Plan Review Details - Permit 05051487
Plan Review Stops For Permit 05051487
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 08:02 Rev Time 1.00
Received By alange Date 2005-10-03 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 08:41 Rev Time 0.75
Received By alange Date 2005-09-19 Time 08:00 Sent To  
Notes
2005-09-19 00:00:00DENIED
 SAME NOTES FROM FIRST REVIEW.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING.
 BUILT-UP ROOFING, SHINGLES, AND
 HARDI-BOARD PRODUCTS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 5. MASTER BEDROOM WINDOW SHALL COMPLY
 WITH FBC 1005.4.4 FOR EMERGENCY ESCAPE
 RESCUE OPENING SIZES.SHOW ON PLANS.
  
 SECOND REVIEW NOTES NOT ADDRESSED:
  
 A.CONTRACTOR LICENSE U-19578 IS A
 CARPENTRY LICENSE AND IS NOT A QUALIFIED
 LICENSE TO DO ROOM ADDITIONS.A CHANGE
 OF CONTRACTOR IS REQUIRED TO COMPLETE
 THE WORK SHOWN ON THE PLANS SUBMITTED.
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-09 Cont ID  
Sent By alange Date 2005-08-09 Time 09:20 Rev Time 0.75
Received By alange Date 2005-08-09 Time 09:20 Sent To  
Notes
2005-08-09 00:00:00DENIED
 SAME NOTES FROM FIRST REVIEW.
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
 * NOC IS ABOUT TO EXPIRE.
  
 2.SHOW NEW AND EXISTING SQUARE FOOTAGE
 ON PLANS FOR A/C AREAS AND COVERED
 PORCHES.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING.
 BUILT-UP ROOFING, SHINGLES, AND
 HARDI-BOARD PRODUCTS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SUBMIT ENERGY CALCS FOR 600C OR
 MANUAL J CALCS FOR THE ADDITION ONLY.
  
 5. MASTER BEDROOM WINDOW SHALL COMPLY
 WITH FBC 1005.4.4 FOR EMERGENCY ESCAPE
 RESCUE OPENING SIZES.SHOW ON PLANS.
  
 NEW COMMENTS:
 A.CONTRACTOR LICENSE U-19578 IS A
 CARPENTRY LICENSE AND IS NOT A QUALIFIED
 LICENSE TO DO ROOM ADDITIONS.A CHANGE
 OF CONTRACTOR IS REQUIRED TO COMPLETE
 THE WORK SHOWN ON THE PLANS SUBMITTED.
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By alange Date 2005-06-27 Time 07:50 Rev Time 1.00
Received By alange Date 2005-06-27 Time 06:57 Sent To  
Notes
2005-06-27 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SHOW NEW AND EXISTING SQUARE FOOTAGE
 ON PLANS FOR A/C AREAS AND COVERED
 PORCHES.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING.
 BUILT-UP ROOFING, SHINGLES, AND
 HARDI-BOARD PRODUCTS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SUBMIT ENERGY CALCS FOR 600C OR
 MANUAL J CALCS FOR THE ADDITTION ONLY.
  
 5. MASTER BEDROOM WINDOW SHALL COMPLY
 WITH FBC 1005.4.4 FOR EMERGENCY ESCAPE
 RESCUE OPENING SIZES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 19:45 Rev Time 0.25
Received By dpalmer Date 2005-09-08 Time 19:45 Sent To P
Notes
2005-09-08 00:00:00NEW SHEETS,
  
 REDLINES FROM PREVIOUS REVIEW NOT
 CORRECTED, REDLINED PLANS ONCE AGAIN.
  
