Plan Review Details - Permit 05050354
Plan Review Stops For Permit 05050354
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-01 Cont ID  
Sent By jwitmer Date 2006-05-01 Time 07:50 Rev Time 1.11
Received By jwitmer Date 2006-05-01 Time 07:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-06 Cont ID  
Sent By jwitmer Date 2006-04-06 Time 14:43 Rev Time 2.20
Received By jwitmer Date 2006-04-06 Time 14:43 Sent To  
Notes
2006-04-06 00:00:00PLANS APPREAR TO BE CODE COMPLIANT, WILL
 REQUIRE REVIEW BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-25 Cont ID  
Sent By jwitmer Date 2006-01-25 Time 17:49 Rev Time 0.55
Received By jwitmer Date 2006-01-25 Time 17:49 Sent To PC
Notes
2006-01-25 00:00:00PERMIT: 05050354
 ADD: 3700 BROADWAYY
 CONT: WEST
 TEL: (561)718-8656
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
  
  
 1) COMMENT#2 FROM THE PREVIOUS REVIEW
 2) COMMENT 6B FROM THE PREVIOUS REVIEW,
 6B)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6C)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 ******* E) ROOF ASSEMBLIES MISSING FL
 COVER SHEET, NOA GOOD FOR STEEL DECK
 PLANS INDICATE T&G DECK.****************
  
 2) COMMENTE# 3 FROM THE PREVIOUS REVIEW
 ALTHOUGH THE ENERGY CALCULATIONS ARE
 SEALED THEY INDICATE THE WORK BEING
 COMPLETED IS IN RIVIERA.CORRECT
  
 3) COMMENT# 5 FROM THE PREVIOUS REVIEW,
 PLEASE PROVIDE FIRE SPRINKLER PLANS
 OF EXISTING SYSTEM AND IF ANY NEW HEADS
 ARE BEING INSTALLED. PLANS WILL BE
 REQUIRED SINCE IT APPEARS THAT YOU ARE
 TAKING THE EXCEPTION TO 1005.4.2
 EXECEPTION (1)
 1. EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL NOT BE REQUIRED IN BUILDINGS
 PROTECTED THROUGHOUT BY AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM.
 THE SHEET FP-1 DOES NOT INDICATE ANY
 EXISTING OR NEW FIRE SPRINKLERS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)805-6731

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-27 Cont ID  
Sent By jwitmer Date 2005-08-27 Time 10:13 Rev Time 2.22
Received By jwitmer Date 2005-08-27 Time 08:16 Sent To  
Notes
2005-08-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050354
 ADD: 3700 BROADWAYY
 CONT: WEST
 TEL: (561)718-8656
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
  
 1) COMMENT# 3) FROM THE PREVIOUS REVIEW,
 PROVIDE ADDITIONAL INFORMATION,
 PROVIDE MIN. BUILDING TYPE OF DESIGN,
 (TABLE 500/ 600) IF ANY AREA INCREASES
 WERE TAKEN? PLANS INDICATE THIS TO BE A
 TYPE IV/ 1 HR PROTECTED/ FULLY
 SPRINKLERED BUILDING.
 1A) FOR THIS BUILDING TO BE CONSIDERED
 TYPE IV CONSTRUCTION, LOOK AT TABLE 600,
 NON BEARING WALLS, NO COMBUSTIBLE IN
 WALLS SHEET A-4 STILL INDICATES THE USE
 OF PLYWOOD AS A SUBSHEATHING. THIS
 BUILDING CAN BE CONSIDERED A TYPE VI
 UNPROTECTED/ FULLY SPRINKLERED BUILDING,
 THIS WILL ALLOW THE WOOD INFILL IN THE
 EXTERIOR WALLS AND PROVIDE AN ALLOWABLE
 24,000 SQ FT BUILDING.
 1B) CLASSIFICATION OF THIS BUILDING AS A
 TYPE IV 1HR PROTECTED BUILDING ALSO
 CREATES A PROBLEM WITH THE ROOF
 SHEATHING, TABLE 600 REQUIRES THEROOF TO
 BE 1 HR RATED, FOOTNOTE "E" DOES ALLOW
 ONE STORY BUILDINGS TO USE FIRE
 RETARDANT WOOD SHEATHING. TYPE VI
 UNPROTECTED/ FULLY SPRINKLERED HAS NO
 SUCH LIMITATIONS WITH THE ROOF.
  
