Plan Review Details - Permit 05051937
Plan Review Stops For Permit 05051937
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By jwitmer Date 2005-06-21 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2005-06-21 Time 09:59 Sent To  
Notes
2005-06-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051937
 ADD: 3607 S DIXIE HWY
 CONT: SJE DESIGN
 TEL: (561)305-0244
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2A)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THIS NEW WALL INDICATED ON THE PLANS
 WOULD BE BUILT NEXT TO AND EXISTING WALL
 THAT WOULD HAVE ELECTRIC OUTLETS IN IT ,
 HOW WILL THAT BE HANDLED?
  
 2B) 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 THE DOOR TO THE EXISTING RESTROOM
 SWINGS INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR FIXTURES, 11-4.22.2
 11-4.22.2(1) ALL DOORS TO ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH
 ?11-4.13.DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
 DUTY TO ACCESSIBILITY WILL BE MET, FOR
 THIS RENOVATION ALTHOUGH THE RESTROOM
 DOESN'T MEET THE ACCESSIBILITY CODE. THE
 INTENT OF THE CODE IS FOR THROUGH A
 SERIES OF RENOVATIONS THE SPACE WILL BE
 MADE TO COMPLY WITH THE ACCESSIBILITY
 CODE. THIS PORTION OF THE CODE IS
 ENVOKED WHENEVER RENOVATIONS ARE MADE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By mcarsill Date 2005-06-20 Time 11:24 Rev Time 0.00
Received By mcarsill Date 2005-06-20 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-17 Cont ID  
Sent By shill Date   Time 08:02 Rev Time 0.00
Received By shill Date 2005-05-31 Time 13:45 Sent To  
Notes
2005-06-17 00:00:00COMM BOARD 27
  
2005-05-31 00:00:00TO "MISC" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2005-06-20 00:00:001. PLEASE INDICATE OCCUPANCY TYPE.
  
 2. PLEASE INDICATE ANY FIRE SAFETY
 EQUIPMENT CONTAINED WITHIN SPACE.
  
 3. THE CROOKED LINE ON THE PLAN
 REPRESENTS WHAT.
  
 4. THE EXISTING WALL SHOWN ON THE
 PLAN SEPARATES WHAT.
  
 5. PLEASE DIPLAY A DETAIL FOR THE
 NEW PROPOSED WALL.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-2910