Plan Review Details - Permit 05050247
Plan Review Stops For Permit 05050247
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-05-24 Cont ID  
Sent By jhiggins Date 2005-05-24 Time 09:31 Rev Time 0.00
Received By jhiggins Date 2005-05-24 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-29 Cont ID  
Sent By shill Date 2005-07-27 Time 16:23 Rev Time 0.15
Received By spalmer Date 2005-07-29 Time 15:38 Sent To PC
Notes
2005-07-29 00:00:00OKAY TO PRINT PER JIM WITMER IMPACT FEE
 RECEIPT RECEIVED
2005-07-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE THE IMPACT FEE RECEIPT.
 PR05023379

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-20 Cont ID  
Sent By shill Date 2005-07-20 Time 13:22 Rev Time 2.00
Received By shill Date 2005-07-20 Time 11:20 Sent To E
Notes
2005-07-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE ALL FROM THE
 PREVIOUS REVIEW.
  
 1.)PROVIDE A COPY OF THE IMPACT FEE
 RECEIPT.
  
 2.)WINDOW C DOES NOT MEET EMERGENCY
 EGRESS REQUIREMENTS FBC1005.2.THE
 ARCHITECT HAS ADDED A NOTE "ADJUST
 SIZE".IT IS NOT ACCEPTABLE TO SPECIFY
 A WINDOW WHICH IS CLEARLY NOT CODE
 COMPLIANT AND ASK FOR THE CONTRACTOR TO
 ADJUST THE SIZE IN THE FIELD.THE PLANS
 ARE TO BE CODE COMPLIANT, AND THIS IS
 CONSIDERED A LIFE SAFETY ISSUE.PLEASE
 SPECIFY A COMPLIANT WINDOW.FEEL FREE
 TO CONTACT ME IF YOU NEED ASSISTANCE.
  
 3.)ADDITIONAL FEES DUE, SEE ATTACHED.
  
 4.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 5.)PLEASE PROVIDE PRODUCT APPROVALS
 FOR THE FOLLOWING:
  
 FRONT DOOR (IMPACT GLASS)
 SLIDIING GLASS DOOR
 LOUVERS
 ROOF (ILLEGIBLE)
  
 ANY PRODUCT APPROVALS NOT SUBMITTED
 CORRECTLY PRIOR TO PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS.
  
 6.)SEE ATTACHED FS553.80(2)(B).
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 20:29 Rev Time 2.00
Received By shill Date 2005-06-11 Time 20:29 Sent To PC
Notes
2005-06-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) PROVIDE A COPY OF THE IMPACT FEE
 RECEIPT.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-101.2.
  
 3.)THE SQUARE FOOTAGE ON THE ENERGY
 CALC DOESN'T MATCH THE PLAN.
  
 4.)WINDOW B IS REQUIRED TO BE SAFETY
 GLASS FBC2405.1.
  
 5.)WINDOW C DOES NOT MEET EMERGENCY
 EGRESS REQUIREMENTS (SINGLE HUNG 48"
 HIGH), FBC1005.2.
  
 6.)ADDITIONAL FEES DUE, SEE ATTACHED
 (VALUE ADJUSTMENT).
  
 7.)A MEANS OF ESCAPE IS TO BE
 PROVIDED, FBC1005.4.5.THE PLAN SHOWS A
 WOOD DOOR BUT THE PRODUCT APPROVALS
 SUBMITTED WERE FOR NON IMPACT GLAZED
 DOORS.
  
 8.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 9.)IN ADDITION TO THE PRODUCT APPROVAL
 FOR ITEM #7 ABOVE, PROVIDE PRODUCT
 APPROVALS FOR:
 SLIDING GLASS DOOR
 LOUVERS
 ROOF (ILLEGIBLE)
  
 NOTE THAT THE FLORIDA PRODUCT APPROVAL
 FOR THE ROOF IS FOR TWO DIFFERENT
 APPROVALS.PROVIDE THE SPECIFIC
 APPROVAL FOR THE GAF ROYAL SOVEREIGN.
 WWW.FLORIDABUILDING.ORG
  
 ANY PRODUCT APPROVALS NOT SUBMITTED
 PRIOR TO ISSUANCE WILL REQUIRE SEPARATE
 PERMITS FOR THOSE ITEMS.
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-21 Cont ID  
Sent By btrobaug Date 2005-07-21 Time 17:44 Rev Time 0.50
Received By btrobaug Date 2005-07-21 Time 17:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By btrobaug Date 2005-05-20 Time 15:11 Rev Time 0.50
Received By btrobaug Date 2005-05-20 Time 15:10 Sent To M
Notes
2005-05-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE OUTSIDE RECEPTACLES PER
 210.52(E).
  
 2} RECEPTACLES MUST BE ADDED IN THE
 KITCHEN PER 210.52(C)(1) SPACING.
  
 3} SEE RECEPTACLE SPACING IN ALL BUT THE
 LIVING ROOM, WILL NEED ADDED RECEPTACLES
 TO COMPLY WITH 210.52(A)(1)&(2).
  
 4} THE DINING ROOM MUST BE ON A SMALL
 APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 NOTE: THE PANEL IN THE LAUNDRY LOCATED
 BETWEEN THE SINK ABD THE WASHING MACHINE
 WOULD BE BETTER PLACED FOR FUTURE
 MAINTENANCE IF IT WERE ON THE OPPOSITE
 WALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-27 Cont ID  
Sent By adarroug Date 2005-07-27 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-07-27 Time 11:29 Sent To B
Notes
2005-07-27 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:28 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:28 Sent To B
Notes
2005-07-12 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 14:11 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 14:11 Sent To Z
Notes
2005-07-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-05-19 Time 12:27 Rev Time 0.00
Received By adarroug Date 2005-05-19 Time 12:27 Sent To E
Notes
2005-05-19 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-06 Cont ID  
Sent By mmclean Date 2005-06-11 Time 08:21 Rev Time 0.00
Received By shill Date 2005-05-06 Time 15:29 Sent To PC
Notes
2005-05-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-29 Cont ID  
Sent By hmoser Date 2005-05-29 Time 15:24 Rev Time 0.00
Received By hmoser Date 2005-05-29 Time 15:24 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By jleech Date 2005-07-25 Time 08:58 Rev Time 0.33
Received By jleech Date 2005-07-25 Time 08:57 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-01 Cont ID  
Sent By jleech Date 2005-06-01 Time 18:05 Rev Time 0.33
Received By jleech Date 2005-06-01 Time 18:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 18:32 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 18:32 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By mmclean Date 2005-05-17 Time 16:38 Rev Time 0.00
Received By mmclean Date 2005-05-17 Time 16:38 Sent To I
Notes
2005-05-18 00:00:00DENIED,
 1. TOO MUCH CONCRETE WITHIN THE FRONT
 SETBACK. (25FT). NEED TO REDUCE CONCRETE
 WALK OR DRIVEWAY.
  
 MUST HAVE 1000SQ FT OR 75% OF LANDSCAPE
 WITHIN THE 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720