Plan Review Details - Permit 05060145
Plan Review Stops For Permit 05060145
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-15 Cont ID  
Sent By mjacobs Date 2005-11-15 Time 09:47 Rev Time 1.50
Received By mjacobs Date 2005-11-15 Time 08:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 16:30 Rev Time 0.00
Received By shill Date 2005-10-14 Time 16:30 Sent To PC
Notes
2005-10-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION FOR
 POOL EQUIPMENT.
  
 2.)POOL SAFETY REQUIREMENTS ARE NOT ON
 THE PLAN, FBC424.2.17.
  
 3.)PROVIDE A SPA DETAIL.
  
 4.)PROVIDE A STEP AND HANDHOLD DETAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By shill Date 2005-06-21 Time 09:39 Rev Time 0.50
Received By shill Date 2005-06-21 Time 09:39 Sent To PC
Notes
2005-06-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A SHORING DETAIL FOR THE
 HOUSE FOUNDATION (SPA IS LESS THAN 5'
 FROM THE PORCH).

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-14 Cont ID  
Sent By btrobaug Date 2005-11-14 Time 12:25 Rev Time 0.25
Received By btrobaug Date 2005-11-14 Time 12:06 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-14 Cont ID  
Sent By btrobaug Date 2005-11-14 Time 12:05 Rev Time 0.33
Received By btrobaug Date 2005-09-29 Time 16:05 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By btrobaug Date 2005-06-14 Time 14:52 Rev Time 0.33
Received By btrobaug Date 2005-06-14 Time 14:47 Sent To P
Notes
2005-06-14 00:00:00 
 THE POOL SPECS INDICATE A GAS HEATER,
 THE SCHEMATIC INTEGRATES A HEAT PUMP.
 PLEASE CORRELATE AND RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 08:50 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 08:50 Sent To E
Notes
2005-10-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 09:21 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 09:21 Sent To E
Notes
2005-09-29 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 16:08 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 16:08 Sent To E
Notes
2005-09-23 00:00:00TO "Z"BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 11:24 Rev Time 0.00
Received By shill Date 2005-06-14 Time 11:24 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-03 Time 15:51 Rev Time 0.00
Received By shill Date 2005-06-03 Time 15:51 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-11-14 Cont ID  
Sent By kstevens Date 2005-11-14 Time 18:46 Rev Time 0.50
Received By kstevens Date 2005-11-14 Time 18:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-06 Cont ID  
Sent By jleech Date 2005-10-06 Time 07:32 Rev Time 0.50
Received By jleech Date 2005-10-06 Time 07:32 Sent To B
Notes
2005-10-06 00:00:00DENIED;
 1.PIPING DIAGRAM DOES NOT MATCH POOL
 LAYOUT. SPA PIPING MISSING, AND LION
 HEADS NOT SHOWN ON POOL DRAWING.
 2ND REQUEST FOR NOTES;
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5)FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON THE
 WATER SERVICE. (ADD TO NOTES)
 6)FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLUMBING SEC. 606.21,
 PURPLE PRIMER REQUIRED ON PVC PIPES AND
 FITTINGS. (ADD TO NOTES)
 7.FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT ARE REQUIRED. (ADD TO NOTES)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 18:05 Rev Time 0.50
Received By kstevens Date 2005-06-20 Time 18:05 Sent To B
Notes
2005-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A. FOLLOWING INFORMATION REQUIRED ON
 PLANS:
  
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES).
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES).
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES).
 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON THE
 WATER SERVICE. (ADD TO NOTES).
 5) FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SECT. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPES AND
 FITTINGS. (ADD TO NOTES).
 6) FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT ARE REQUIRED. (ADD TO NOTES).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-28 Cont ID  
Sent By mmclean Date 2005-09-28 Time 18:33 Rev Time 0.00
Received By mmclean Date 2005-09-28 Time 18:33 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 19:03 Rev Time 0.00
Received By mmclean Date 2005-06-13 Time 19:03 Sent To I
Notes
2005-06-13 00:00:00DENIED,
 1. POOL SETBACK FOR REAR MUST BE 5FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720