Plan Review Details - Permit 05050210
Plan Review Stops For Permit 05050210
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-23 Cont ID  
Sent By shill Date 2005-07-23 Time 21:19 Rev Time 1.50
Received By shill Date 2005-07-23 Time 20:39 Sent To M
Notes
2005-07-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)FROM PREVIOUS LIST, A-2.01, FLOOR
 PLAN, IT APPEARS THAT EXISTING
 NON-HABITABLE SPACE IS TO BE ENCLOSED.
 PALM BEACH COUNTY IMPACT FEE REVIEW
 REQUIRED, 561-233-5025.
  
 3.)THE SHEETS WHICH CHANGED ARE NOT
 SEALED.DOCUMENTS SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-06 Cont ID  
Sent By shill Date 2005-06-06 Time 17:48 Rev Time 2.00
Received By shill Date 2005-06-06 Time 16:02 Sent To  
Notes
2005-06-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)GN-1, ACI-99 SHOULD BE -02,
 FBC3502.ALSO DIVISION 6 MAKES
 REFERENCE TO IBC; GOVERNING CODE IS FBC.
 PLEASE CHECK ALL REFERENCES.
  
 3.)A-2.01, FLOOR PLAN, IT APPEARS THAT
 EXISTING NON-HABITABLE SPACE IS TO BE
 ENCLOSED.PLEASE CONTACT 233-5025 TO
 DETERMINE IF IMPACT FEES ARE DUE.
  
 4.)ENERGY CALCS REQUIRED.
  
 5.)PROVIDE INFORMATION AS TO HOW YOU
 DETERMINED THE OCCUPANT LOAD, SHEET CV,
 BUILDING CODE ANALYSIS.IT REFERS TO
 TABLE 1003.1. BUSINESS AREAS ARE PER 100
 FEET (200 SHOWN).
  
 6.)7-A4.01, THE EMPLOYEE LOUNGE SINK
 IS TO COMPLY WITH FBC11-4.24.
  
 WHEN RESUBMITTING, PLEASE REPLACE ONLY
 SHEETS WHICH HAVE BEEN REVISED AND
 SUBMIT OLD SHEETS SEPARATELY.A
 TRANSMITTAL LETTER EXPLAINING HOW EACH
 ITEM WAS ADDRESSED WILL EXPEDITE PLAN
 REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-05 Cont ID  
Sent By dpalmer Date 2005-07-05 Time 13:51 Rev Time 1.00
Received By dpalmer Date 2005-07-05 Time 13:51 Sent To  
Notes
2005-07-05 00:00:00*** UNSAT ****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 1)NOTE: PLEASE SEE RESPONSE LTR MENTIONS
 SIZING OF GUTTER PROVIDED, HOWEVER
 PLEASE SEE ONLY 12X12 IS SHOWN , NO
 LENGTH WAS PORVIDED.?
 366,
  
 2)NOTE: PLEASE SUBMIT MANUFACTURE
 SPEC/CUT SHEETS FOR MTS.
 PLEASE SEE RESPONSE LTR MENTIONS A "MAIN
 BRKR ON GEN WILL BE THE DISCONNECTING
 MEANS AS PERMITTED IN 225.3.4B" PLEASE
 SEE 225.3.4B, THIS CODE DOES NOT SEEM TO
 APPLY.
 THE MTS WILL BE CONSIDERED THE DISC
 MEANS. THE BRKR ON A GEN IS NOT
 ACCEPTABLEAS THE MEANS OF DISC.
 PLEASE SEE 225.31-225.36.,110.27 ETC.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY REPLACE WITH NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2005-05-18 Time 14:46 Sent To I
Notes
2005-05-18 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS FOR PANELS ARE SHOWN,
 HOWEVER PLEASE INDICATE FOR MAIN AND
 MTS.
  
 2)NOTE: PLEASE SHOW SIZE OF GUTTER TO BE
 INSTALLED PER 366 OF THE NEC.
 PLEASE SEE PLANS SHALL NOT CONTAIN
 REFERENCE TO CODES IN WHOLE OR IN PART
 FBC 104.2.1
  
 3)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 ATTACHMENT PER 250.50.
 PLEASE ALSO SEE THE CODE SHALL NOT BE
 REFERENCED IN WHOLE OR IN PART.
 FBC 104.2.1
  
 4)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING CONDUCTORS SHALL BE
 INSTALLED FROM METER TI THE FIRST MEANS
 OF DISCONNECT. PLEASE SEE RISE INDICATES
 AND EQUIP. GRND.
  
 5)NOTE: PLEASE SEE RISER INDICATES
 "GENERATORS CABLES" FOR PORTABLE GEN.
 UNIT. PLEASE CLARIFY THESE CABLES AS
 SHOWN. WILL THEY BE CONNECTED INTO ATS?
 WILL THEY TERMINATE INTO AN ENCLOSURE
 OUTSIDE? ETC. OR WILL THESE CABLES BE
 INSTALLED IN FUTURE? IF SO PLEASE ADD
 NOTE THAT CABLES BE FUTURE AND NOT
 INSTALLED AT THIS TIME.
  
 6)NOTE: PLEASE SUBMIT MANUFACTURE SPECS
 FOR MTS.
 PLEASE SEE MTS SHALL HAVE A MANUAL MEANS
 OF DISCONNECT LOCATED ON THE OUTSIDE OF
 THE MTS.
  