 2) COMMENT 6B FROM THE PREVIOUS REVIEW,
 6B)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6C)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 ******* E) ROOF ASSEMBLIES MISSING FL
 COVER SHEET, NOA GOOD FOR STEEL DECK
 PLANS INDICATE T&G DECK.****************
  
 3) ALTHOUGH THE ENERGY CALCULATIONS ARE
 SEALED THEY INDICATE THE WORK BEING
 COMPLETED IS IN RIVIERA.
  
 4) COMENT# 8 FROM THE PREVIOUS
 REVIEWDEALS WITH INFILL FOR THE EXTERIOR
 WALLS, DEPENDING ON THE RESULTS OF
 QUESTION # 1 THIS MAY OR MAY NOT BE A
 ISSUE. SHEET A-4, FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 4A) EXTERIOR WALL DETAILS INDICATE THE
 USE OF WOOD INFILL, DEPENDING ON THE
 CLASSIFICATION OF THIS BUILDING THIS MAY
 BE A ISSUE. THE ITEMS IN CONCERN ARE THE
 DESIGNER OF RECORD DOES NOT INDICATE HOW
 THE 2X8 PT PLATE WILL BE ANCHORED INTO
 THE EXISTING STRUCTURE?
  
 5) PLEASE PROVIDE FIRE SPRINKLER PLANS
 OF EXISTING SYSTEM AND IF ANY NEW HEADS
 ARE BEING INSTALLED. PLANS WILL BE
 REQUIRED SINCE IT APPEARS THAT YOU ARE
 TAKING THE EXCEPTION TO 1005.4.2
 EXECEPTION (1)
 1. EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL NOT BE REQUIRED IN BUILDINGS
 PROTECTED THROUGHOUT BY AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM.
  
 6) NEW COMMENT THE ORIENTATION OF
 BROADWAY IS ON THE WRONG SIDE OF THE
 BUILDING, CORRECTING WILL HELP IN TABLE
 600 ISSUES, SEE A-1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 09:04 Rev Time 2.22
Received By jwitmer Date 2005-06-26 Time 09:04 Sent To Z
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050354
 ADD: 3700 BROADWAYY
 CONT: WEST
 TEL: (561)718-8656
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)PROVIDE OCCUPANCY CLASSIFICATION? IT
 APPEARS TO BE A SCHOOL, AGE OF STUDENTS,
 IS THIS A VOCATIONAL SCHOOL? SEE 306.1.1
 & 306.1.4.
  
 3) PROVIDE ADDITIONAL INFORMATION,
 PROVIDE MIN. BUILDING TYPE OF DESIGN,
 (TABLE 500/ 600) IF ANY AREA INCREASES
 WERE TAKEN?
  
 4) THE VALUE OF THE BUILDING FROM THE
 PROPERTY APPRAISER INDICATES THE VALUE
 AT $138,050.00 REQUIRING; 3401.7.2.6
 WHEN REPAIRS AND ALTERATIONS AMOUNTING
 TO MORE THAN 50 PERCENT OF THE VALUE OF
 THE EXISTING BUILDING ARE MADE DURING
 ANY 12 MONTH PERIOD, THE BUILDING OR
 STRUCTURE SHALL BE MADE TO CONFORM TO
 THE REQUIREMENTS FOR A NEW BUILDING OR
 STRUCTURE OR BE ENTIRELY DEMOLISHED.
 EXCEPTIONS:
 1. PROVIDED THERE IS NO CHANGE IN
 OCCUPANCY, FOUNDATIONS, SLABS, TIE
 BEAMS, TIE COLUMNS, REINFORCED MASONRY
 AND MASONRY WALLS ERECTED IN
 COMPLIANCE WITH THE CODE UNDER WHICH THE
 BUILDING WAS CONSTRUCTED.
 2. THOSE PROPERTY IMPROVEMENTS
 INVOLUNTARILY ALTERED BY RIGHT OF
 EMINENT DOMAIN NEED ONLY TO MEET THE
 REQUIREMENTS OF THE CODE IN FORCE AT THE
 TIME OF ORIGINAL CONSTRUCTION.
  
 5A) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5B) 1606.1.5 PROVIDE THE MEAN ROOF
 HEIGHT. PROVIDE ROOF ZONE INFORMATION,
 POS/ NEG PRESSURES FOR ZONES 1,2 & 3.
  
