Plan Review Details - Permit 05051930
Plan Review Stops For Permit 05051930
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-10-12 Cont ID  
Sent By jgomez Date 2005-10-12 Time 11:29 Rev Time 1.00
Received By jgomez Date 2005-10-12 Time 11:29 Sent To P
Notes
2005-10-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- AGREEMENT WITH ANDY CHARNOUBI FROM
 THE RIF GROUP WAS TO APPLY FOR SEPARATE
 PERMIT FOR ITEMS LISTED ON ITEM #1 OF
 PROVISO DATED 9-7-05. INFORMATION WAS
 SUBMITTED AS SUBMITTAL. THIS WASN'T THE
 AGREEMENT. NEED TO APPLY FOR SEPARATE
 PERMIT FOR THOSE ITEMS.
  
 2- BBQ HOOD AND GRILL: A) BBQ HOOD:
 INFORMATION SUBMITTED DOESN'T SPECIFY
 ANYWHERE IF THE SPECIFIC SELECTED MODEL
 IS DESIGNED FOR OUTDOOR USE AS
 REQUESTED. THERE ARE SPECIFIC HOODS THAT
 ARE DESIGNED FOR OUTDOOR USE AND THOSE
 WERE THE SPECIFICATIONS REQUESTED TO
 SUBMIT. SEC. 104.2.1.2 CITY AMENDMENTNS
 TO FBC 2001.
  
 B) BBQ HOOD INFORMATION SUBMITTED
 DOESN'T MATCH MODEL SPECIFIED ON
 ARCHITECT'S PLANS. REVISE A REQUIRED.
  
 3- AS STATED ON PROVISO DATED 9-7-05
 REVISION FEES WILL APPLY TO REVISED
 PLANS. OWES $80.00
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-08 Cont ID  
Sent By jgomez Date 2005-09-07 Time 13:22 Rev Time 1.50
Received By jgomez Date 2005-09-07 Time 13:21 Sent To PC
Notes
2005-09-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- AS AGREED ON WITH G.C. SEPARATE
 PERMITS FOR SINGLE HUNG WINDOWS, FRENCH
 DOORS, 2X6 WINDOW MULLIONS, CASEMENT
 WINDOWS, SLIDING GLASS DOORS & SHUTTERS.
 2- PROVIDE COMPLETE SPECS AND LISTING
 FOR BBQ HOOD FOR EXTERIOR USE AND
 SPECIFIC GRILL TO BE INSTALLED.
 3-A) REVISE DRAWINGS TO CLARIFY IF USING
 CONCRETE OR CLAY TILE. SEE WALL SECTION
 AND ELEVATIONS. REVISION FEES APPLY.
 B) REVISE SHEET A1: COLUMNS AT LANAI ARE
 C4 NOT C2. REVISION FEES WILL APPLY.
 C) SHEET A3: SPECIFY CONNECTOR FOR
 GIRDER TRUSS RESTING ON (3)2X6 POST.
 REVISION FEES APPLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-15 Cont ID  
Sent By jgomez Date 2005-08-15 Time 14:14 Rev Time 2.00
Received By jgomez Date 2005-08-15 Time 14:14 Sent To PC
Notes
2005-08-15 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOC.
  
 2- CLARIFY IF USING STORM SHUTTERS OR
 IMPACT GLAZING. THERE IS A NOTE SAYING
 THAT SHUTTERS WILL BE DONE UNDER
 SEPARATE PERMIT. BUT, PRODUCT APPROVALS
 SUBMITTED ARE FOR NON-IMPACT AND IMPACT
 GLAZING. PROVIDE COMPLETE PRODUCT
 APPROVALS FOR IMPACT OR FOR NON-IMPACT.
  
 3- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR SLIDING GLASS DOORS
 AS SHOWN ON PLANS. PRODUCT APPROVAL
 SUBMITTED IS FOR A DIFFERENT
 CONFIGURATION OF DOORS.
  
 4- A) PROVIDE COMPLETE SPECS AND
 APPROVED LISTING FOR BBQ. INCLUDING
 MODEL SELECTED.
 B) PROVIDE SPECS AND APPROVED LISTING
 FOR HOOD TO BE USED OUTDOOR.
  
