Plan Review Details - Permit 05050464
Plan Review Stops For Permit 05050464
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-26 Cont ID  
Sent By mjacobs Date 2005-07-26 Time 08:10 Rev Time 1.50
Received By mjacobs Date 2005-07-26 Time 06:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By mjacobs Date 2005-05-23 Time 14:33 Rev Time 0.00
Received By mjacobs Date 2005-05-23 Time 11:59 Sent To  
Notes
2005-05-23 00:00:00BUILDING PLAN REVIEW
 PERMIT:05050464
 ADD:2000 PALM BCH LKS BLVD
 CONT:S.O. ENTERPRISES,INC.
 TEL: (772)221-8354
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST
 ACTION:DENIED
  
 1) EACH SHEET SHALL BE CLEARLY
 SEALED,DATED,SIGNED AND HAVE THE PERSON
 RESPONSIBLE LICENSE NUMBER ON EACH
 SHEET.SEE F.A.CODE SEC.61G15-23.002 ALSO
 471.025
  
 2) ON SHEET A-1, THE DOOR SCHEDULE
 MENTIONED B3 AND C2 BUT IN THE DATAIL
 AREA THEY ARE NOT SHOWN. PLEASE CLARIFY.
  
 3) SHOW DETAILS OF HOW THE TOP AND
 BOTTOM TRACK PLATES WILL BE ATTATCHED TO
 STRUCTURE.
  
 4) THE NEW WALLS ARE LABLED AS (1A)
 HOWEVER THERE IS NO DETAIL FOR A TYPE
 (1A) WALL. PLEASE MAKE CLEAR.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 07:08 Rev Time 0.30
Received By dpalmer Date 2005-08-18 Time 07:08 Sent To  
Notes
2005-08-18 00:00:00ELEC OK, PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-07 Cont ID  
Sent By dpalmer Date 2005-07-07 Time 07:54 Rev Time 0.50
Received By dpalmer Date 2005-07-07 Time 07:54 Sent To  
Notes
2005-07-07 00:00:00******** UNSAT *********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 AND SOME CHANGES IN PLANS HAVE COMMENTS.
  
 1)NOTE: PLEASE SEE NOTE#1 FROM PREVIOUS
 REVIEWED REQUESTED THE ENGINEER
 RESPONSIBLE FOR DESIGN TO SIGN AND SEAL
 PLANS. THIS WAS DONE, HOWEVER ENGINEER'S
 TITLE BLOCK WAS REMOVED??
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.023 FOR REQUIRED TITLEBLOCK AND
 INFORMAITON REQUIRED ON SAID TITLE
 BLOCK.
  
 2)NOTE: PLEASE SEE RISER DIGRAM HAS NOW
 BEEN REVISED, PLEASE SEE PANEL "LB" IS
 STILL SHOWN AS MLO. PLEASE SEE RISER
 MENTIONS 175A BRKR. PLEASE SEE PANEL
 "LA" INDICATES BEING A 225A MCB? PLEASE
 CORRELATE.
 PLEASE SEE PANEL "LB" DOES NOT INDICATE
 ANY OCP FEEDING "LA"? IS THIS A FEED
 THRU LUGS PANEL?
 408.16,240.21 ETC.
  
 3)NOTE: PLEASE SEE PANEL 4H STILL
 INDICATES 200A OCP FEEDING 45KVA
 TRANSFORMER? ON #6 AWG.
 PLEASE SEE MAX OCP IN 450.3(125%).
 PLEASE ALSO SEE 240.4,310.16 FOR SIZING
 OF CONDUCTORS.
  
 4)NOTE: PLEASE SEE 210.8B3 FOR
 KITCHEN/BRK RM RECEPTS WHICH REQUIRES
 ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETSFOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By dpalmer Date 2005-05-20 Time 07:42 Rev Time 0.75
Received By dpalmer Date 2005-05-20 Time 07:34 Sent To  
Notes
2005-05-20 00:00:00********UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS ARE CONTAINING
 A TITLE BLOCK OF SORTS WHICH REFERENCE A
 PE FOR PLANS, HOWEVER THE PE SHOWN HAS
 NOT SIGNEDAND SEALED PLANS.??
 PLEASE SEE IF PE IS RESPONSIBLE FOR
 DESIGNAND ON PLANS , THEN THAT PE MUST
 SIGN,DATE AND SEALED PLANS. FS471.025
  
 PLEASE SEE SEAL FOR ARCH (IF ARCH SEALS
 PLANS) IS CLEAR AND VISABLE WIH
 INFORMATION REQUIRED ON SEAL FOR P, M
 AND E SHEETS.
 FS 481.221 FAC 61G1-16.003
  
 2)NOTE: PLEASE CLARIFY MEANS OF DISC AND
 OCP FROM BUS RISER?
 PLEASE SEE 4H IS SHOWN AS MLO? THERE
 SHALL BE A MAIN AND OCP ON THE LINE SIDE
 4H.
 PLEASE SEE PANELS ON THE SECONDARY SIDE
 OF THE TRANSFORMER ARE BOTH SHOWN AS
 MLO.
 PLEASE SEE THESE SHALL BOTH HAVE MCB'S
 INSTALLED.
 215.5,408.16,240.21 ETC.
  