 6) 3401.7.2.4 THE REPLACEMENT OF GARAGE
 DOORS, EXTERIOR DOORS,SKYLIGHTS,
 OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY
 WITH CHAPTER 16 OF THIS CODE.
 6A) 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 6B)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6C)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- NO FL COVERSHEET, FOR SMALL
 MISSLE ONLY
 B) MULLIONS- NO FL COVERSHEET
 C) EXTERIOR DOOR- ARCH FL COVERSHEET
 DOES NOT MATCH NOA.
 D) STORM SHUTTERS REQUIRED FOR SMALL
 MISSLE IMPACT TESTING NO SUBMITTALS
 E) ROOF ASSEMBLIES MISSING FL COVER
 SHEET, NOA GOOD FOR STEEL DECK PLANS
 INDICATE T&G DECK.
  
 F)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 7) ENERGY CALS SIGNED BY A ACHITECT OR
 ENGINEER ARE REQUIRED TO BE SEALED AND
 ORIGINAL SIGNATURE, NOT COPIES.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) SHEET A-4, FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 8A) EXTERIOR WALL DETAILS INDICATE THE
 USE OF WOOD INFILL, DEPENDING ON THE
 CLASSIFICATION OF THIS BUILDING THIS MAY
 BE A ISSUE. THE ITEMS IN CONCERN ARE THE
  
 DESIGNER OF RECORD DOES NOT INDICATE HOW
 THE 2X8 PT PLATE WILL BE ANCHORED INTO
 THE EXISTING STRUCTURE?
  
 8B) THERE IS NO INFORMATIONFOR
 STRAPPING REQUIREMENTS FOR EITHER THE
 TOP OR BOTTOM PLATE.
  
 8C) 13-406.1.ABCD1.2 EXTERIOR JOINTS IN
 THE ENVELOPE ENERGY CODE ARE "ALL"
 PRESCRIPTIVE REQUIREMENTS TO BE MET. NO
 INSULATION IN THE WOOD FRAME WALL.
 SEE METHOD A.
  
 9) SHEET A-4/ WINDOW SECTION AND A-3
 BOTH INDICATE WINDOW INFILLS, SHEET A-3
 INDICATES INFILL FROM COLUMN TO COLUMN
 BUT NO FILLED CELL ADJACENT TO WINDOWS
 NOR BUCK DETAILS.
  
 10) 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 IN. (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 IN. (1525 MM) IN LENGTH
 MINIMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH ?11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
  
 11) SHOWERS:11-4.21.3 SEAT. A SEAT SHALL
 BE PROVIDED IN SHOWER STALLS 36 INCHES
 BY 36 INCHES (915 MM BY 915 MM) AND
 SHALL BE AS SHOWN IN FIGURE 11-36.
 THE SEAT SHALL BE MOUNTED 17 INCHES TO
 19 INCHES (430 MM TO 485 MM) FROM THE
 BATHROOM FLOOR AND SHALL EXTEND THE FULL
 DEPTH OF THE STALL.IN A 36 INCH BY 36
 INCH (915 MM BY 915 MM) SHOWER STALL,
 THE SEAT SHALL BE ON THE WALL OPPOSITE
 THE CONTROLS.WHERE A FIXED SEAT IS
 PROVIDED IN A 30 INCH BY 60 INCH MINIMUM
 (760 MM BY 1525 MM) SHOWER STALL, IT
 SHALL BE A FOLDING TYPE AND SHALL BE
 MOUNTED ON THE WALL ADJACENT TO THE
 CONTROLS AS SHOWN IN FIGURE 11-57.THE
 STRUCTURAL STRENGTH OF SEATS AND THEIR
 ATTACHMENTS SHALL COMPLY WITH 11-4.26.3.
  
 12) WEST ENTRY DOOR TO COMPLY WITH:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 13) IF THE OCCUPANCY CLASSIFICATION IS
 EDUCATIONAL AND NOT BUSSINESS EGRESS
 WINDOW REQUIREMENTS:
 1005.4.2 EVERY ROOM OR SPACE GREATER
 THAN 250 FT^2 (23.2 M^2) IN
 EDUCATIONAL OCCUPANCIES USED FOR
 CLASSROOM OR OTHER EDUCATIONAL PURPOSES
 OR NORMALLY SUBJECT TO STUDENT
 OCCUPANCY AND EVERY ROOM OR SPACE
 NORMALLY
 SUBJECT TO CLIENT OCCUPANCY, OTHER
 THAN BATHROOMS, IN GROUP D OCCUPANCIES
 SHALL HAVE NOT LESS THAN ONE OUTSIDE
 WINDOW FOR EMERGENCY RESCUE THAT
 COMPLIES WITH THE FOLLOWING:
  
 1. SUCH WINDOWS SHALL BE OPENABLE
 FROM THE INSIDE WITHOUT THE USE OF
 TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20 IN. (51
 CM) IN WIDTH, 24 IN. (61 CM) IN
 HEIGHT, AND 5.7 FT^2 (0.53 M^2) IN
 AREA.
  
