Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By prafter Date 2005-07-11 Time 09:52 Rev Time 0.50
Received By prafter Date 2005-07-11 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By pkrauss Date 2005-06-07 Time 20:46 Rev Time 0.25
Received By pkrauss Date 2005-06-07 Time 20:44 Sent To  
Notes
2005-06-07 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC/M TABLE 403.3.
  
 2.INDICATE OUTSIDE AIR INTAKE, LAYOUT,
 DUCT SIZE AND MATERIAL.
  
 3.PLEASE CLARIFY LOCATION OF THE AHU.
 IS IT LOCATED IN A CLOSET SEPARATE FROM
 THE BATHROOM/STORAGE AREA?MECAHNICAL
 CLOSETS SHALL COMPLY WITH 2001 FBC/M
 603.9.
  
 4.PLEASE CLARIFY THE OFFICE 1 AND 2
 ARE OCCUPIED BY THE SAME TENANT.PLEASE
 NOTE, IF NOT TENANT IN OFFICE 2 SHALL BE
 ABLE TO TEMPERATURE CONTROL OF THEIR
 SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.