Plan Review Details - Permit 05050974
Plan Review Stops For Permit 05050974
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-06-27 Cont ID  
Sent By jleech Date 2005-06-27 Time 14:50 Rev Time 0.50
Received By jleech Date 2005-06-27 Time 14:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-05-28 Cont ID  
Sent By kstevens Date 2005-05-28 Time 16:27 Rev Time 0.45
Received By kstevens Date 2005-05-28 Time 16:27 Sent To  
Notes
2005-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. -
 THE RISER REVISION SUBMITTED IN NOT
 CLEAR AS TO HOW THE PIPING IS TO BE RUN
 AND AT WHAT TOTAL DEVELOPED LENGHT.
 SUBMIT AN ISOMETRIC SHOWING THE COMPLETE
 SYSTEM AND CLOUD THE NEW PIPING. SHOW
 ALL PIPE LENGTHS FOR ALL CUT SECTIONS AS
 STATED. - MAKE SURE PRINTED NAME AND
 SIGNATURE OF PERSON WHO DESIGNS SYSTEM
 IS ON THE PLANS. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 13:36 Rev Time 0.00
Received By shill Date 2005-06-09 Time 13:36 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 10:01 Sent To G
Notes
2005-05-16 00:00:00TO "G" BOX