Plan Review Stops For Permit 05051429 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-09-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-09-12 |
Time |
06:45 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2005-09-12 |
Time |
06:12 |
Sent To |
PC |
|
Notes |
2005-09-12 00:00:00 | BUILDING PROVISO: | | 1 ) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-08-29 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-08-29 |
Time |
14:05 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2005-08-29 |
Time |
14:00 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-07-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-07-27 |
Time |
17:35 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2005-07-27 |
Time |
17:34 |
Sent To |
PC |
|
Notes |
2005-07-27 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05051429 | | ADD: 7117 EAGLE TERRACE | | CONT: DANIEL ELECTRICAL | | TEL: (561)848-9495 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) FL BLD CODE 104.2.1.2 | | ADDITIONAL INFORMATION REQUIRED, | | PROVIE DOCUMENTATION OF ROOM USAGE NEXT | | TO THE GENERATOR LOCATION. IF SLEEPING | | ROOMS INDICATE COMPLIANCE WITH: | | 2001 FL BLD CODE, 1005.4: | | PROVIDE EMERGENCY EGRESS WINDOWS IN | | SLEEPING ROOMS WITH A MINIMUM NET CLEAR | | OPENING HEIGTH OF 24" AND NET CLEAR | | OPENING WIDTH OF 20" AND A NET CLEAR | | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR | | OPENINGS ARE PERMITTED TO HAVE A NET | | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH | | SHALL NOT BE MORE THAN 44 " ABOVE THE | | FINISH FLOOR. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-08-25 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-08-25 |
Time |
08:36 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2005-08-25 |
Time |
07:40 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-06-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-27 |
Time |
11:35 |
Rev Time |
0.55 |
Received By |
btrobaug |
Date |
2005-06-27 |
Time |
11:00 |
Sent To |
G |
|
Notes |
2005-06-27 00:00:00 | | | PLEASE NOTE THE PREVIOUS NOTES REQUESTED | | INFORMATION ON LOCATION OF EQUIPMENT. | | THE TRANSFER SWITCH AND DISCONNECT | | REQUIRED BY 225.36 ARE NOT SHOWN. ALSO | | THERE IS NO INDICATION OF FEEDER ROUTING | | FROM THE GENERATOR TO THE DISCONNECT AND | | THEN TRANSFER SWITCH SINCE NO TRANSFER | | SWICH WAS LOCATED ON THE SITE PLAN. | | | | REGARDING THE 100 AMP PANEL SHOWN BEING | | FED FROM THE TRANSFER SWITCH. | | PLEASE SHOW LOCATION ON A SITE/FLOOR | | PLAN. INDICATE WHICH IS NEW AND WHICH IS | | EXISTING EQUIPMENT ON THE RISER. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-06-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-06-02 |
Time |
18:21 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2005-06-02 |
Time |
18:18 |
Sent To |
M |
|
Notes |
2005-06-02 00:00:00 | | | PLEASE PROVIDE A SITE/FLOOR PLAN SHOWING | | THE PHYSICAL LOCATION OF THE SERVICE AND | | GENERATOR EQUIPMENT SO THAT DISCONNECT | | GROUPING AND COMPLIANCE WITH 225.31 & 32 | | CAN BE VERIFIED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2005-08-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-08-30 |
Time |
07:17 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-08-30 |
Time |
07:17 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-06-30 |
Time |
11:02 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-06-30 |
Time |
11:02 |
Sent To |
B |
|
Notes |
2005-06-30 00:00:00 | ACTIVE GAS PERMIT DOESNOT INCLUDE | | GENERATOR REVISED PLANS REQUIRED. | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-06-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-22 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-06-22 |
Time |
15:49 |
Sent To |
E |
|
Notes |
2005-06-22 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-05-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-31 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-31 |
Time |
08:51 |
Sent To |
E |
|
Notes |
2005-05-31 00:00:00 | TO 'E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-05-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-05-23 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-23 |
Time |
08:35 |
Sent To |
Z |
|
Notes |
2005-05-23 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2005-06-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-06-13 |
Time |
20:36 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2005-06-13 |
Time |
20:36 |
Sent To |
|
|
Notes |
2005-06-13 00:00:00 | PROVISO: | | MANUFACTURER SUBMITTAL DOES NOT INDICATE | | LOCATION OF EXHAUST FROM ADJACENT | | BUILDINGS, FRESH AIR INTAKES I.E., | | WINDOWS, DOORS, GRILLES INSOFFIT. | | LOCATION SHALL COMPLY WITH 2001 FBC(M) | | 804.3.4 & 804.3.5. | | | | PLEASE NOTE, ADDITIONAL PERMIT REQUIRED | | FOR GAS.GENERATOR WAS NOT INDICATED | | WITH THE ORIGINAL GAS PERMIT | | APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-05-27 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-05-27 |
Time |
12:34 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-05-27 |
Time |
12:34 |
Sent To |
I |
|
Notes |
|
|