 5- CLARIFY IF USING CEMENT OR CLAY TILE.
 ELEVATIONS CALL FOR CONCRETE ROOF TILE.
 TYP. WALL SECTION IN SHEET A6 CALLS FOR
 CLAY BARREL TILE AND PRODUCT APPROVAL
 SUBMITTED IS FOR CONCRETE TILE. CLARIFY.
  
 6- PROVIDE PRODUCT APPROVAL FOR
 2"X6"X1/8" MULLION.
  
 7- PROVIDE COPY OF THE IMPACT FEES PAID
 RECEIPT.
  
 8- SHEET A1: COLUMNS AT LANAI ARE C4,
 NOT C2. REVISE AS REQUIRED.
  
 9- SHEET A3: SPECIFY CONNECTOR FOR
 GIRDER TRUSS RESTING ON (3)2X6 POST.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By jgomez Date 2005-07-07 Time 17:47 Rev Time 2.00
Received By jgomez Date 2005-07-07 Time 17:47 Sent To Z
Notes
2005-07-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- SHEET T1: UPDATE GENERAL NOTES. SEE
 COMMENTS ON PLANS.
  
 3- DESIGN PARAMETERS: WHY MINIMUM SOIL
 BEARING PRESSURE IS : NA?
  
 4- PROVIDE COMPLETE SPECS AND LISTING
 FORBBQ DESIGNED TO BE INSTALLED IN
 PORCH. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC 2001 AND SEC. 2808 FBC 2001.
  
 5- PROVIDE UL LISTING AND SPECS FOR
 FIREPLACE. SEC. 2806 FBC 2001.
  
 6- SHEET A1: FOOTING DETAIL BETWEEN GOLF
 CART AND THEATER DOESN'T MATCH DETAIL 5.
 REVISE AS REQUIRED.
  
 7- DOOR LEADING DIRECTLY INTO A SLEEPING
 ROOM IS NOT ALLOWED. PREVIOUS PLANS
 SHOWED BUILT OUT FLOOR LEVELS AND
 THEATER CONFIGURATION. THIS PLAN SHOWS A
 ROOM WITH A CLOSET. PROVIDE THEATER SET
 UP OR CONSPICUOSLY WRITE UNDER THEATER
 THAT ROOM IS NOT DESIGNED FOR SLEEPING
 PURPOSES. SEC. 411.2.8 FBC 2001.
  
 8- PROVIDE FULL BATHROOM WITH DOOR THAT
 ALLOWS 29" MIN. CLEAR OPENING AS
 REQUIRED BY SEC. 11-11 FBC 2001.
  
 9- PLANS ARE SPECIFYING LOT 20. THIS
 PLANS ARE FOR LOT 3. REVISE AS REQUIRED.
  
 10- REVISE/UPDATE ALL TRUSS ANCHOR
 SPECIFYING SAME SIZE AND NUMBER OF NAILS
 AS SHOWN ON CATALOGUE THAT WAS REVISED
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001.
 OTHERWISE, PROVIDE TESTING & ENGINEERING
 FOR NAIL SIZE AND NUMBER THAT DIFFER
 FROM THOSE ALREADY TESTED AND PUBLISHED
 BY THE MANUFACTURER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11- CONNECTOR THD210 IS A WOOD TO WOOD
 CONNECTOR. SEE CATALOGUE FOR PROPER
 MASONRY CONNECTORS AND REVISE AS REQ'D.
  
 12- CLARIFY WHY USING ONLY AN F
 CONNECTOR TO SUPPORT END OF GIRDER TRUSS
 ABOVE BEDROOM #3 ENTRY. SEE PLAN FOR
 COMMENTS. SPECIFY CALCULATED UPLIFT AT
 THIS POINT. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 13- CLEARLY SPECIFY MULLIONS AND ANCHORS
 FOR BIG FIXED WINDOWS AT LIVING ROOM
 THAT MEET THE CALCULATED DESIGN
 PRESSURES. SEE PRODUCT APPROVAL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 14- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) SLIDING GLASS DOORS. DADE COUNTY NOA
 DOESN'T MATCH INFORMATION SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
  
 B)WINDOW MULLIONS SPECIFIED. SEE
 COMMENT #13 ABOVE.
  