 2. THE BOTTOM OF THE OPENING SHALL BE
 NOT MORE THAN 44 IN.(112 CM)
 ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE OF BEING
 OPERATED FROM NOT MORE THAN 54 IN.
 (137 CM) ABOVE THE FINISHED FLOOR.
  
 3. THE CLEAR OPENING SHALL ALLOW A
 RECTANGULAR SOLID, WITH A WIDTH AND
 HEIGHT THAT PROVIDES NOT LESS THAN
 THE REQUIRED 5.7 FT2 (0.53 M^2)
 OPENING AND A DEPTH NOT LESS THAN
 20 IN.(51 CM), TO PASS FULLY
 THROUGH THE OPENING.
  
 4. SUCH WINDOWS SHALL BE ACCESSIBLE BY
 THE FIRE DEPARTMENT AND SHALL OPEN
 INTO AN AREA HAVING ACCESS TO A
 PUBLIC WAY.
  
 EXCEPTIONS:
  
 1. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL NOT BE REQUIRED IN
 BUILDINGS PROTECTED THROUGHOUT
 BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM.
 2. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL NOT BE REQUIRED IF THE
 ROOM OR SPACE HAS A DOOR LEADING
 DIRECTLY TO THE OUTSIDE OF THE
 BUILDING.
 3. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL NOT BE REQUIRED FOR
 ROOMS LOCATED HIGHER THAN THREE
 STORIES ABOVE GRADE.
  
 14) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-31 Cont ID  
Sent By dpalmer Date 2005-12-31 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2005-12-31 Time 12:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 18:30 Rev Time 0.10
Received By dpalmer Date 2005-09-03 Time 18:30 Sent To  
Notes
2005-09-03 00:00:00NO NEW ELECTRICAL SHEETS, STAMPED AND
 REDLINED NOTES ON 5/19/05

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-05-19 Cont ID  
Sent By dpalmer Date 2005-05-19 Time 12:00 Rev Time 1.00
Received By dpalmer Date 2005-05-19 Time 12:00 Sent To I
Notes
2005-05-19 00:00:00***REDLINED NOTES***
  
 1)NOTE: GFI PROTECTION FOR KITCHEN
 RECEPTS UNDER 2002 NEC 210.8B3
  
 2)NOTE: HIGH-LEG MARKING PER NEC.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-01-20 Cont ID  
Sent By mamini Date 2006-01-20 Time 09:50 Rev Time 0.50
Received By mamini Date 2006-01-20 Time 09:50 Sent To  
Notes
2006-01-20 00:00:00PASSED WITH PROVISOS:
  
 1. SUBMIT CIVIL PLANS TO THE PUBLIC
 UTILITIES AND ENGINEERING PRIOR TO ANY
 CONNECTION WORK TO THE CITY SERVICES,
 ATT; MANNY GONZALEZ, 494-1085.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2005-08-15 Cont ID  
Sent By mamini Date 2005-08-15 Time 13:20 Rev Time 0.50
Received By mamini Date 2005-08-15 Time 13:20 Sent To  
Notes
2005-08-15 00:00:00FAILED:
  
 1. NOTE TO THE ARCHITECT AND THE
 MICHANICAL ENGINEER, THERE IS NO CIVIL
 PLAN WITH THIS SUBMITTAL.
 2. SHEET P-1 REFERS TO CIVIL DRAWINGS
 FOR CONTINUATION OF WATER & SEWER.
 3. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT BACK OF THE SIDEWALK, IF
 NOT ALRADY INSTALLED.
 4. SHEET P-1 REFERS TO GREASE TRAP, PER
 ARCHITECT THERE NO KITCHEN PROPOSED FOR
 THIS FACILITY.
 5. EXISTING BACKFLOW,METER, AND THE
 PROPOSED DOUBLE DETECTOR CHECK ASSEMBLY
 AND ITS CONNECTION AS REQUIRED BY THE
 FIRE DEPARTMENT MUST BE SHOWN.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By mamini Date 2005-06-27 Time 14:09 Rev Time 0.50
Received By mamini Date 2005-06-27 Time 14:09 Sent To  
Notes
2005-06-27 00:00:00FAILED:
  
