Plan Review Details - Permit 05051446
Plan Review Stops For Permit 05051446
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-24 Cont ID  
Sent By jwitmer Date 2006-02-24 Time 10:58 Rev Time 0.55
Received By jwitmer Date 2006-02-24 Time 10:57 Sent To PC
Notes
2006-02-24 00:00:002-24-06 REVISION # 4 SWING OF DOOR SUITE
  
 #104.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-22 Cont ID  
Sent By jwitmer Date 2006-02-22 Time 16:51 Rev Time 0.55
Received By jwitmer Date 2006-02-22 Time 16:51 Sent To PC
Notes
2006-02-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051446
 ADD: 2247 PALM BEACH LAKES
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 6 FROM THE PREVIOUS REVIEW,
 SUITE# 104 DOOR BY THE ELEVATOR
 DOESN'T MEET REQUIREMENTS OF:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 REQUIRES 18" OF WALL NEXT TO THE
 LATCH PULL SIDE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-23 Cont ID  
Sent By jwitmer Date 2005-12-23 Time 15:29 Rev Time 2.22
Received By jwitmer Date 2005-12-23 Time 15:29 Sent To PC
Notes
2005-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051446
 ADD: 2247 PALM BEACH LAKES
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SINCE THE SCOPE OF WORK HAS CHANGED
 UPDATE THE VALUE OF THE WORK TO BE
 COMPLETED UNDER THIS PERMIT.
  
 2) EXTERIOR AWNING IS TO BE COVERED
 UNDER A SEPERATE PERMIT.
 104.1.1 WPB ADMINISTRATIVE CODE.
  
 3) PLANS DO NOT INDICATE THE MINIMUM
 BUILDING TYPE?601.2.1
 IF BUILDING IS FIRE SPRINKLERED? IF
 SUPERVISED? TABLE 600
  
 4) SHEETS A1-A2 BOTH SHOW AN EXIT ACCESS
 CORRIDOR BUT DOESN'T PROVIDE A UL
 LISTING OR GYPSUM LISTING FOR THE WALL
 ASSEMBLY OR FIRE RESISTANCE
 RATING?704.2.4.
  
 5)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 6) SUITE# 104 DOOR BY THE ELEVATOR
 DOESN'T MEET REQUIREMENTS OF:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 REQUIRES 18" OF WALL NEXT TO THE
 LATCH PULL SIDE.
  
 7) SCOPE OF WORK REVEALS THAT WINDOWS
 ARE TO BE REPLACED:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 REPLACEMENT WINDOWS .
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-06-21 Cont ID  
Sent By jwitmer Date 2005-06-21 Time 08:33 Rev Time 1.33
Received By jwitmer Date 2005-06-21 Time 08:33 Sent To  
Notes
2005-06-21 00:00:00BUILDING PROVISOS:
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 20:27 Sent To  
Notes
2006-02-08 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE SOME NOTES FROM
 PREVIOUS REVIEW WHICH NEED TO BE
 ADDRESSED.
  
  
  
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE:? THIS IS UNCLEAR, AS LIGHTING
 LOADS ON "AM" SCHEDULE DO NOT SEEM TO
 CORRELATE WITH CALCS SHOWN ONE-1
  
 **PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE SHOWN ON LOAD CALCULATIONS
 INCLUDING ANY LARGEST MOTOR LOADS AT
 125%.
 215.3,230.42 ETC.
 PLEASE SEE ONLY EXT LTS SEEM TO BE SHOWN
 AT 125%.
  
 4)NOTE: NO, ? SEE NOTE ABOVE AS, THE
 LOADS ON "AM" SHOULD BE THE SAME AS
 SHOWN FOR MAIN BLDG SERVICE?
 PLEASE VERIFY WHY THIS IS SHOWN
 SUBSTANTIALLY LARGER.
  
 **PLEASE CORRLELATE LOADS SHOWN ON
 MSB "AM" WITH RISER
 CALCULATIONS/LOAD(S).
 215.5
  
 5)NOTE: OK
  
 ** PLEASE CALL TO GO OVER COMMENTS AS
 SHEETS FOR INTERIOR WALLS ETC MAY BE
 STAMPED IF NEEDED FOR INSPECTIONS ONCE
 FIRE REVIEW IS DONE AND PASSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATEIN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER'
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 19:31 Rev Time 0.00
Received By dpalmer Date 2005-12-20 Time 19:22 Sent To  
Notes
2005-12-20 00:00:00***UNSAT ***
  
 1)NOTE: PLEASE SEE DUE TO MAJOR INCREASE
 IN SCOPE OF WORK FROM ORIGINAL PERMIT
 APPLICATION AND PLANS SUBMITTED, PLEASE
 ADJUST VALUE FOR COMPLETE SCOPE OF WORK.
 104.6.5 FBC, ADMINISTRATIVE CODE
 AMENDMENTS.
  
