Plan Review Details - Permit 05051108
Plan Review Stops For Permit 05051108
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-27 Cont ID  
Sent By lmartine Date 2007-03-27 Time 16:15 Rev Time 0.00
Received By lmartine Date 2007-03-27 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-03-14 Cont ID  
Sent By lmartine Date 2007-03-14 Time 13:05 Rev Time 0.00
Received By lmartine Date 2007-03-14 Time 13:05 Sent To  
Notes
2007-03-14 13:20:58 
 REVISION #4 COMMENTS
 ------------------------------------
  
  
  
 DRAWINGS SUBMITTED SHALL BE SIGNED AND SEALED BY
 DESIGNER OF RECORD.
  
 PROVIDE TYPICAL WALL SECTION.
  
 SHOW COMPLIANCE FOR THE EMERGENCY ESCAPE REQUIREMENT,
 SEE FBC, R310.1, FROM NEW SLEEPING ROOM UPSTAIRS.
  
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-23 Cont ID  
Sent By alange Date 2006-02-23 Time 07:51 Rev Time 0.75
Received By alange Date 2006-02-17 Time 11:14 Sent To  
Notes
2006-02-23 00:00:00HURRICANE ROOM STRUCTURAL DETAIL OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 09:55 Rev Time 1.66
Received By alange Date 2005-10-03 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-08 Cont ID  
Sent By alange Date 2005-09-08 Time 08:58 Rev Time 2.00
Received By alange Date 2005-09-08 Time 07:19 Sent To  
Notes
2005-09-08 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.ALL MIAMI-DADE PRODUCT APPROVALS
 SUBMITTED REQUIRE THE FOLLOWING STATE
 PRODUCT APPROVAL TO BE ATTACHED.
 ROOFING, GARAGE OVERHEAD DOOR AND
 WINDOWS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.ROOF SHEATHING NAILING SHALL COMPLY
 WITH FBC 2306.1 WPB AMMENDMENTS
 SHOW PERIMETER ZONES AT 4" FASTENER
 SPACING.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-17 Cont ID  
Sent By alange Date 2005-06-17 Time 14:10 Rev Time 4.00
Received By alange Date 2005-06-16 Time 15:21 Sent To  
Notes
2005-06-17 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.ALL PRODUCT APPROVALS SUBMITTED
 REQUIRE THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SUBMIT DETAILS FOR FIREPLACE.
  
 4.PRODUCT APPROVALS FOR EXTERIOR DOOR
 AN OUTSWING DOOR.PLANS SHOW DOOR AS AN
 INSWING DOOR.PLEASE REVISE.
  
 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR LINTELS WITH STATE APPROVAL.
  
 6.BUILDING IS IN FLOOD ZONE "A".
 PLEASE NOTE ON PLAN THAT THE FINISH
 FLOOR ELEVATION SHALL BE A MINIMUM OF 6"
 ABOVE THE BASE FLOOD ELEVATION OF 7FT.
  
 7.ROOF SHEATHING NAILING SHALL COMPLY
 WITH FBC 2306.1 WPB AMMENDMENTS
  
 8.SOILS REPORTS SUBMITTED NOT
 ORIGIONAL SIGNED AND SEALED.PLEASE
 SUBMIT ORIGONALS.
  
 9.BUILDING IS TO BE IN AN AREA OF
 QUESTIONABLE SOILS.
 PLEASE SUBMIT A REVISED SUBSURFACE
 EXPLORATION REPORT AS RECOMMENDED BY
 ARDAMAN & ASSOCIATES REPORT FROM
 DECEMBER 13, 04.INCLUDE
 RECOMMENDATIONS FOR FOOTINGS AND
 FOUNDATION WORK.
  
 10.ON WINDOW SCHEDULE SHOW TYPE OF
 WINDOW USED.
  
 11.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS COMPLYING WITH FBC 2309.6
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-04-14 Cont ID  
Sent By dpalmer Date 2007-04-14 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2007-04-14 Time 08:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-04-03 Cont ID  
Sent By dpalmer Date 2007-04-03 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2007-04-03 Time 11:02 Sent To PC
Notes
2007-04-03 12:35:52** UNSAT**
  
 *** PROVISO/REVISION NEEDED****
  
  
 1) NOTE: PLEASE SEE THE LOAD FOR THE AMOUNT OF RECESSED
 LIGHTING FIXTURES SHALL BE BASED ON THE FIXTURE WATTAGE
 BY THE NUMBER OF FIXTURES ON TOP OF THE 3WATTS PER SQ
 FT.
 THIS WAS TAKEN TO CODE PANELIST LAST YEAR TO CONFIRM
 THE SECTION OF 220.3B4. WHEN THE AMOUNT OF RECESSED
 LIGHTING IS FAR BEYOND WHAT WOULD BE NORMALLY
 CONSIDERED FOR THE GENERAL LIGHTING LOAD, THEN THE
 WATTAGE FOR FIXTURES ARE TO BE ADDED.
 THERE WAS NO CUT OFF FOR THE AMOUNT OF FIXTURES, AS IT
 WAS LEFT TO THE AHJ TO DETERMINE LOADS ON AN INDIVIDUAL
 BASIS WHEN REVIEWING THE AMOUNT OF FIXTURES.
 PLEASE SEE IN EITHER CASE THE LIGHTING IS NOT DE-RATED
 AT 50%. THERE IS NO LOCATION IN THE CODE WHERE LIGHTING
 LOADS PERMIT THIS DE-RATING FOR RESIDENTIAL USE.
 PLEASE SEE 220.30, 220.31.
  