 1. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT BACK OF THE SIDEWALK, IF
 NOT ALRADY INSTALLED.
 2. IF KITCHEN FACILITY IS BUILT THEN
 GREASE/WATER SEPARATOR WILL NEED TO BE
 INSTALLED TO MEET THE CITY' WASTEWATER
 DISCHARGE ORDINANCE, PLEASE CONTACT MR.
 RODNEY COMPO AT 822-2272 FOR SPECCIFIC
 AND REQUIREMENTS.
 2. SIDEWALK ALONG THE PROPERTY MUST BE
 RESOTRED IF BROKEN AND/OR INSTALLED IF
 REQUIRED.
 3.PLUMBING PLANS REFER TO CIVIL PLANS
 FOR CONTINUATION OF SERVICES, NO CIVIL
 PLANS ARE PROVIDED. NOTE THAT IF NEW
 CONNECTIONS TO THE CITY SERVICES THEN
 CIVIL PLANS SHOWING LOCATION FOR METERS
 AND BACKFLOWSAND AND THEIR SIZES MUST BE
 SUBMITTED TO THE PUBLIC UTILITIES AND
 ENGINEERING ATT; MANNY GONZALEZ AT
 494-1085.
 4. PER SANITATION DEPARTMENT ( GREGORY
 RODGERS 822-2075) ONLY A 2 C.Y. WITH
 CANSTERS FOR THE PROPOSED DUMPSTER CAN
 BE USED.
 5. PLEASE SHOW HOW THE PROPOSED PARKING
 WILL DRAINED. SHEET A-1
 6. NOTE THAT APPROACH TO THE SITE MUST
 BE CONSTRUCTED PER CITY OF WPB' STANDARD
 AND REQUIREMENTS. SEE ATTACHED
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-04-18 Cont ID  
Sent By mwennerg Date 2006-04-18 Time 14:03 Rev Time 0.00
Received By mwennerg Date 2006-04-18 Time 14:03 Sent To  
Notes
2006-04-18 00:00:00PLANS WERE PASSED AND STAMPED ON 1/3/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By mwennerg Date 2006-01-03 Time 15:42 Rev Time 0.00
Received By mwennerg Date 2006-01-03 Time 15:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-09-09 Cont ID  
Sent By mwennerg Date 2005-09-09 Time 10:16 Rev Time 0.00
Received By mwennerg Date 2005-09-09 Time 10:16 Sent To  
Notes
2005-09-09 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT FIRE RESPONSES
 REGARDING FIRE SPRINKLER COMMENTS REFER
 TO CIVIL DRAWINGS WHICH WERE NOT
 SUBMITTED WITH THIS PACKAGE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By mwennerg Date 2005-06-01 Time 12:59 Rev Time 0.00
Received By mwennerg Date 2005-06-01 Time 12:59 Sent To  
Notes
2005-06-01 00:00:00****DENIED****
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS.
  
 2) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, MONITORING OF THE FIRE
 ALARM SYSTEM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 3) PLEASE ILLUSTRATE THE OCCUPANCY
 CLASSIFICATION ON THE DRAWINGS.
  
 4) AN ADDRESS NUMBER IS REQUIRED ON THE
 BUILDING THAT IS A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 5) PLEASE SHOW THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION.
  
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATIONS FOR THE WALLS AND
 CEILINGS.
  
 7) IF THIS IS A NEW FIRE SPRINKLER
 INSTALLATION, PLEASE PROVIDE DETAILS FOR
 THE DOUBLE CHECK DETECTOR ASSEMBLY.
  