 2)NOTE: PLEASE SEE MECHANICAL REVIEW
 COMMENTS SND POSSIBLE FIRE REVIEW
 COMMENTS WHICH WILL AFFECT ELECTRICAL
 PLANS.
  
 3)NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE SHOWN ON LOAD CALCULATIONS
 INCLUDING ANY LARGEST MOTOR LOADS AT
 125%.
 215.3,230.42 ETC.
 PLEASE SEE ONLY EXT LTS SEEM TO BE SHOWN
 AT 125%.
  
 4)NOTE: PLEASE CORRLELATE LOADS SHOWN ON
 MSB "AM" WITH RISER
 CALCULATIONS/LOAD(S).
 215.5
  
 5)NOTE: PLEASE VERIFY OF THE 1200 MCB IS
 BACKFED INTO PANEL. THIS APPEARS TO BE
 SHOWN ON THE PANEL SCHEDULE AS WELL AS
 BEING INDICATED ON THE TOP OF THE PANEL
 AS A MCB PANEL.??
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATEIN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER'
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-17 Cont ID  
Sent By dpalmer Date 2005-06-17 Time 09:00 Rev Time 1.50
Received By dpalmer Date 2005-06-17 Time 07:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-02-15 Cont ID  
Sent By mwennerg Date 2006-02-15 Time 16:04 Rev Time 0.00
Received By mwennerg Date 2006-02-15 Time 16:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-12-22 Cont ID  
Sent By mwennerg Date 2005-12-22 Time 10:10 Rev Time 0.00
Received By mwennerg Date 2005-12-22 Time 10:10 Sent To  
Notes
2005-12-22 00:00:00******DENIED******
  
 1) PLEASE PROVIDE FIRE RESISTANCE
 INFORMATION FOR NEW AWNINGS.
  
 2) PLANS MENTION DUCT SMOKE DETECTORS.
 DEVICES WHERE INSTALLED SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS, AND IF TIED INTO A
 FIRE ALARM SYSTEM.
  
 3) ADDITIONAL EXIT SIGNS REQUIRED IN
 CORRIDORS TO SARTISFY MINIMUM 100'
 DISTANCE REQUIREMENT.
  
 4) IF APPLICABLE, SEPARATE SHOP DRAWINGS
 AND PERMITS REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-17 Cont ID  
Sent By mwennerg Date 2005-06-17 Time 11:18 Rev Time 0.00
Received By mwennerg Date 2005-06-17 Time 10:27 Sent To  
Notes
2005-06-17 00:00:00****PASSED****
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 08:33 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 08:33 Sent To M
Notes
2006-01-27 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-12 Cont ID  
Sent By adarroug Date 2006-01-12 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 11:32 Sent To  
Notes
2006-02-06 00:00:00TO "COMM" BD#27
2006-01-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 12:51 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 12:51 Sent To  
Notes
2005-11-22 00:00:00TO "COMM" BD#61
2005-11-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-19 Cont ID  
Sent By adarroug Date 2005-07-19 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-07-19 Time 10:32 Sent To M
Notes
2005-07-19 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 14:01 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 14:01 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#21
2005-07-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-01 Cont ID  
Sent By pkrauss Date 2005-07-01 Time 10:26 Rev Time 0.00
Received By pkrauss Date 2005-05-25 Time 09:55 Sent To  
Notes
2005-06-06 00:00:00TO COMM BD#19
2005-05-25 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-02-06 Cont ID  
Sent By rregueir Date 2006-02-06 Time 17:19 Rev Time 0.00
Received By rregueir Date 2006-02-06 Time 16:55 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-30 Cont ID  
Sent By hmoser Date 2006-01-30 Time 08:03 Rev Time 0.00
Received By hmoser Date 2006-01-30 Time 08:03 Sent To  
Notes
2006-01-30 00:00:00PULLED MECHANICAL PLANS OUT FILED ONE
 CALLED CONTRACTOR TO P/U OTHER.HM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-12-03 Cont ID  
Sent By rregueir Date 2005-12-03 Time 09:09 Rev Time 0.00
Received By rregueir Date 2005-12-02 Time 19:32 Sent To  
Notes
2005-12-03 00:00:00------------------DENIED----------------
  
 1) DUCT SIZES, GRILL DESIGNATION AND CFM
 MISSING IN SUITES 104 THRU 110 AND 204
 THRU 208. PLEASE INCLUDE ALL NECESSARY
 INFORMATION ON PLAN.
  
