPSTREAM OF THE CARETAKER. WHERE
 DOES THIS ENTER THE POOL OR SPA? SECTION
 104.2.1.
 C. PIPING SCHEMATIC: NO INLET TO 2.5HP
 PUMP. PLEASE CLARIFY. SECTION 104.2.1.
 D. PIPING SCHEMATIC: SHOWS THE AUTO FILL
 LINE AND THE OVERFLOW LINE CONNECTING TO
 THE SUCTION LINE TO THE PUMP DOWNSTREAM
 OF THE SKIMMER. PLEASE CLARIFY. IF THESE
 ARE TIED TO THE SUCTION SIDE OF THE PUMP
 THE OVER FLOW LINE DOES NOT REFLECT THE
 POOL LAYOUT, AND VALVES ARE REQUIRED PER
 SECTION 424.2.8.
 E. ALL DRAWINGS, INFORMATION &
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1. - LAST PAGE IN PLANS
 WITH THE CARETAKER IN-FLOOR POOL
 CLEANING SYSTEM SHALL COMPLY WITH THIS
 SECTION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-14 Cont ID  
Sent By mmclean Date 2005-06-14 Time 17:16 Rev Time 0.00
Received By mmclean Date 2005-06-14 Time 17:16 Sent To PC
Notes
***NONE***