 8) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 9) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 BE WIRED INTO THE FIRE ALARM SYSTEM TO
 CAUSE A GENERAL FIRE ALARM, NOT A
 SUPERVISORY SIGNAL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-04-26 Cont ID  
Sent By jleech Date 2006-04-26 Time 14:00 Rev Time 0.00
Received By jleech Date 2006-04-26 Time 14:00 Sent To  
Notes
2006-04-26 00:00:00NO GAS;
  
 GENERATOR TO BE UNDER SEPARATE PERMIT.
 GENERATOR SPECS., ELECTRICAL PLAN AND
 GAS PLAN S ARE REQUIRED, AT TIME OF
 APPLICATION.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-21 Cont ID  
Sent By pschmitz Date 2006-01-21 Time 12:55 Rev Time 0.00
Received By pschmitz Date 2006-01-21 Time 12:55 Sent To  
Notes
2006-01-21 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 DENIED
  
 1.PREVIOUS REVIEW:
 PLAN REVIEW COMMENTS SHALL BE RESPONDED
 TO BY THE DESIGN PROFESSIONALS. REFERING
 TO EACH OTHER OR CONTRACTOR, IS NOT
 HELPFUL IN EXPEDITING YOUR PERMIT.
 SHT P-2 NOTES
 SUBMIT MANFACTURE DATA SHEETS FOR
 GENERATOR TO VERIFY CODE COMPLIANCE.
 SEE PLUMBING REVIEW COMMENTS
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-28 Cont ID  
Sent By adarroug Date 2006-04-28 Time 11:40 Rev Time 0.00
Received By adarroug Date 2006-04-28 Time 11:40 Sent To B
Notes
2006-04-28 00:00:00TO "JWITMER" DESK/BACK FROM INPACT FEES

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-03-08 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-03-08 Time 15:19 Sent To  
Notes
2006-04-03 00:00:00TO "COMM" BD#48
2006-03-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 15:29 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 15:29 Sent To  
Notes
2005-12-30 00:00:00TO "COMM" BD#61
2005-12-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 10:24 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 10:24 Sent To  
Notes
2005-08-15 00:00:00TO "COMM" BD#15
2005-08-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-06-27 Time 10:23 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 09:44 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#12
2005-05-10 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By pkrauss Date 2005-08-30 Time 07:01 Rev Time 0.55
Received By pkrauss Date 2005-08-30 Time 07:01 Sent To  
Notes
2005-08-30 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR THE GAS
 GENERATOR INDICATED ON PLAN SHEET P-1 &
 P-2. PLEASE NOTE, THE GENERATOR
 EXHAUST SHALL TERMINATE A MINIMUM OF 10
 FT FROM ANY FRESH AIR INTAKE, WINDOW OR
 DOOR.SITE PLAN DOES NOT INDICATE
 LOCATION OF THE GENERATOR, PROTECTION
 FROM DAMAGE MAY BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 16:51 Rev Time 1.55
Received By pkrauss Date 2005-06-23 Time 16:38 Sent To  
Notes
2005-06-23 00:00:00DENIED:
 1.PLAN SHEET AC-1 DUCT PENTRATING WALL
 BETWEEN THE STORAGE ROOM AND CLASS ROOM
 #6 INDICATES A FIRE DAMPER.ACCORDING
 TO PLAN SHEET A-2 THE FIRE DAMPER SHOULD
 BE LOCATED BETWEEN THE CORRIDOR AND THE
 STORAGE ROOM, PLEASE CLARIFY.
  
 2.PROVIDE CURB DETAIL & TERMINATION
 LOCATION FOR EXHAUST FANS.PROVIDE
 DISTANCE FROM FRESH AIR INTAKES ON THE
 RTU'S.
  
 3.PROVIDE INFORMATION FOR EXHAUST DUCT
 TO THE DRYER LOCATED IN THE "HOUSEHOLD
 ROOM".INDICATE DUCT SIZE, MATERIAL,
 AND TERMINATION.PLEASE NOTE, PER 2001
 FBC(M) 504.6, MAKEUP AIR SHALL BE
 PROVIDED FOR INTALLATIONS THAT EXHAUST
 GREATER THAN 200 CFM.
  
 4.PLAN SHEET AC-1 INDICATES RETURN AIR
 IN THE LAUNDRY AREA.WILL THIS BE
 RECIRCULATED?
  
 5.PROVIDE SPECIFICATION ON THE DRYER.
  
 6.INDICATE WHAT KIND OF FOOD PREP WILL
 BE TAKING PLACE.PLAN SHEET A-2
 INDICATES HOT & COLD FOOD.PLEASE
 INDICATE ANY "COOKING" EQUIPMENT OR
 APPLIANCES.
  
 7.PLAN SHEET AC-1 INDICATES
 DISHWASHER, PLEASE PROVIDE SUBMITTAL
 DATA.WILL A HEAT HOOD BE REQUIRED?
  