 2) KEY NOTES 5,6,7 ON PAGES M2 AND M3
 REFER TO DETAIL 1/M7 FOR DUCT/DIFFUSER
 SIZES AND LAYOUT. THIS DETAIL CONTAINS
 NO SUCH INFORMATION.
  
 3) KEY NOTES 5,6,7 ON PAGES M4 AND M5
 REFER TO DETAIL 1/M8 FOR DUCT/DIFFUSER
 SIZES AND LAYOUT. THIS DETAIL CONTAINS
 NO SUCH INFORMATION.
  
 4) VAV T1-14 ON PAGE M2 REFERENCES KEY
 NOTE 4 (FIRE DAMPER EXCEPTION). DUCT IS
 NOT SHOWN TO RUN THE MIN. 5' PAST THE
 RATED WALL TO MEET THE CONDITIONS OF THE
 FIRE DAMPER EXCEPTION.
  
 5) PAGE M5 SUITE 209 SHOWS A 24X18 DUCT
 FEEDING VAV T2-20 AND T2-21 EXCLUSIVELY.
 THE TWO VAVS COMBINED CALL FOR A TOTAL
 OF 270 CFM. IS THIS INTENTIONAL?
  
 6) GENERAL HVAC NOTE #9 CALLS FOR DUCT
 SMOKE DETECTORS IN ALL 4 AC SYSTEMS
 BASED ON CFMS.PLEASE INDICATE ON PLAN
 THE LOCATION OF DUCT SMOKE DETECTORS,
 ENSURING SERVICE/INSPECTION ACCESS AND
 COMPLIANCE WITH MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 RONALD J REGUEIRO AT 561.805.6734 OR
 PATTY KRAUS AT 561.805.6719

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-22 Cont ID  
Sent By prafter Date 2005-07-22 Time 07:47 Rev Time 0.50
Received By prafter Date 2005-07-22 Time 07:47 Sent To B
Notes
2005-07-22 00:00:00MECH. PLAN RESUB 5/20/05
  
 ALL SIX CHECK LIST ITEMS, O/K.
  
 PAT RAFTER 561/805/6728.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By pkrauss Date 2005-07-01 Time 07:35 Rev Time 1.20
Received By pkrauss Date 2005-07-01 Time 07:35 Sent To  
Notes
2005-07-01 00:00:00DENIED:
 1.PLAN SHEET M-4, SUPPLY AND RETURN
 AIR DUCT PENETRATING TENANT SEPARATION
 BETWEEN SUITE 206 & 205, FIRE DAMPERS
 ARE NOT INDICATED ON THE PLAN.
  
 2.PROVIDE DETAIL OF THE SHAFT ENCLOSER
 INDICATED ON PLAN SHEET M-5.PLEASE
 NOTE, FIRE DAMPER REQUIRED WHERE DUCT
 PENETRATES THE SHAFT WALL 2001 FBC
 705.1.2.2.1.
  
 3.PLEASE INDICATE PROTECTION FOR DUCT
 DUCTS SERVING THE FIRST FLOOR. 2001
 FBC(M) 607.4.
  
 4.PLAN SHEET M-7 KEY NOTE #3
 REFERENCES DUCT PENETRATION DETAIL
 7/S-1.PLEASE CLARIFY LOCATION OF THE
 DETAIL?
  
 5.PROVIDE TIE DOWN & SUPPORT DETAIL
 FOR RTU CURB SHOWN ON PLAN SHEET M-8.
  
