Plan Review Details - Permit 05050459
Plan Review Stops For Permit 05050459
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By btrobaug Date 2005-06-10 Time 09:11 Rev Time 0.75
Received By lsmith Date 2005-06-01 Time 11:02 Sent To Z
Notes
2005-06-01 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. DRAWINGS MUST COMPLY TO THE SEC.
 104.2 FBC2001.
 2. THE POLES MUST MEET THE DESIGN FOR
 WIND FOR PBC OF 140 MPH 3SEC. GUST.
 3. ?104.2.1 REQUIREMENTS. AS REQUIRED BY
 ?104.3.1.1 OF THE CODE, TWO OR MORE
 COPIES OF SPECIFICATIONS, AND OF
 DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK, SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT.SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL
 THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-10 Cont ID  
Sent By btrobaug Date 2005-05-27 Time 13:44 Rev Time 0.50
Received By btrobaug Date 2005-05-19 Time 09:50 Sent To B
Notes
2005-06-10 00:00:00 
 APPLICATION NOT SIGNED.
  
 PLEASE SUBMIT CIRCUIT NUMBERS AND PANEL
 DESIGNATION FOR ORIGIN OF CIRCUITS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 11:23 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 11:22 Sent To  
Notes
2005-05-11 00:00:00TO "E" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-22 Cont ID  
Sent By lsmith Date 2005-07-01 Time 11:00 Rev Time 0.00
Received By lsmith Date 2005-07-01 Time 11:01 Sent To I
Notes
2005-07-22 00:00:00APPROVED BY MICHELLE MCLEAN

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By mmclean Date 2005-06-07 Time 15:30 Rev Time 0.00
Received By mmclean Date 2005-06-07 Time 15:30 Sent To E
Notes
2005-06-07 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF SURVEY
 SHOWING THE LOCATION OF THE LIGHT POLES.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720