 8.PROVIDE DETAIL FOR SECURING ROOF
 CURBS & EQUIPMENT.SHOW COMPLAINCE WITH
 2001 FBC 1606, FOR REQUIRED WIND LOADS.
  
 9.PLANS DO NOT INDICATE CONDENSATE
 LAYOUT, MATERIAL, AND TERMIANTION.
 TERMINATION SHALL COMPLY WITH 2001
 FBC(M)307.2.1.AND FBC 1503.4.4.
  
 10.PROVIDE ADDTIONAL INFORMATION FOR
 THE GENERATOR ON PLAN SHEET P-2.
 PROVIDE MANUFACTURER'S SUBMITTAL DATA.
  
 11.PLEASE INDCIATE ALL APPLIANCES THAT
 WILL UTILIZE THE GAS.PLEASE INDICATE
 NATURAL OR LP GAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-04-26 Cont ID  
Sent By jleech Date 2006-04-26 Time 14:09 Rev Time 0.00
Received By jleech Date 2006-04-26 Time 14:08 Sent To  
Notes
2006-04-26 00:00:00PLUMBING PLAN REVIEW ONLY NO GAS THIS
 PLAN.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-01-21 Cont ID  
Sent By pschmitz Date 2006-01-21 Time 13:05 Rev Time 0.00
Received By pschmitz Date 2006-01-21 Time 13:08 Sent To  
Notes
2006-01-21 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
  
 [email protected]
 FBC 2001
 DENIED
 1.PREVIOUS REVIEWS NOT ADDRESSED.
 DATED 8-28-05 AND 6-16-05
 THE FOLLOWING COMMENTS HAVE NOT BEEN
 ADDRESSED FOR THE THIRD TIME.
 FS 553.80(2)(B) DESIGN PROFESSIONAL
 DOUCMENTS.
 SEE ATTACHEDNOTICE.FOR ADDITIONAL FEE.
  
 PLAN REVIEW COMMENTS SHALL BE RESPONDED
 TO BY THE DESIGN PROFESSIONALS. REFERING
 TO EACH OTHER OR CONTRACTOR, IS NOT
 HELPFUL IN EXPEDITING YOUR PERMIT.
  
 2.SHT P-1 KITCHEN DETAIL,REFERENCE.
 SEE CIVIL ENGINEERING DRAWING FOR GREASE
 TRAP.
 GREASE INTERCEPTOR IF REQUIRED SHALL
 BE SIZED BY THE ENVIRONMENTAL COMPLIANCE
 MANAGER.WASTE ORD #2938-96 OR #3434.
 PLEASE CONTACT LYNN MASSON
 (561)822-2271, BY E-MAIL
 [email protected], OR FAX (561)822-22792
  
 3. SHT A-3 THE FOLLOWING INFORMATION FOR
 CHAPTER 11 SHALL BE SHOWN OR INDICATED
 ON THE PLANS:
 FOR URINAL: (SHT A-3 NOT ADDRESSED)
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR SHOWERS: SHT A-3
 E. 11-4.21.7 CURBS (SHALL BE NO HIGHER
 THAN 1/2")
 SEE GAS PLAN REVIEW COMMENTS
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-28 Cont ID  
Sent By pschmitz Date 2005-08-28 Time 06:18 Rev Time 0.00
Received By pschmitz Date 2005-08-28 Time 06:17 Sent To  
Notes
2005-08-28 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
  