 7)NOTE: PLEASE VERIFY BOTH PANELS A AND
 B SEEM TO INDICATE MCB'S . THIS IS ONLY
 A NOTE. IFMLO, PLEASE ADJUST PANEL
 INFORMATION.
  
 8)NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED. ONLY CONNNECTED LOADS
 SHOWN.
 PLEASE INCLUDE/SHOW ALL CONTINUOUS LOADS
 AND LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
  
 9)NOTE: PLEASE SEE 225.31-225.36 FOR
 FEEDERS FROM GEN.
 PLEASE SEE GROUPING OF MAINS REQUIRED.
  
 10)NOTE: PLEASE VERIFY REQUIRED SIGN
 CIRCUIT PER 600.5
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETSAND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By mwennerg Date 2005-05-20 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2005-05-20 Time 14:50 Sent To  
Notes
2005-05-20 00:00:00SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED FOR FIRE ALARM SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-23 Cont ID  
Sent By shill Date 2005-07-23 Time 21:25 Rev Time 0.00
Received By shill Date 2005-07-23 Time 21:25 Sent To M
Notes
2005-07-23 00:00:00NEW MECHANICAL SHEETS (ADDRESSED
 PROVISO); SENT TO HM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-23 Cont ID  
Sent By shill Date 2005-07-23 Time 20:39 Rev Time 0.00
Received By shill Date 2005-07-23 Time 20:39 Sent To AD
Notes
2005-07-23 00:00:00TO SMH DESK, TAKEN OFF OF COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 11:00 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#47
2005-06-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-16 Time 15:48 Rev Time 0.00
Received By adarroug Date 2005-05-05 Time 08:07 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#21
2005-05-09 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-25 Cont ID  
Sent By hmoser Date 2005-07-25 Time 07:37 Rev Time 0.00
Received By hmoser Date 2005-07-25 Time 07:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-16 Cont ID  
Sent By dpalmer Date 2005-06-16 Time 12:53 Rev Time 0.00
Received By hmoser Date 2005-06-16 Time 12:10 Sent To  
Notes
2005-06-16 00:00:00PASS PROVISO
 1) A/C UNIT #1 PLEASE SHOW DUCT SIZE OF
 DUCT GOING OVER CONFERENCE ROOM FOR
 ROUGH INSPECTION.
 2) IF EXISTING AIRHANDLERS ARE OVER 2000
 CFM FAN SHUTDOWN WILL BE REQUIRED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-22 Cont ID  
Sent By kstevens Date 2005-07-22 Time 10:06 Rev Time 0.55
Received By kstevens Date 2005-07-22 Time 10:06 Sent To  
Notes
2005-07-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1. THE FOLLOWING SHEETS HAVE NOT BEEN
 SEALED AS REQUIRED BY SECTION 104.2.2
 AND FLORIDA STATUTES:
 CV, GN-1, A-2.01, AND A-4.01
 2. THE SIGNATURES OF THE NEW SHEETS DO
 NOT MATCH THE SIGNATURES OF THE SHEET
 SUBMITTED PREVIOUSLY. PLEASE SUBMIT A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE OF THE
 ARCHITECT OF RECORD FOR OUR FILES. THE
 LETTER SHALL HAVE A TITLE BLOCK AS
 REQUIRED BY FAC 61G1-16.004
 3. FROM PREVIOUS REVIEW:
 4. SHT P2.1 DOMESTIC WATER RISER. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. A
 WATER HAMMER ARRESTOR IS REQUIRED ON THE
 LINE TO THE DISH WASHER AND TO THE ICE
 MAKER IF SUPPLIED. SECTION 604.9.
 RESPONSE NOTED, BUT THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE AND IF THE MANUF. REQUIRES
 ACCESS, AN ACCESS PANEL IS REQUIRED OR
 THE ARRESTOR CAN BE LOCATED UNDERNEATH
 THE SINK FOR ACCESS. SUBMIT MANUFACTURE
 INFORMATION ON THE TYPE AND MODEL OF THE
 WATER HAMMER ARRESTOR TO BE USED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By kstevens Date 2005-06-15 Time 18:22 Rev Time 0.78
Received By kstevens Date 2005-06-15 Time 18:22 Sent To  
Notes
2005-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHTS A-2.01 & A-2.3 PER SECTION
 11-4.24.5 THE CLEAR FLOOR SPACE SHALL BE
 PROVIDED IN FRONT OF THE SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE
 SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. THE CABINET SHALL NOT HAVE
 DOORS IN THE CLEAR FLOOR SPACE.
 2. SHT P0.1 WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL REQUIRED PER SECTION
 607.3.2.
 3. SHTS P0.1 & P2.1 DEMOLITION, IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF
 THE DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. CLEANOUTS AND/OR FUTURE
 FIXTURES SHALL NOT BE CONSIDERED AS DEAD
 ENDS. SECTION 704.5.
 4. SHT P2.1 DOMESTIC WATER RISER. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. -
 WATER HAMMER ARRESTOR IS REQUIRED ON THE
 LINE TO THE DISH WASHER AND TO THE ICE
 MAKER IF SUPPLIED. SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]