Plan Review Details - Permit 05051815
Plan Review Stops For Permit 05051815
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2005-06-18 Cont ID  
Sent By shill Date 2005-06-18 Time 11:37 Rev Time 0.25
Received By shill Date 2005-06-18 Time 11:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-01 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 11:57 Rev Time 0.50
Received By btrobaug Date 2005-08-01 Time 11:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-11 Cont ID  
Sent By btrobaug Date 2005-06-11 Time 10:04 Rev Time 0.50
Received By btrobaug Date 2005-06-11 Time 09:59 Sent To M
Notes
2005-06-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM
 INDICATING WHERE THE TRANSFER SWITCH
 INTEGRATES IN THE SERVICE.
  
 2} SHOW COMPLIANCE WITH 225.31-36.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 11:48 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:48 Sent To MEDGAS
Notes
2005-07-26 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 14:46 Sent To I
Notes
2005-07-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 18:18 Rev Time 0.00
Received By shill Date 2005-06-08 Time 18:18 Sent To E
Notes
2005-06-08 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 12:57 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 12:57 Sent To Z
Notes
2005-05-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 11:14 Rev Time 0.25
Received By jleech Date 2005-08-01 Time 11:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-07-28 Cont ID  
Sent By hmoser Date 2005-07-28 Time 18:46 Rev Time 0.00
Received By hmoser Date 2005-07-28 Time 18:46 Sent To P
Notes
2005-07-28 00:00:00PLAN DENIED
 PLEASE INDICATE TYPE OF FUEL BEING USED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By pkrauss Date 2005-06-14 Time 09:34 Rev Time 0.30
Received By pkrauss Date 2005-06-14 Time 09:34 Sent To P
Notes
2005-06-14 00:00:00DENIED:
 1.PLANS NOR APPLICATION INDICATE FUEL
 SOURCE (NATURAL GAS, PROPOANE OR DIESEL
 FUEL, ETC).INDICATE GAS PERMIT IF
 AVAILABLE.
  
 2.PLANS DO NOT INDICATE LOCATION OF
 FUEL SOURCE.
  
 3.MANUFACTURER'S SUBMITTAL DATA DOES
 NOT INDICATE CLEARANCES FROM ADJACENT
 BUILDINGS, PROPERTY LINES, FRESH AIR
 INTAKES I.E., DOORS, WINDOWS, GRILLES IN
 SOFFITS.LOCATION SHALL COMPLY WITH
 2001 FBC(M) 804.3.4 & 804.3.5.
  
 PLEASE NOTE, PROPANE GAS & TANK
 INSTALLATION SHALL COMPLY WITH NFPA 58
 FOR LOCATION OF TANKS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 11:07 Rev Time 0.25
Received By jleech Date 2005-08-01 Time 11:07 Sent To  
Notes
2005-08-01 00:00:00GAS PERMIT APP. HAS BEEN RECIEVED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-18 Cont ID  
Sent By jleech Date 2005-06-18 Time 10:10 Rev Time 0.50
Received By jleech Date 2005-06-18 Time 10:10 Sent To B
Notes
2005-06-18 00:00:00SEE GAS REVIEW UNDER PERMIT APPLICATION
 NO.05041398. PERMIT DENIED ON 5/5/05 BY
 KEN STEVENS.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By mmclean Date 2005-07-25 Time 16:30 Rev Time 0.00
Received By mmclean Date 2005-07-25 Time 16:30 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By mmclean Date 2005-06-08 Time 09:21 Rev Time 0.00
Received By mmclean Date 2005-06-08 Time 09:21 Sent To I
Notes
2005-06-08 00:00:00DENIED,
 1. NEED TO PROVIDE THE SIDE SETBACK FOR
 THE GENERATOR FROM STRUCTURE AND
 PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720