 210.52D,210.11C3,210.8, MUST BE 20A AND
 #12.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-11 Cont ID  
Sent By btrobaug Date 2005-06-11 Time 09:53 Rev Time 0.50
Received By btrobaug Date 2005-06-11 Time 09:47 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By spalmer Date 2005-05-20 Time 13:44 Rev Time 0.15
Received By spalmer Date 2005-05-20 Time 13:44 Sent To  
Notes
2005-05-20 00:00:00OKAY PER EDNASHA BOWERS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 14:58 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 14:58 Sent To B
Notes
2005-09-21 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 09:28 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 09:28 Sent To E
Notes
2005-09-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 16:36 Sent To Z
Notes
2005-08-29 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 11:32 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 11:32 Sent To M
Notes
2005-08-04 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 18:30 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 18:30 Sent To Z
Notes
2005-07-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 18:17 Rev Time 0.00
Received By shill Date 2005-06-08 Time 18:17 Sent To E
Notes
2005-06-08 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-27 Cont ID  
Sent By alange Date 2005-06-27 Time 07:50 Rev Time 0.00
Received By alange Date 2005-05-26 Time 08:37 Sent To  
Notes
2005-05-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-09-12 Cont ID  
Sent By tgordon Date 2005-09-12 Time 09:10 Rev Time 0.00
Received By tgordon Date 2005-09-12 Time 09:12 Sent To B
Notes
2005-09-12 00:00:00FORM 600-C SUPPLIED9-12-05 .
 NOT APPLYING FOR MECH. PERMIT AT THIS
 TIME, NO MECH. CONTRACTOR OR MECH. PLANS
 SUBMITTED.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-08-08 Cont ID  
Sent By prafter Date 2005-08-08 Time 08:05 Rev Time 0.50
Received By prafter Date 2005-08-08 Time 08:05 Sent To B
Notes
2005-08-08 00:00:00 
  
  
  
  
 MECH. PLANRESUB.JULY 28/05
  
 A/C PLAN REV. 6/24/05 PATTY KRAUSS.
  
 QUESTIONS NOT ADRESSED FROM PREVIOUS
 REV.SEE ATTACHED REV. 6/24/05
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-24 Cont ID  
Sent By pkrauss Date 2005-06-24 Time 08:19 Rev Time 0.30
Received By pkrauss Date 2005-06-24 Time 08:08 Sent To B
Notes
2005-06-24 00:00:00DENIED:
 PLEASE PROVIDE A COMPLETED FORM 600C OR
 ENERGY AND MANUAL J CALCULATIONS FOR THE
 ADDITION ONLY.2001 FBC(M)101.4.1.1 &
 CHAPTER 6 METHOD C.
  
 INDICATE IF THE A/C FOR THIS AREA WILL
 BE NEW OR EXISTING.
  
 NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By jleech Date 2005-09-12 Time 08:14 Rev Time 0.25
Received By jleech Date 2005-09-12 Time 08:14 Sent To M
Notes
2005-09-12 00:00:00NEW PLANS RE-STAMP OK
2005-09-08 00:00:00NEW SHEETS

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-14 Cont ID  
Sent By kstevens Date 2005-06-14 Time 08:39 Rev Time 0.35
Received By kstevens Date 2005-06-14 Time 08:39 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-09-02 Cont ID  
Sent By mmclean Date 2005-09-02 Time 19:46 Rev Time 0.00
Received By mmclean Date 2005-09-02 Time 19:46 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-08-03 Cont ID  
Sent By mmclean Date 2005-08-03 Time 10:40 Rev Time 0.00
Received By mmclean Date 2005-08-03 Time 10:40 Sent To I
Notes
2005-08-03 00:00:00DENIED,
 1. NEED TO PROVIDE TWO CLEAR COPY OF
 SURVEY SHOWING THE LOCATION OF THE WORK
 AND SETBACKS. (FRONT/SIDE/REAR).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By mmclean Date 2005-06-08 Time 10:57 Rev Time 0.00
Received By mmclean Date 2005-06-08 Time 10:57 Sent To I
Notes
2005-06-08 00:00:00DENIED,
 1. NEED TO PROVIDE TWO CLEAR COPY OF
 SURVEY SHOWING THE LOCATION OF THE WORK
 AND SETBACKS. (FRONT/SIDE/REAR).
 2. FRONT PORCH ADDITION CANNOT ENCROACH
 WITHIN THE 25FT FRONT SETBACK OF
 PROPERTY.
 3. FRONT SETBACK SHOWS 28FT AND NEW
 ADDITION FRONT PORCH SITS 6FT INTO THE
 SETBACK, LEAVING THE FRONT SETBACK AT
 22FT, MUST HAVE 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720