Plan Review Stops For Permit 05050210 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-07-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-23 |
Time |
21:19 |
Rev Time |
1.50 |
Received By |
shill |
Date |
2005-07-23 |
Time |
20:39 |
Sent To |
M |
|
Notes |
2005-07-23 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)FROM PREVIOUS LIST, A-2.01, FLOOR | | PLAN, IT APPEARS THAT EXISTING | | NON-HABITABLE SPACE IS TO BE ENCLOSED. | | PALM BEACH COUNTY IMPACT FEE REVIEW | | REQUIRED, 561-233-5025. | | | | 3.)THE SHEETS WHICH CHANGED ARE NOT | | SEALED.DOCUMENTS SUBMITTED FOR PUBLIC | | RECORD ARE TO BE SIGNED SEALED ORIGINALS | | FAC61G15-23.002. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-06-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-06-06 |
Time |
17:48 |
Rev Time |
2.00 |
Received By |
shill |
Date |
2005-06-06 |
Time |
16:02 |
Sent To |
|
|
Notes |
2005-06-06 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED, FS713.13. | | | | 2.)GN-1, ACI-99 SHOULD BE -02, | | FBC3502.ALSO DIVISION 6 MAKES | | REFERENCE TO IBC; GOVERNING CODE IS FBC. | | PLEASE CHECK ALL REFERENCES. | | | | 3.)A-2.01, FLOOR PLAN, IT APPEARS THAT | | EXISTING NON-HABITABLE SPACE IS TO BE | | ENCLOSED.PLEASE CONTACT 233-5025 TO | | DETERMINE IF IMPACT FEES ARE DUE. | | | | 4.)ENERGY CALCS REQUIRED. | | | | 5.)PROVIDE INFORMATION AS TO HOW YOU | | DETERMINED THE OCCUPANT LOAD, SHEET CV, | | BUILDING CODE ANALYSIS.IT REFERS TO | | TABLE 1003.1. BUSINESS AREAS ARE PER 100 | | FEET (200 SHOWN). | | | | 6.)7-A4.01, THE EMPLOYEE LOUNGE SINK | | IS TO COMPLY WITH FBC11-4.24. | | | | WHEN RESUBMITTING, PLEASE REPLACE ONLY | | SHEETS WHICH HAVE BEEN REVISED AND | | SUBMIT OLD SHEETS SEPARATELY.A | | TRANSMITTAL LETTER EXPLAINING HOW EACH | | ITEM WAS ADDRESSED WILL EXPEDITE PLAN | | REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-07-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-07-05 |
Time |
13:51 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2005-07-05 |
Time |
13:51 |
Sent To |
|
|
Notes |
2005-07-05 00:00:00 | *** UNSAT **** | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | REVIEW. | | | | 1)NOTE: PLEASE SEE RESPONSE LTR MENTIONS | | SIZING OF GUTTER PROVIDED, HOWEVER | | PLEASE SEE ONLY 12X12 IS SHOWN , NO | | LENGTH WAS PORVIDED.? | | 366, | | | | 2)NOTE: PLEASE SUBMIT MANUFACTURE | | SPEC/CUT SHEETS FOR MTS. | | PLEASE SEE RESPONSE LTR MENTIONS A "MAIN | | BRKR ON GEN WILL BE THE DISCONNECTING | | MEANS AS PERMITTED IN 225.3.4B" PLEASE | | SEE 225.3.4B, THIS CODE DOES NOT SEEM TO | | APPLY. | | THE MTS WILL BE CONSIDERED THE DISC | | MEANS. THE BRKR ON A GEN IS NOT | | ACCEPTABLEAS THE MEANS OF DISC. | | PLEASE SEE 225.31-225.36.,110.27 ETC. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | ONLY REPLACE WITH NEW SHEETS INTO | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-05-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-05-18 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2005-05-18 |
Time |
14:46 |
Sent To |
I |
|
Notes |