 6.PLEASE NOTE, ENGINEER IS REQUIRED TO
 HAVE IS PRINTED NAME & LICENSE NUMBER
 INDICATED ON EACH PLAN SHEET IN
 ACCORDANCE WITH FS 471.025 & FAC
 61G15-23.002.CERTIFICATE OF
 AUTHORIZATION (BUSINESS NUMBER) SHALL
 ALSO BE IDENTIFIED ON THE TITLE BLOCK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-02-23 Cont ID  
Sent By pschmitz Date 2006-02-23 Time 13:49 Rev Time 0.00
Received By pschmitz Date 2006-02-23 Time 14:00 Sent To  
Notes
2006-02-23 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CH 1, ADMINISTRATION, 2004 EDITION (
 ATFBC)FBC BUILDING 2004, CH 11
  
 PLUMBING COMMENTS NOT INCLUDED 2-16-06
  
 2-22-06 MISSING COMMENTS E-MAILED,
 BYROBERT SCHULLER.
 EXISTING REST RM'S NO CHANGES.
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-02-16 Cont ID  
Sent By pschmitz Date 2006-02-16 Time 15:22 Rev Time 0.00
Received By pschmitz Date 2006-02-16 Time 15:10 Sent To  
Notes
2006-02-16 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 "DENIED"
 "PREVIOUS COMMENTS NOT ADDRESSED"
  
 DENIED
 1.) SHT A-1,A-2
 ?104.2 DRAWINGS AND SPECIFICATIONS
 ?104.2.1 REQUIREMENTS. AS REQUIRED BY
 ?104.3.1.1 OF THE CODE, TWO OR
 MORE COPIES OF SPECIFICATIONS, AND OF
 DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK, SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT.SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR
 SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS
 AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 2.)
 SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1 APPLICATION.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 ?11-4.1.1(1)(A) ALL AREAS OF NEWLY
 DESIGNED OR NEWLY CONSTRUCTED
 BUILDINGS AND FACILITIES REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1.2 AND
 ?11-4.1.3 AND ALTERED PORTIONS OF
 EXISTING BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY
 ?11-4.1.6 SHALL COMPLY WITH THIS CODE,
 ?11-4.1 THROUGH ?11-4.35, UNLESS
 OTHERWISE PROVIDED IN THIS
 SECTION OR AS MODIFIED IN A
 SPECIAL APPLICATION SECTION.
 3.) SHT P-1
 A)PROVIDE A DWV AND WATER PIPE
 ISOMETRIC.SEC 104.2
 B) WATER HEATER DETAIL
 ?P607.3 THERMAL EXPANSION CONTROL. A
 MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH ?P607.3.1 AND ?P607.3.2.
  
 END OF COMMENTS, QUESTIONS
 561-805-6692
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-17 Cont ID  
Sent By pschmitz Date 2005-12-17 Time 11:27 Rev Time 0.00
Received By pschmitz Date 2005-12-17 Time 10:52 Sent To  
Notes
2005-12-17 00:00:000 PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1.) SHT A-1,A-2
 ?104.2 DRAWINGS AND SPECIFICATIONS
 ?104.2.1 REQUIREMENTS. AS REQUIRED BY
 ?104.3.1.1 OF THE CODE, TWO OR
 MORE COPIES OF SPECIFICATIONS, AND OF
 DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK, SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT.SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR
 SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS
 AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 2.)
 SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1 APPLICATION.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 ?11-4.1.1(1)(A) ALL AREAS OF NEWLY
 DESIGNED OR NEWLY CONSTRUCTED
 BUILDINGS AND FACILITIES REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1.2 AND
 ?11-4.1.3 AND ALTERED PORTIONS OF
 EXISTING BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY
 ?11-4.1.6 SHALL COMPLY WITH THIS CODE,
 ?11-4.1 THROUGH ?11-4.35, UNLESS
 OTHERWISE PROVIDED IN THIS
 SECTION OR AS MODIFIED IN A
 SPECIAL APPLICATION SECTION.
 3.) SHT P-1
 A)PROVIDE A DWV AND WATER PIPE
 ISOMETRIC.SEC 104.2
 B) WATER HEATER DETAIL
 ?P607.3 THERMAL EXPANSION CONTROL. A
 MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH ?P607.3.1 AND ?P607.3.2.
  
 END OF COMMENTS, QUESTIONS
 561-805-6692
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-06-24 Cont ID  
Sent By kstevens Date 2005-06-24 Time 18:15 Rev Time 0.86
Received By kstevens Date 2005-06-24 Time 18:15 Sent To  
Notes
2005-06-24 00:00:00NO PLUMBING RISERS SUBMITTED. MINOR
 CHANGES IN DWV. PER CITY CODES SUBJECT
 TO FIELD INSPECTORS APPROVAL.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-29 Cont ID  
Sent By mmclean Date 2005-06-29 Time 16:11 Rev Time 0.00
Received By mmclean Date 2005-06-29 Time 16:11 Sent To  
Notes
2005-06-29 00:00:00PARKING MUST BE DOUBLE STRIPPED.