 2) NOTE: PLEASE SEE 250.66, 310.15B6 FOR THE MINIMUM
 GROUNDING ELECTRODE CONDUCTOR.
  
 3) NOTE: PLEASE SEE 110.26 AS THE CU PANEL IS STILL
 BEING SHOWN BEHIND THE CONDENSING UNIT.
 PLEASE SEE THIS WAS REDLINED ON PLANS.
  
 ** PLANS WERE GIVEN A *PROVISO* UPON ISSUANCE TO HAVE
 ALL REVISIONS AND CORRECTIONS MADE BEFORE ROUGH AND
 THIS WAS NOT DONE. THE SERVICE AND SEVERAL OTHER
 CHANGES WERE MADE TO THE PLANS WITHOUT REVISIONS EVER
 BEING SUBMITTED.
 PLEASE KNOW THAT THE REVISED PLANS ARE TO BE 100%,
 SUBMITTED AND STAMPED FOR REVIEW BEFORE FINAL
 ELECTRICAL INSPECTION.
 PLANS WHICH ARE BEING STAMPED AT THIS TIME ARE ONLY FOR
 A PARTIAL FINAL OR TCO.
 PLEASE SUBMIT REVISED PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 15:25 Sent To PC
Notes
2007-03-29 20:53:37 
  
 ****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE SEE THE PLANS SUBMITTED ARE NOW MORE COMPLETE
 PLANS FOR REVIEW FOR CODE COMPLIANCE. PLEASE SEE THERE
 ARE NEW COMMENTS BASED ON THE PLANS SUBMITTED.
 THE PREVIOUS REVIEW REQUESTED PLANS TO BE COMPLETED FOR
 CODE COMPLIANCE.
  
 1) NOTE: PLEASE SEE ALL CIRCUITING HAS NOW BEEN REMOVED
 FROM PLANS. PLEASE SEE BY DOING SO SOME ITEMS DO NOT
 INDICATE HOW THEY ARE BEING CONTROLLED.
 PLEASE SEE OUTSIDE FLOODS?
 HOW ARE THESE CONTROLLED?
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PANEL SCHEDULE IS NOT SHOWING ANY
 WIRE SIZES TO BE REVIEWED FOR CODE COMPLIANCE. 240.4,
 310.16, 408.4
 FBC 106.3.5.4.
  
 3) NOTE: PLEASE CLARIFY THE SMOKE DEVICES AS SOME WHICH
 ARE BEING SHOWN AS SD ARE NOTED AS SMOKE DETECTORS AND
 SOME WITH THE S SYMBOLS ARE ALSO NOTED AS SMOKE
 DETECTORS?
 PLEASE SEE NFPA-72 DEFINITIONS FOR TYPES OF DEVICES. IF
 SMOKE ALARMS, INDICATE AS SA.
 PLEASE SEE THE PANEL SCHEDULE SHOWS THE 120VA HARDWIRED
 DEVICES AS SMOKE DETECTORS, WHICH IS NOT POSSIBLE.
 PLEASE SEE NOTE ON PANEL SCHEDULE WHICH ALSO MENTIONS
 SMOKE DETECTORS??
 IF THERE ARE MULTIPLE TYPES OF DEVICES INSTALLED,
 PLEASE CLARIFY AND ALSO INDICATE IF TIED INTO A FA OR
 SECURITY SYSTEM W/ SOUNDING DEVICES. IF SD IS USED,
 THEN SOUNDING DEVICES ARE REQUIRED TO ALERT AN OCCUPANT
 IN THE EVENT OF ALARM STATUS.
 NFPA-72 2002 11.5.1.1.1, 11.8.3
  
 4) NOTE: PLEASE CORRELATE THE RISER WITH THE PANELS.
 PLEASE SEE PANEL *A* IS BEING SHOWN AS A 400A RATED
 PANEL WITH A 350AMP MAIN WHEN THE PANEL ON RISER IS
 SHOWN AS 200AMPS??
 PLEASE KNOW THAT DEPENDING ON WHICH IS ACTUALLY
 INSTALLED; THE RISER MAY NEED TO BE COMPLETELY REVISED
 TO INCREASE SERVICE, CONDUCTORS GROUNDING ETC. 215.5,
 310.16, 240.4 ETC.
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE 310.15B6, 250.66 AS THE SERVICE IS
 BEING SHOWN AS 400AMPS, OR MORE DEPENDING ON NOTE #4
 ABOVE. MINIMUM SIZE GEC IS 1/0.
  