2005-05-18 00:00:00 | *********** UNSAT ********** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | AIC RATINGS FOR PANELS ARE SHOWN, | | HOWEVER PLEASE INDICATE FOR MAIN AND | | MTS. | | | | 2)NOTE: PLEASE SHOW SIZE OF GUTTER TO BE | | INSTALLED PER 366 OF THE NEC. | | PLEASE SEE PLANS SHALL NOT CONTAIN | | REFERENCE TO CODES IN WHOLE OR IN PART | | FBC 104.2.1 | | | | 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | ATTACHMENT PER 250.50. | | PLEASE ALSO SEE THE CODE SHALL NOT BE | | REFERENCED IN WHOLE OR IN PART. | | FBC 104.2.1 | | | | 4)NOTE: PLEASE SEE 250.6,250.24, NO | | EQUIPMENT GROUNDING CONDUCTORS SHALL BE | | INSTALLED FROM METER TI THE FIRST MEANS | | OF DISCONNECT. PLEASE SEE RISE INDICATES | | AND EQUIP. GRND. | | | | 5)NOTE: PLEASE SEE RISER INDICATES | | "GENERATORS CABLES" FOR PORTABLE GEN. | | UNIT. PLEASE CLARIFY THESE CABLES AS | | SHOWN. WILL THEY BE CONNECTED INTO ATS? | | WILL THEY TERMINATE INTO AN ENCLOSURE | | OUTSIDE? ETC. OR WILL THESE CABLES BE | | INSTALLED IN FUTURE? IF SO PLEASE ADD | | NOTE THAT CABLES BE FUTURE AND NOT | | INSTALLED AT THIS TIME. | | | | 6)NOTE: PLEASE SUBMIT MANUFACTURE SPECS | | FOR MTS. | | PLEASE SEE MTS SHALL HAVE A MANUAL MEANS | | OF DISCONNECT LOCATED ON THE OUTSIDE OF | | THE MTS. | | | | 7)NOTE: PLEASE VERIFY BOTH PANELS A AND | | B SEEM TO INDICATE MCB'S . THIS IS ONLY | | A NOTE. IFMLO, PLEASE ADJUST PANEL | | INFORMATION. | | | | 8)NOTE: PLEASE SEE NO LOAD CALCULATIONS | | WERE SUBMITTED. ONLY CONNNECTED LOADS | | SHOWN. | | PLEASE INCLUDE/SHOW ALL CONTINUOUS LOADS | | AND LARGEST MOTOR LOADS AT 125%. | | 215.3,230.42 ETC. | | | | 9)NOTE: PLEASE SEE 225.31-225.36 FOR | | FEEDERS FROM GEN. | | PLEASE SEE GROUPING OF MAINS REQUIRED. | | | | 10)NOTE: PLEASE VERIFY REQUIRED SIGN | | CIRCUIT PER 600.5 | | | | PLEASE SEE ANY OTHER COMMENTS FROM OTHER | | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON | | ELECTRICAL PLANS. | | | | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED | | SHEETSAND ONLY INSERT NEW REVISED | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | STAMPING. | | PLEASE SUBMIT ONE SET OF OLD/VOIDED | | SHEETS FOR REFERENCE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2005-05-20 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2005-05-20 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2005-05-20 |
Time |
14:50 |
Sent To |
|
|
Notes |
2005-05-20 00:00:00 | SEPARATE SHOP DRAWINGS AND PERMIT IS | | REQUIRED FOR FIRE ALARM SYSTEM. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-07-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-23 |
Time |
21:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-07-23 |
Time |
21:25 |
Sent To |
M |
|
Notes |
2005-07-23 00:00:00 | NEW MECHANICAL SHEETS (ADDRESSED | | PROVISO); SENT TO HM DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-07-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-07-23 |
Time |
20:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-07-23 |
Time |
20:39 |
Sent To |
AD |
|
Notes |
2005-07-23 00:00:00 | TO SMH DESK, TAKEN OFF OF COMM BOARD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-06-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-27 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-06-27 |
Time |
11:00 |
Sent To |
|
|
Notes |
2005-07-01 00:00:00 | TO "COMM" BD#47 | 2005-06-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-06-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-06-16 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-05-05 |
Time |
08:07 |
Sent To |
|
|
Notes |