 C) CASEMENT WINDOWS: NEED THE FLORIDA
 PRODUCT APPROVAL. NOA ALONE IS NOT
 ACCEPTABLE.
  
 15- SOIL TEST REPORT SUBMITTED IS FOR
 LOT 20. NEED ONE FOR LOT 3.
  
 16- SURVEY SUBMITTED DOESN'T MATCH FLOOR
 PLANS. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-24 Cont ID  
Sent By btrobaug Date 2006-10-24 Time 07:56 Rev Time 0.50
Received By btrobaug Date 2006-10-24 Time 07:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 17:09 Rev Time 0.50
Received By btrobaug Date 2006-07-14 Time 17:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By btrobaug Date 2006-07-07 Time 13:31 Rev Time 0.50
Received By btrobaug Date 2006-07-07 Time 11:50 Sent To PC
Notes
2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER SHOWS #3 FEEDERS TO PANEL
 "C", THE SCHEDULE LISTS #6 ON A 100 AMP
 BREAKER. PLEASE CORRECT. NOTE PANEL "C"
 HAS A 87 AMP LOAD, 4.25 ON PANEL "A"
 SHEDULE/CALC. CORRECT CALC AND SCHEDULE.
  
 2} THE RECEPTACLES ON THE KITCHEN ISLAND
  
 MUST BE GFI PER 210.8(A)(6).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-11 Cont ID  
Sent By btrobaug Date 2005-06-11 Time 13:21 Rev Time 0.50
Received By btrobaug Date 2005-06-11 Time 13:16 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 15:29 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 15:29 Sent To E
Notes
2006-10-18 15:29:46TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-28 Cont ID  
Sent By adarroug Date 2006-06-28 Time 11:01 Rev Time 0.00
Received By adarroug Date 2006-06-28 Time 11:01 Sent To E
Notes
2006-06-28 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 15:36 Sent To B
Notes
2005-10-06 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 14:43 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 14:43 Sent To B
Notes
2005-09-01 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-02 Cont ID  
Sent By adarroug Date 2005-08-02 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-08-02 Time 09:30 Sent To B
Notes
2005-08-02 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 11:19 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 11:19 Sent To Z
Notes
2005-07-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 17:38 Rev Time 0.00
Received By shill Date 2005-06-09 Time 17:38 Sent To E
Notes
2005-06-09 00:00:00TO RES RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 12:33 Rev Time 0.00
Received By mmclean Date 2005-06-01 Time 09:39 Sent To  
Notes
2005-06-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-16 Cont ID  
Sent By hmoser Date 2005-06-16 Time 18:04 Rev Time 0.00
Received By hmoser Date 2005-06-16 Time 17:42 Sent To P
Notes
2005-06-16 00:00:00PASS PRIVISO
 COMPLETE RETURN AIR IN GUEST ROOM.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-18 Cont ID  
Sent By mperson Date 2006-12-18 Time 09:08 Rev Time 0.33
Received By mperson Date 2006-12-18 Time 09:08 Sent To PC
Notes
2006-12-18 09:09:23REVISION: AS BUILT SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By jleech Date 2005-10-12 Time 16:12 Rev Time 0.33
Received By jleech Date 2005-10-12 Time 16:12 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-18 Cont ID  
Sent By jleech Date 2005-06-18 Time 06:40 Rev Time 0.33
Received By jleech Date 2005-06-18 Time 06:40 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 16:15 Rev Time 0.00
Received By mmclean Date 2005-08-01 Time 16:15 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 12:31 Rev Time 0.00
Received By mmclean Date 2005-06-09 Time 16:02 Sent To  
Notes
2005-07-11 00:00:00DENIED,
 1. SURVEY DOES NOT MATCH PLANS.
 2. LOT IS NOT INCLUDING IN THE MINOR
 AMENDMENT FOR ZERO LOT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2005-06-09 00:00:00ZONING WILL REVIEW LAST. NEED TO HAVE
 GRACE REVIEW REGARDING THE REAR SETBACK.