 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS, OR SMOKE
 DETECTORS IN BEDROOMS ON 2ND FLOOR. BED-RM #4, AND
 OFFICE WHICH IS CONSIDERED AN ADAPTABLE SLEEPING ROOM.
 NFPA-72 11.5.1.1.1
  
 7) NOTE: PLEASE SEE THE VALUE FOR THE LOW VOLTAGE
 PERMIT AS PREVIOUSLY NOTED AHS NOT BEEN INCREASED BY
 THE CONTRACTOR. PLEASE KNOW THAT A VALUE WILL BE
 ASSESSED BY THIS OFFICE USING THE MARSHALL'S AND SWIFT
 GUIDE WHICH IS ADOPTED INTO THE FBC PER 108.3
  
 8) NOTE: PLEASE SEE 220.3B4 AS THE RECESSED LIGHTING AS
 REDLINED ON NOTES ON PREVIOUS PLANS NEEDS TO BE SHOWN
 IN LOAD CALCULATIONS.
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTERSPACES ARE TO BE SHOWN AS GFI OR GFI
 PROTECTED.
  
 ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME
 INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF
 SUBMITTED PLANS COULD BE DONE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-03-08 Cont ID  
Sent By dpalmer Date 2007-03-08 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2007-03-08 Time 14:25 Sent To PC
Notes
2007-03-08 15:45:33** UNSAT **
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED ARE NOT
 COMPLETE AT THIS TIME FOR COMPLETE REVIEW OF CODE
 COMPLIANCE.
 PLEASE KNOW THAT THERE MAY BE COMMENTS ONCE PLANS ARE
 COMPLETE.
  
 2) NOTE: PLEASE SEE *PROVISO* WHICH WAS GIVEN IN
 SEPTEMBER OF 05 WHICH REQUIRED THOSE ITEMS TO BE
 REVISED *BEFORE ROUGH*. THIS WAS NOT DONE YET ROUGH
 ELECTRICAL INSPECTION WAS CALLED IN WITH NOTES ATTACHED
 TO PLANS.
 INSPECTOR INFORMED THIS OFFICE THAT THE NOTES WHICH
 WERE ATTACHED TO PLANS WERE TORN OFF.
 PLEASE COMPLETE THE FOLLOWING.
  
 PLEASE COMPLETE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH REVISED PANEL SCHEDULES TO BE REVISED AND
 SUBMITTED. PLEASE SEE MANY ITEMS ON PLANS DO NOT
 CONTAIN CIRCUITING AND REVIEW FOR CODE COMPLIANCE CAN
 NOT BE DONE AT THIS TIME.
 PLEASE COMPLETE AND SUBMIT LOAD CALCULATIONS PER NEC.
 PLEASE CORRELATE LOADS ON PANEL SCHEDULES AND COMPLETE
 AS REQUIRED PER CODE AND PREVIOUS *PROVISO *NOTES.
 PLEASE SUBMIT THE COMPLETE ELECTRICAL RISER DIAGRAM TO
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE BE SURE TO SEE THE 2002 NEC.
 210.52,210.11, 220, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.4 ETC.
  
 3) NOTE: PLEASE SEE THE DEVICES WHICH ARE SHOWN AS
 SMOKE DETECTORS SHOULD BE SHOWN AS SMOKE ALARMS IF THEY
 ARE 120V WITH DETECTION AND SOUNDING IN THE SINGLE
 UNIT.
 PLEASE SEE NFPA-72 DEFINITIONS FOR THE DIFFERENCES FROM
 SMOKE DETECTORS AND SMOKE ALARMS.
  
 4) NOTE: PLEASE SEE THERE ARE NOW NUMEROUS LOW VOLTAGE
 ITEMS ON PLANS WHICH THE LOW VOLTAGE PERMIT WAS UNDER
 VALUED BASED ON PLANS.
 PLEASE HAVE THE CONTRACTOR INCREASE VALUE FOR ALL LV
 WORK AS SHOWN WHICH SHALL INCLUDE ALL LABOR AND
 MATERIALS EVEN IF OWNER SUPPLIED.
 PLEASE KNOW A VALUE MAY BE ACCESSED BY THIS OFFICE IF
 AN APPROPRIATE VALUE IS NOT APPLIED.**
 FBC 108.3
  
 ** PLEASE KNOW A HOLD IS NOW BEING PLACED ON THE
 ELECTRICAL AND BUILDING PERMIT ON INSPECTIONS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-02-15 Cont ID  
Sent By dpalmer Date 2006-02-15 Time 15:53 Rev Time 0.00
Received By dpalmer Date 2006-02-15 Time 15:44 Sent To B
Notes
2006-02-15 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE SEE "PROVISO" NOTES FROM
 9/29/05 WHICH HAVE NOT BEEN ADDRESSED OR
 SUBMITTED.
 PLEASE SEE THE PERMIT WAS ISSUED ON THE
 CONDITION THESE ITMES BE ADDRESSED, CODE
 COMPLIANT AND RETURNED FOR REVIEW.
 PLEASE SEE NOTES BELOEW.
  
 2)NOTE: PLEASE CORRELATE ALL PANELS,
 LOADS ETC.
 PLEASE SUBMIT LOADS CALCUALTIONS WHICH
 MEET THE NEC 220
 PLEASE CORRELATE LOADS ON PANELS ETC.
 PLEASE RE-FIGURE AS REQUESTED ON
 PREVIOUS REVIEW.
 215.5
  
 3)NOTE: PLEASE SEE MANY ITEMS FOR
 PREVIOUS "PROVISO" CAN BE REVIEWED FOR
 CORRECTED ITEMS AS THE FIRST FLR PLANS
 WERE NOT SUBMITTED.?
 215.5
  
 4)NOTE: PLEASE SEE RISER HAS NOW BEEN
 REVISED TO REMOVED GROUNDING ELECTODE
 ATTACHMENT TO FOOTER STEEL, HOWEVER THIS
 ATTACHMENT FOR NEW CONSTRUCTION IS
 REQUIRED TO BE INSTALLED PER 250.50,
 250.52A
 THIS SHALL NOT BE DELETED FROM PLANS AND
 RISER.
  