2005-05-20 00:00:00 | TO "COMM" BD#21 | 2005-05-09 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-07-25 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-07-25 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-07-25 |
Time |
07:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-06-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-06-16 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-06-16 |
Time |
12:10 |
Sent To |
|
|
Notes |
2005-06-16 00:00:00 | PASS PROVISO | | 1) A/C UNIT #1 PLEASE SHOW DUCT SIZE OF | | DUCT GOING OVER CONFERENCE ROOM FOR | | ROUGH INSPECTION. | | 2) IF EXISTING AIRHANDLERS ARE OVER 2000 | | CFM FAN SHUTDOWN WILL BE REQUIRED. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2005-07-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-07-22 |
Time |
10:06 |
Rev Time |
0.55 |
Received By |
kstevens |
Date |
2005-07-22 |
Time |
10:06 |
Sent To |
|
|
Notes |
2005-07-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | | | 1. THE FOLLOWING SHEETS HAVE NOT BEEN | | SEALED AS REQUIRED BY SECTION 104.2.2 | | AND FLORIDA STATUTES: | | CV, GN-1, A-2.01, AND A-4.01 | | 2. THE SIGNATURES OF THE NEW SHEETS DO | | NOT MATCH THE SIGNATURES OF THE SHEET | | SUBMITTED PREVIOUSLY. PLEASE SUBMIT A | | SIGNED, SEALED, DATED, NOTORIZED LETTER | | INDICATING THE LEGAL SIGNATURE OF THE | | ARCHITECT OF RECORD FOR OUR FILES. THE | | LETTER SHALL HAVE A TITLE BLOCK AS | | REQUIRED BY FAC 61G1-16.004 | | 3. FROM PREVIOUS REVIEW: | | 4. SHT P2.1 DOMESTIC WATER RISER. WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | IN THE CEILING AS SHOWN. PDI-WH 201. A | | WATER HAMMER ARRESTOR IS REQUIRED ON THE | | LINE TO THE DISH WASHER AND TO THE ICE | | MAKER IF SUPPLIED. SECTION 604.9. | | RESPONSE NOTED, BUT THE WATER HAMMER | | ARRESTOR SHALL BE LOCATED NEAR THE | | FIXTURE AND IF THE MANUF. REQUIRES | | ACCESS, AN ACCESS PANEL IS REQUIRED OR | | THE ARRESTOR CAN BE LOCATED UNDERNEATH | | THE SINK FOR ACCESS. SUBMIT MANUFACTURE | | INFORMATION ON THE TYPE AND MODEL OF THE | | WATER HAMMER ARRESTOR TO BE USED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-06-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-06-15 |
Time |
18:22 |
Rev Time |
0.78 |
Received By |
kstevens |
Date |
2005-06-15 |
Time |
18:22 |
Sent To |
|
|
Notes |
2005-06-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | 1. SHTS A-2.01 & A-2.3 PER SECTION | | 11-4.24.5 THE CLEAR FLOOR SPACE SHALL BE | | PROVIDED IN FRONT OF THE SINK TO ALLOW | | FORWARD APPROACH. THE CLEAR FLOOR SPACE | | SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH | | THE SINK. THE CABINET SHALL NOT HAVE | | DOORS IN THE CLEAR FLOOR SPACE. | | 2. SHT P0.1 WATER HEATER DETAIL. THERMAL | | EXPANSION CONTROL REQUIRED PER SECTION | | 607.3.2. | | 3. SHTS P0.1 & P2.1 DEMOLITION, IN THE | | INSTALLATION OR REMOVAL OF ANY PART OF | | THE DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | PROHIBITED. CLEANOUTS AND/OR FUTURE | | FIXTURES SHALL NOT BE CONSIDERED AS DEAD | | ENDS. SECTION 704.5. | | 4. SHT P2.1 DOMESTIC WATER RISER. WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | IN THE CEILING AS SHOWN. PDI-WH 201. - | | WATER HAMMER ARRESTOR IS REQUIRED ON THE | | LINE TO THE DISH WASHER AND TO THE ICE | | MAKER IF SUPPLIED. SECTION 604.9. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|