 3)NOTE: PLEASE SEE 200A OCP SHOWN FOR
 MAIN SIDE OF 45 KVA TRANSFORMER DOES NOT
 MEET 450.3. A MAX OCP OF 125% IS ONLY
 PERMITTED.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AN
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-07-29 Cont ID  
Sent By mwennerg Date 2005-07-29 Time 13:54 Rev Time 0.00
Received By mwennerg Date 2005-07-29 Time 13:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-26 Cont ID  
Sent By mwennerg Date 2005-05-26 Time 09:16 Rev Time 0.00
Received By mwennerg Date 2005-05-26 Time 09:16 Sent To  
Notes
2005-05-26 00:00:001) PLEASE REFER TO COMMENTS FROM OTHER
 REVIEWERS IN REGARDS TO FS AND FAC
 REQUIREMENTS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODELS.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 10:26 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 10:26 Sent To P
Notes
2005-12-06 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 17:14 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 17:14 Sent To P
Notes
2005-11-14 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 11:47 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 11:47 Sent To P
Notes
2005-09-20 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 15:46 Sent To  
Notes
2005-08-17 00:00:00TO "COMM" BD#1
2005-08-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 11:47 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 11:32 Sent To  
Notes
2005-07-05 00:00:00TO "COMM" BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 12:32 Rev Time 0.00
Received By pkrauss Date 2005-05-10 Time 11:06 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#5
2005-05-13 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By pkrauss Date 2005-07-25 Time 15:06 Rev Time 0.35
Received By pkrauss Date 2005-07-25 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 11:58 Rev Time 0.35
Received By pkrauss Date 2005-06-23 Time 11:48 Sent To  
Notes
2005-06-23 00:00:00DENIED:
 SEAL OF THE ARCHITECT IS NOT LEGIBLE.
 THE ENIGNEER INDICATED ON THE MECHANICAL
 PLAN IS W. BRUCE MILLER, BUT HE DID NOT
 SIGN, SEAL OR DATE PLANS AS REQUIRED PER
 FS471.025 & FAC 61G15-23.003.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE QUESTIONS, PLEASE CONTACT
 PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-12-07 Cont ID  
Sent By kstevens Date 2005-12-07 Time 11:37 Rev Time 0.50
Received By kstevens Date 2005-12-07 Time 11:36 Sent To  
Notes
2005-12-07 00:00:00REVISION OK - WATER AND SANT. RISER
 DIAGRAMS

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-11-19 Cont ID  
Sent By jleech Date 2005-11-19 Time 13:12 Rev Time 1.00
Received By jleech Date 2005-11-19 Time 13:12 Sent To  
Notes
2005-11-19 00:00:00DENIED;
 1. BREAK SINK NOT SHOWN ON SANITARY
 RISER DIAGRAM.
 2.WATER RISER PIPING IS NOT SIZED, SHOCK
 ARRESTORS FOR BREAK SINK ARE MISSING,
 WATER SEVICE IS PIPED WRONG AT HEATER
 AND SHUTOFF VALVE IS NOT SHOWN.
 3.WATER RISER DIAGRAM SHOWS HOT AND COLD
 WATER TO BREAK SINK, AND ALSO HAS A NOTE
 AT THE SINK CALLING FORINSTA HOT
 PLEASE CORRECT.
 4.OLD RISER DIAGRAM SHOWED NOTE SAID
 "TIE INTO EXISTINGBUILDING SANITARY AT
 RESTROOMS ABOVE 6TH FLOOR CEILING",
 REVISED PLAN READS,"ABOVE 5TH FLOOR
 CEILING. SUITE IS ON THE 7TH FLOOR. THE
 EXISTING 4" SANITARY PIPE AT BATHROOMS
 SHOULD NOT BE CAPPED OFF, THAT STACK
 BECOMES A VENT ON THE TOP FLOOR AND GOES
 OUT THE ROOF.
 ONE SET OF DRAWINGS MARKED IN RED.
 PLUMBING PLAN REVIED BY;
 JOHN LEECH
 805-6695
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-10-03 Cont ID  
Sent By jleech Date 2005-10-03 Time 09:59 Rev Time 1.00
Received By jleech Date 2005-10-03 Time 09:59 Sent To  
Notes
2005-10-03 00:00:00REVISION DENIED;
 ANY CHANGES TO THE PLANS MUST BE
 APPROVED BY DESIGN PROFESSIONAL WHO DREW
 THE PLANS. ALL CHANGES SUBMITED SHALL BE
 SUBMITED ON ARCHITECT LETER HEAD,
 CLOUDED, SEAL AND SIGNED. SEE CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC
 CHAPTER 1, SEC. 104.2 AND 104.2.2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-02 Cont ID  
Sent By jleech Date 2005-09-02 Time 07:42 Rev Time 1.00
Received By jleech Date 2005-09-02 Time 07:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-04 Cont ID  
Sent By jleech Date 2005-08-04 Time 12:45 Rev Time 1.00
Received By jleech Date 2005-08-04 Time 12:45 Sent To  
Notes
2005-08-04 00:00:00DENIED;
 1.WATER RISER DIAGRAM; SHOCK ARRESTORS
 REQUIRED AT BREAK SINK. PLEASE SIZE HOT
 AND COLD MAINS.
 2.PAGE A-1 BREAK SINK SHALL BE OPEN
 FRONT PER FBC CHAPTER 11 SEC. 11.4.24.5.
 3.SEE ELECTRICAL PLAN REVIEW NOTE # 1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-18 Cont ID  
Sent By pschmitz Date 2005-06-18 Time 12:00 Rev Time 0.00
Received By pschmitz Date 2005-06-18 Time 11:59 Sent To M
Notes
2005-06-18 00:00:00PLUMBING PLAN REVIEW FBC 2001
 PASS PENDING ELECTRICAL PLAN REVIEW,
 NOTE # 1
 END OF COMMENTS
 QUESTIONS PAUL SCHMITZ 561-805-6692

Review Stop PC PERMIT CLERK
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***