 5)NOTE: PLEASE SEE A NEW DETAIL WAS
 SUBMITTED FOR A "HURRICANE ROOM" HOWEVER
 PLANS WERE NOT REVISED TO SHOW THIS
 ROOM, LTS, RECEPTS ETC. 210.52,210.70
 ETC.
 PLEASE ALSO SEE BLDG COMMENTS AS THE
 8 1/2X 11 IS MISSING THE TITLE BLOCK FOR
 ARCHITECT AND OTHER POSSIBLE INFORMATION
 NEEDED FOR BLDG REVIEW.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 AND OTHER INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-29 Cont ID  
Sent By dpalmer Date 2005-09-29 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2005-09-29 Time 13:20 Sent To M
Notes
2005-09-29 00:00:00********** PROVISO/ REVISION **********
  
 PLEASE SEE ITEMS BELOW ALONG WITH ANY
 OTHER REVISIONS MUST BE SUBMITTED FOR
 REVIEW AND STAMPING BEFORE ANY ROUGH
 ELECTRICAL INSPECTION.
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE SMOKE DETECTORS ARE
 REQUIRED ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING LEADING TO THE FLOOR ABOVE IN
 THE IMEDIATE VICINITY OF STAIRS.
 PLEASE SEE MISSING SD AT REAR FOYER
 LOWER LEVEL.
 PLEASE SEE SD AT FRONT FOYER REQUIRED ON
 WALL NO MORE THAN 10' ABOVE FF.
  
 2)NOTE: PLEASE SEE MIN CONTROL AND
 EGRESS LIGHT FIXTURE(S) REQUIRED AT REAR
 FOYER ENTRY/ EXIT.
 PLEASE ALSO SEE MEANS OF EGRESS FROM
 LAUNDRY RM AND BEDRM #3.3-WAY/4-WAY
 SWITCHES REQUIRED.
 PLEASE SEE SEE A "GAS FIXURE" MAY BE
 INSTALLED ALSO, HOWEVER AN ELECTRICAL SW
 AND FIXTURE IS REQUIRED.
 PLEASE SEE FRONT PORCH IS OK, DUE TO
 ELECTRICAL RECESSED LTS ALONG W/GAS FIX.
 210.70, LS 101 7.8
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 4)NOTE: PLEASE SEE "DEN" RECEPTS (A-32)
 CIRCUITED TO SMALL APPL CIRCUIT.
 BRKFST AREA, DINING AREA MAY NOT FEED
 OTHER ARES.
 PLEASE ADJUST.
  
 5)NOTE: PLEASE CORRELATE ALL LOADS ON
 PANELS AND LOAD CALCUALTIONS.
 PLEASE GO THROUGH LOAD CALCULATIONS AND
 RE-FIGURE TO MEET NEC 220.
 PANEL "A" SHOWS 30KVA FOR PANEL "B",
 HOWEVER PANEL "B" SHOWS 40KVA.
 SEE PANEL "C" ETC.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2005-08-31 Time 12:23 Sent To  
Notes
2005-08-31 00:00:00*********UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 CHANGES IN PLANS.
  
 1)NOTE; 210.8A6,INDICATE GFI'S ALONG
 KITCHEN COUNTERSPACES, REDLINED ONE.
 SEE PLANS.
  
 2)NOTE: PLEASE SEE NFPA-72, 8-1.4.2,
 WHICH REQUIRES SD'S TO BE MIN OF 3' FROM
 BATH DRS.
 PLEASE SEE REDLINED PLANS FOR THESE.
 PLEASE SEE "GREAT RMM" APPEARS TO SHOW
 TWO SD'S ??
 THIS IS OK, BUT NOT REQUIRED.(FYI).
  
 3)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS CORRELATE WITH RISER
 DIAGRAM SUBMITTED.
 PLEASE SEE PLANS DO NOT SHOW LOCATION OF
 METER/SERVICE.
 PLEASE SEE TRANSFER SWITCH IS STILL
 SHOWN ON PLANS, HOWEVER THIS HAS NOW
 BEEN REMOVED FROM RISER?
  
 4)NOTE:PLEASE SEE CIRCUITING FOR MIN
 DINING RM, ETC RECEPTS WERE REVISED,
 HOWEVER, PLEASE SEE CIRCUIT A-32 WHICH
 SHARES BRKFAST AREA AND DEN AREA.
 PLEASE SEE 210.52B1, OTHER OUTLETS MAY
 NOT BE ON THESE CIRCUITS.
 PLEASE SEE REDLINED RECEPTS ON PLANS IN
 DEN.
  
 5)NOTE: : PLEASE SEE REDLINED PLANS FOR
 SOME RECEPTS MISSING FOR 2' OF WALL
 SPACE AND WITH 6' OF DOORWAY. .
 210.52.2ND FLR.
  
 6)NOTE:PLEASE CORRELATE LOAD
 CALCUALTIONS NOW SUBMITTED. PLEASE SEE
 THE LOADS SEEM TO HAVE BEEN ROUNDED DOWN
 FOR EACH AND SERVICE. PLEASE SEE LOADS
 MAY BE ROUNDED UP , BUT CAN BE ROUNDED
 DOWN.
 PLEASE SEE REDLINED PLANS.
 PLEASE SEE POOL PANEL INDICATES 3.4KW
 AND PANEL "B" SHOWS 4.2?
 PLEASE SEE PANEL "A" SHOWS KW RATING FOR
 PANEL "B" AS 15KW, HOWEVER PANEL "B"
 INDICATES LOAD AT 39.9 WHICH DOES NOT
 SEEM TO CORRELATE WITH LOAD CALCS OR
 PANEL "A"?
 PLEASE SEE 220.31.
  
 7)NOTE: PLEASE SEE FS 553.80(2)(B), THIS
 IS ONLY A NOTICE.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS. (ZONING ETC)
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SEE ALL OTHER COMMENTS FOR
 GENERATOR WILL NOT BE INCLUDED.
 PLEASE BE SURE TO SEE COMMENTS DUE TO
 PLANNING FOR LOCATION OF FUTURE
 EQUIPMNET. MAINS AND DISCONNECTING MEANS
 SHALL BE GROUPED.
 230.72, 225.34, 225.31
 PLEASE CALL IF THERE ARE ANY QUESTIONS,
 ON THIS.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CAONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By dpalmer Date 2005-06-07 Time 10:58 Rev Time 1.50
Received By dpalmer Date 2005-06-07 Time 10:58 Sent To M
Notes
2005-06-07 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS "APPROACH AND DRIVEWAY FOR NEW
 TWO STORY HOUSE" PLEASE ADJUST PERMIT
 APPLICATION FOR NEW TWO STORY HOUSE.
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE SEE AREA(S) TO BE INCLUDED AS
 KITCHEN COUNTERSPACE AREA.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
 8-1.4.2
  
 4)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED FOR A/C DISC'S. 110.26
  
 5)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS. IF GENERATOR IS TO
 BE INCLUDED UNDER ELECTRICAL PERMIT FOR
 MAIN HOUSE. SITE PLAN, SURVEY ETC MUST
 SHOW LOCATION OF GEN. ALSO.
 PLEASE ALSO SEE OTHER COMMENTS FOR GEN
 TO FOLLOW.
  
 6)NOTE: PLEASE PROVIDE ROMM DESIGNATION
 ON PLANS.
 215.5
  
 7)NOTE: PLEASE SEE CIRCUITING OF DINING
 RM, BREAKFAST AREAS AND THE LIKE PER
 210.52-B-1.
  
 8)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE 210.12 2002NEC.
  
 9)NOTE: PLEASE SEE ROOM ABOVE GARAGE.
 PLEASE SEE RECEPTS WHICH APPEAR TO BE
 FLOOR RECEPTS?? OR ARE THESE
 MIS-LOCATED.? 210.52
 PLEASE ALSO SEE OTHER MISSING RECEPTS
 MISSING FOR 2' OF WALL SPACE.
  
 10)NOTE: PLEASE SEE CIRCUITING FOR BATH
 GFI RECEPTS IN MASTER BATH.
 PLEASE SEE 210.11C3, 210.52D
 PLEASE SEE THERE SHALL BE NO OTHER
 RECEPTS/OUTLETS EXCEPT FOR THOSE IN
 BATHRM.
  
 11)NOTE: PLEASE SEE PLANS INDICATE "SPA"
 RECEPT FOR MASTER BATH.
 PLEASE SEE PANEL SCHEDULE DOES NOT
 INDICATE THIS. PLEASE ALSO ADJUST LOAD
 CALCULATIONS TO INCLUDE LOAD AND PLEASE
 SHOW AS GFI /GFI PROTECTED .
 215.5,220.31,680.71
  
 12)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR EACH PANEL.
 PLEASE CORRELATE LOADS ON PANEL
 SCHEDULES AND SERVICE RISER LOAD CALCS.
 PLEASE CORRELATE LOAD(S) FOR SUB
 PANEL(S). PLEASE SEE PANEL "A" SHOWS THE
 SAME LOAD AS SUB PANEL "B" , YET LOADS
 IMPOSED ON EACH PANEL(BY PANEL SCHEDULE)
 ARE COMPLETELY DIFFERENT.
 220,215.5 ETC.
 PLEASE ALSO INCLUDE SIZE OF METERCAN TO
 BE PROVIDED.
  
 13)NOTE: PLEASE SEE SUB PANEL FOR POOL
 IS MISSING FROM RISER, PANEL SCHEDULES
 ETC.215.5
  
 14)NOTE: PLEASE CORRELATE DESCRIPTION
 FOR PANEL "B". PLEASE SEE PANEL SHOWN AS
 42 CIR, HOWEVER PANEL MENTIONS 30??
 215.5
  
 15)NOTE: PLEASE SEE 250.50 WHICH
 REQUIRES THE "FOOTER STEEL" TO BE PART
 OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SEE RISER MENTIONS STRUCTUAL
 STEEL. IF THE CONSTRUCTION OF THE HOUSE
 ALSO INCLUDES "STRUCTUAL STEEL" THEN IT
 WOULD ALSO BE INCLUDED AS PART IF THE
 GES. 250.50
  
 PLEASE SEE THE FOLLOWING COMMENTS FOR
 GEN/ATS ETC.
 "IF" GENERATOR IS TO BE INCLUDED AS PART
 OF THESE PLANS AND UNDER THE ELECTRICAL
 PERMIT FOR THE HOUSE, THEN ALL OF THE
 FOLLOWING INFORMATION MUST BE INCLUDED
 WITH THIS PERMIT APPLICATION PACKAGE.
  
  
 16)NOTE: PLEASE SUBMIT COMLPETE SITE
 PLAN SHOWING GEN LOCATIONS ALONG WITH
 ANY OTHER EQUIPMENT WHICH MAY NEED TO BE
 INCLUDED. THIS MUST ALSO BE INCLUDED ON
 SURVEY SHOWING ALL DIMENIONS.
 FUEL STORAGE TANK? ETC.
 PLEASE ALSO SUBMIT ELEVATIONS FOR
 EQUIPMENT WHICH MUST MUST BE ABOVE BASE
 FLOOD ELEVATION.
 700.9 AND FEMA REGULATIONS OF UTILITY
 EQUIPMENT.
  
 17)NOTE: PLEASE INDICATE THE PRIME MOVER
 FOR GEN.
 215.5,700.12B1-2 ETC
  
 18)NOTE: PLEASE SEE STRUCTURAL DETAIL9S0
 MUST BE SUBMITTED FOR BLDG REVIEW FOR
 ATTACHMENT OF GEN TO SLAB/ FBC 140MPH
 WIND LOAD.
  
 19)NOTE: PLEASE NOTE/KEEP IN MIND MIN
 CLEARENCE FROM WINDOW/DOOR AND ATTIC
 OPENINGS. A MIN OF 10" IS REQUIRED FOR
 EXHAUST. SEE MECH CODE FOR MIN
 REQUIREMENTS. THIS IS NOT AN ELECTRICAL
 CODE.
  
 20)NOTE: PLEASE SUBMIT COMPLETE
 MANUFACTTURE CUT/SPEC SHEETS FOR
 GENERATOR, AND ATS.
 PLEASE BE SURE ALL MEET 702.3-702.6.
 225.31-225.36
  
 21)NOTE: PLEASE SEE MEANS OF DISC MUST
 MEET 225.31-225.36.
 NO DISC IS SHOWN ON LINE SIDE OF ATS.
 NO INFORMATION FOR ATS IS PROVIDED.
 SIZE?
 PLEASE SEE THE MEANS OF DISC IS REQUIRED
 TO BE LOCATED ADJACENT TO OR BACK TO
 BACK WITH TRANSFER SWITCH.
 215.5
  
 22)NOTE: PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLEASE SEE PLANS MENTIOSN
 AN ATS (AUTOMATIC TRANSFER SWITCH) YET
 RISER MENTIONS A MANUAL TRANSFER
 SWITCH(MTS).
 PLEASE SEE 702.5, IF SYSTEM IS GOING TO
 BE AN "AUTOMATIC" SYSTEM, THEN GEN. IS
 REQUIRED TO BE SIZED FOR SERVICE/LOAD
 CALCULATIONS AS SHOWN.
 MEANS OF LOAD SHEEDING (IF) PROVIDED
 WOULD NEED TO BE SHOWN IN DETAIL.
 215.5
  
 23)NOTE: PLEASE INCLUDE CONDUCTORS FROM
 TRANSFER SWITCH TO MCB PANEL.
 PLEASE SEE 250.24, 250.6 IF FIRST MEANS
 OF DISC IS PROVIDED.
  
 24)NOTE: PLEASE BE SURE TO NOTE WHEATHER
 OR NOT GEN IS TO BE SEPARATELY DERIVED
 OR NOT..
  
 PLEASE SEE MANY OF THE ABOVE LOCATIONS
 HAVE BEEN REDLIND ON ONE SET OF PLANS
 FOR COMMENTS ABOVE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT "ONE" SET OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 16:21 Sent To E
Notes
2007-04-12 16:21:46TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:31 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:31 Sent To E
Notes
2007-03-30 17:31:52TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-03-26 Cont ID  
Sent By mmiller Date 2007-03-26 Time 18:31 Rev Time 0.00
Received By mmiller Date 2007-03-26 Time 18:31 Sent To  
Notes
2007-03-26 18:31:30SENT TO LUIS MATINEZ'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-03-26 Cont ID  
Sent By mmiller Date 2007-03-26 Time 18:25 Rev Time 0.00
Received By mmiller Date 2007-03-26 Time 18:25 Sent To  
Notes
2007-03-26 18:25:30SENT TO DEWEY PALMER'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-03-26 Cont ID  
Sent By spalmer Date 2007-03-26 Time 18:21 Rev Time 0.00
Received By spalmer Date 2007-03-26 Time 18:21 Sent To Z
Notes
2007-03-26 18:21:46TO JOHN ROACH

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 14:53 Sent To Z
Notes
2007-03-13 14:53:39TO "Z" BOX--DRIVEWAY REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 14:20 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 14:20 Sent To E
Notes
2007-03-06 14:21:53TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 14:49 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 14:49 Sent To B
Notes
2007-02-02 14:49:51TO "LMARTINEZ" DESK/2 REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 17:27 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 17:27 Sent To E
Notes
2006-02-13 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-28 Cont ID  
Sent By mmclean Date 2005-09-29 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 09:22 Sent To E
Notes
2005-09-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 10:28 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 10:28 Sent To Z
Notes
2005-09-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 11:21 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 11:21 Sent To E
Notes
2005-08-29 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 13:52 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 13:52 Sent To Z
Notes
2005-08-15 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-17 Cont ID  
Sent By alange Date 2005-06-17 Time 14:10 Rev Time 0.00
Received By alange Date 2005-06-06 Time 13:36 Sent To  
Notes
2005-06-06 00:00:00TO SFD RACK (E)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 14:59 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 14:59 Sent To B
Notes
2005-06-01 00:00:00TO "MISC" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 14:23 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 14:22 Sent To ENG
Notes
2005-05-24 00:00:00TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 16:02 Sent To Z
Notes
2005-05-16 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-30 Cont ID  
Sent By tgordon Date 2005-09-30 Time 08:10 Rev Time 0.30
Received By tgordon Date 2005-09-30 Time 08:10 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-07 Cont ID  
Sent By tgordon Date 2005-09-07 Time 08:23 Rev Time 0.45
Received By tgordon Date 2005-09-07 Time 08:23 Sent To B
Notes
2005-09-07 00:00:00*** DENIED ***
 1) PLEASE SHOW WHICH SUB-SECTION OF
 SECTION 703 FBC/M 2001 YOU ARE USING
 TO OBTAIN COMBUSTION AIR FOR THE
 LAUNDRY ROOM.
 2) SUPPLY AIR DUCTS (MAIN TRUNK LINES &
 BRANCH LINES) ARE NOT PROPERLY SIZED
 FOR ADEQUATE AIR DISRIBUTION.
 3) RETURN AIR DUCTS TO AHU'S ARE NOT
 PROPERLY SIZED PER 2001 FBC/M 601.4.
 4) RETURN AIR GRILLS TO AHU'S ARE NOT
 SIZED (18"X18" WOULD BE TO SMALL).
 5) SUPPLY AIR DUCTS CAN NOT GO TO
 CLOSETS IN GARAGE (HAZARDOUS FUMES
 MAY ENTER DUCTS WHEN UNIT IS NOT
 RUNNING).
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By pkrauss Date 2005-06-15 Time 09:14 Rev Time 0.40
Received By pkrauss Date 2005-06-15 Time 07:29 Sent To P
Notes
2005-06-15 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW;
 1.PLAN SHEET P2.1 INDICATES A GAS FIRE
 PLACE.PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL DATA.PROVIDE COMBUSTION AIR
 CALUCALTIONS AND MAKE-UP AIR (IF
 REQUIRED).
  
 2.PLAN SHEET P2.2 INDICATES A GAS
 DRYER.PLEASE PROVIDE CALCUALTIONS FOR
 COMBUSTION AIR AND AIR MAKE UP PER
 CHAPER 7 OF THE 2001 FBC(M).
  
 3.PLANS DO NOT INDICATE ACCESS OR
 HANGING DETAIL FOR THE AHU'S 1 & 2.
 SHOW COMPLAINCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 610.1.ABC.3.5.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.NOTE ON PLAN SHEET M2.1
 INDICATES THE REQUIREMENT FOR THE PAN
 BUT ONLY MENTIONS CONDENSATE LINE.
 SECONDARY DRAIN LINE SHALL TERMINATE AT
 A CONSPICUOUS POINT.
  
 5.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE
 PER 2001 FBC 1503.4.4.
  
 6.INDICATE LINE SIZE FOR THE
 CONDESATE, AND REFRIGERANT LINES.
  
 7.CONDENSING UNITS BE SUPPORTED BY A
 LEVEL CONCRETE SLAB A MINIMUM OF 3 1/2
 THICKEXTENDING A MINIMUM OF 2" ABOVE
 THE ADJOINING GRADE.
  
 8.PLANS DO NOT INDICATE TIE DOWN OR
 ANCHORING FOR THE CONDENSING UNIT.
 PLEASE REFERENCE 2001 FBC(M)301.13.1.
  
 9.PROVIDE GRILLE SIZES.ALSO MISSING
 RETURN AIR DUCT & JUMPER SIZES.PLEASE
 NOTE,SQUARE INCHES OF THE RETURN AIR
 JUMPERS ARE TO BE A MINIMUM OF 1 1/2
 TIMES GREATER THAN THE SUPPLY AIR INTO
 THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-31 Cont ID  
Sent By jleech Date 2005-08-31 Time 14:28 Rev Time 0.50
Received By jleech Date 2005-08-31 Time 14:28 Sent To M
Notes
2005-08-31 00:00:00PROVISO;
 PLUMBING ONLY SEPARATE PERMIT AND PLANS
 REQUIRED FOR GAS.
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By kstevens Date 2005-06-15 Time 17:20 Rev Time 1.20
Received By kstevens Date 2005-06-15 Time 17:20 Sent To B
Notes
2005-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHT P2.2 THE SANITARY RISER DIAGRAM
 DOES NOT MEET CODE REQUIREMENTS. CORRECT
 THE FOLLOWING.
 A. VENT REQUIRED AT LAV FIRST FLOOR
 POWDER ROOM . SECTION 901.2.1
 B. CLEANOUT IS REQUIRED AT THE BASE OF
 THE STACK TO THE SECOND FLOOR. SECTION
 708.3.4.
 C. SIZE ALL PIPE SECTIONS PER TABLE
 710.1(1).
 D. VENTS ARE REQUIRED FOR BOTH KITCHEN
 SINKS. SECTION 901.2.1.
 E. VENTS REQUIRED FOR LAV NEAR THE
 GARAGE AND THE SINK IN THE GARAGE.
 SECTION 901.2.1.
 F. GARAGE SINK SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT OF THE POWDER
 ROOM FIXTURES. SECTION 909.1. SINK SHALL
 DISCHARGE DOWNSTREAM OF FIXTURES.
 G. VENT REQUIRED FOR THE SECOND FLOOR
 DOUBLE LAVS. SECTION 104.2.1.
 H. W/C AND TUB ARE NOT VENTED AS PIPED
 FOR BATHROOM WITH THE DOUBLE LAVS, AND
 THE WASH MACHINE SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT OF THAT
 BATHROOM. SECTIONS 901.2.1. & 909.1.
 I. VENTS ARE REQUIRED FOR THE TUB AND
 SINK NEAR AND AT THE GREAT ROOM. SECTION
 901.2.1.
 J. THE GREAT ROOM SINK SHALL NOT DRAIN
 THRU THE HORIZONTAL WET VENT OF THE
 BATHROOM FIXTURES. THIS SINK SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES. SECTION 909.1
 K. A VENT, A STANDPIPE AND A CLEANOUT
 ARE REQUIRED FOR THE WASH MACHINE. THE
 CLEANOUT SHALL BE LOCATED 4' ABOVE THE
 FLOOR. SECTIONS 708.10, 901.2.1 AND
 1002.1.
 L. VENTS ARE REQUIRED FOR BOTH LAVS IN
 THE MASTER BATHROOM. SECTION 901.2.1.
 M. FITTINGS CONNECTING THE ISLAND SINK
 IN THE KITCHEN AND THE TUB IN THE MASTER
 BATHROOM DO NOT GUIDE THE WASTE IN THE
 DIRECTION OF FLOW AS REQUIRED IN SECTION
 706.3.
 2. SEE RED LINE CORRECTIONS ON ONE SET
 OF PLANS AS AN EXAMPLE TO AID IN
 CORRECTING THE CODE VIOLATIONS.
 3. GAS INDICATED ON PLANS. SEPARATE
 PLANS AND PERMIT REQUIRED FOR GAS. SEE
 ATTACHED SHEET FOR GAS PERMIT
 APPLICATION REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2007-03-27 Cont ID  
Sent By jroach Date 2007-03-27 Time 09:06 Rev Time 0.00
Received By jroach Date 2007-03-27 Time 09:06 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-03-16 Cont ID  
Sent By jroach Date 2007-03-16 Time 15:24 Rev Time 0.00
Received By jroach Date 2007-03-16 Time 15:24 Sent To  
Notes
2007-03-16 15:25:50***FAILED***
  
 1) SURVEY SHALL BE PROVIDED INDICATING THE LOCATION OF
 THE RESIDENCE AND THE LOCATION AND DIMENSION OF THE
 REVISED DRIVEWAY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2005-09-29 Cont ID  
Sent By mmclean Date 2005-09-27 Time 17:52 Rev Time 0.00
Received By mmclean Date 2005-09-27 Time 17:52 Sent To I
Notes
2005-09-27 00:00:00PROVISO
 1.REF. ON 2ND FLOOR GREAT ROOM MUST BE
 AN U/C REF.
  
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK.
 NOTE: SURVEY SHOWS A 6FT U.E. IN REAR OF
 PROPERTY, NOTHING CAN BE
 BUILT/CONSTRCUTED IN U.E.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-08-23 Cont ID  
Sent By mmclean Date 2005-08-23 Time 08:59 Rev Time 0.00
Received By mmclean Date 2005-08-23 Time 08:59 Sent To I
Notes
2005-08-23 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION OF
 DRIVEWAY & WALKWAY (LENGTH & WIDTH).
 **MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK***.
 2. THE PROPOSED PORCH IS ENCROACHING 1FT
 INTO THE 25FT FRONT SETBACK. PLANS SHOWS
 6FT INTO THE 30FT FRONT SETBACK.
 **MUST HAVE 25FT IN FRONT SETBACK***.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By mmclean Date 2005-05-20 Time 11:15 Rev Time 0.00
Received By mmclean Date 2005-05-20 Time 11:15 Sent To I
Notes
2005-05-20 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF THE
 SURVEY WITH SITEPLANS
 2. SITEPLAN NEED TO PROVIDE THE
 DIMENSION OF THE LOT SHOWING THE
 COMPLETE VIEW OF THE PROPERTY.
 3. MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK/SPA. CANNOT BUILD ANYTHING IN
 THE 12FT EASEMENT IN REAR OF PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720