 [email protected]
 FBC 2001
 DENIED
 1.PREVIOUS REVIEW:
 PLAN REVIEW COMMENTS SHALL BE RESPONDED
 TO BY THE DESIGN PROFESSIONALS. REFERING
 TO EACH OTHER OR CONTRACTOR, IS NOT
 HELPFUL IN EXPEDITING YOUR PERMIT.
 2. PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT DIVISION OF
 ENVIROMENTAL HEALTH FOR REVIEW PRIOR TO
 RESUBMITTING. EACH SET OF PLANS
 RESUBMITTED FOR REVIEW BY CITY WPB SHALL
 BE STAMPED BY HEALTH DEPT REVIEWER.
 SECTION 101.4.7.- FOOD SERVICE.
 3. GREASE INTERCEPTOR: IF REQUIRED SHALL
 BE SIZED BY THE ENVIRONMENTAL COMPLIANCE
 MANAGER.WASTE ORD #2938-96 OR #3434.
 PLEASE CONTACT LYNN MASSON
 (561)822-2271, BY E-MAIL
 [email protected], OR FAX (561)822-22792
 4. SHT A-3 THE FOLLOWING INFORMATION FOR
 CHAPTER 11 SHALL BE SHOWN OR INDICATED
 ON THE PLANS:
 FOR WATER CLOSETS: (SHT A-3 STALLS)
 GRAB BARS, IN STALLS, 42" SHALL BE ON
 THE LONG SIDE, 36" GRAB BARS ON SHORT
 SIDE.
 FOR URINAL: (SHT A-3 NOT ADDRESSED)
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR SHOWERS: SHT A-3
 E. 11-4.21.7 CURBS (SHALL BE NO HIGHER
 THAN 1/2")
 DRINKING FOUNTAIN:( YOUR COMMENT ABOUT
 YOUNG PEOPLE, AND THEIR AGE, DOES NOT
 EXEMPT YOU FROM COMPLING WITH, CH 11 FL
 ACCESSIBILITY CODE)
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE
 E. 11-4.1.3(10)(A) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. (IF THIS
 IS A SINGLE ELEVATION UNIT - NOT
 REQUIRED IF HIGH/LOW DRINKING FOUNTAIN).
 8. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
  
 5. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2. ( NO CIVIL PLANS WITH THIS
 SUBMITTAL)
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 10:11 Rev Time 4.50
Received By kstevens Date 2005-06-16 Time 10:11 Sent To  
Notes
2005-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT DIVISION OF
 ENVIROMENTAL HEALTH FOR REVIEW PRIOR TO
 RESUBMITTING. EACH SET OF PLANS
 RESUBMITTED FOR REVIEW BY CITY WPB SHALL
 BE STAMPED BY HEALTH DEPT REVIEWER.
 SECTION 101.4.7.
 2. THE GREASE INTERCEPTOR SHALL BE SIZED
 BY RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE MANAGER. CONTACT MR. COMPO
 (561) 822-2272, E-MAIL [email protected],
 OR FAX (561) 653-2692. SUBMIT THE
 DETERMINATION SHEET FROM MR. COMPO WITH
 PLANS WHEN RESUBMITTING. WASTE ORD.
 #2938-96.
 3. INDICATE IF THERE WILL BE COOKING OF
 MEALS AT THE KITCHEN FACILITY. WHAT TYPE
 OF MEALS WILL BE SERVED? SECTION
 104.2.1.
 4. INDICATE THE AGE OF THE STUDENTS AS
 THIS WILL AFFECT THE REQUIREMENTS OF THE
 SCHOOL. SECTION 104.2.1.
 5. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1003.1 & 403.1.
 INDICATE THE SQUARE FOOTAGE OF EACH
 OCCUPANCY.
 6. SHT A-2 BOYS BATHROOM, URINALS SHALL
 NOT BE SUBSTITUTED FOR MORE THAN 50% OF
 THE REQUIRED WATER CLOWETS. - DEPENDING
 ON THE RESPONSE TO COMMENT #5 ABOVE,
 THIS MAY OR MAY NOT APPLY.
 7. SHT A-3 THE FOLLOWING INFORMATION FOR
 CHAPTER 11 SHALL BE SHOWN OR INDICATED
 ON THE PLANS:
 FOR WATER CLOSETS:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT (SHOWS MAX 20")
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 FOR URINAL:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES (SHOW
 LENGTH & WIDTH)
 B. 11-4.21.3 SEAT (TO COMPLY WITH FIG.
 36 AND SHOW CONTROL LOCATION).
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNIT
 E. 11-4.21.7 CURBS
 DRINKING FOUNTAIN:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE
 E. 11-4.1.3(10)(A) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. (IF THIS
 IS A SINGLE ELEVATION UNIT - NOT
 REQUIRED IF HIGH/LOW DRINKING FOUNTAIN).
 8. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 9. SHT P-1 WATER RISER DIAGRAM. ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN IN SOME
 AREAS. PDI-WH 201.
 10. WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL IS REQUIRED, AND A
 VACUUM RELIEF VALVE IS REQUIRED FOR ALL
 BOTTOM FED WATER HEATERS. SECTIONS
 607.3.2. AND 504.2.
 11. THE FOLLOWING ARE GAS PERMIT
 APPLICTION REQUIREMENTS:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-27 Cont ID  
Sent By jlong Date 2005-06-27 Time 18:33 Rev Time 0.00
Received By jlong Date 2005-06-27 Time 18:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved