Plan Review Details - Permit 05050054
Plan Review Stops For Permit 05050054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-27 Cont ID  
Sent By jwitmer Date 2005-07-27 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2005-07-27 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By lsmith Date 2005-06-07 Time 09:04 Rev Time 0.50
Received By lsmith Date 2005-06-07 Time 09:04 Sent To  
Notes
2005-06-07 00:00:00BUILDING PLAN REVIEW: FAILED
  
  
 1. SUBMIT A DRAWING SHOWING THE DETAILS
 FOR THE SLAB INCLUDING THE ANCHORING
 DETAILS FOR THE GENERATOR.
  
 ANY QUESTIONS PLEASE CALL;
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-27 Cont ID  
Sent By btrobaug Date 2005-09-27 Time 11:44 Rev Time 0.50
Received By btrobaug Date 2005-09-27 Time 11:10 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-22 Cont ID  
Sent By btrobaug Date 2005-06-22 Time 11:51 Rev Time 0.50
Received By btrobaug Date 2005-06-22 Time 11:50 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-24 Cont ID  
Sent By btrobaug Date 2005-05-24 Time 14:40 Rev Time 0.50
Received By btrobaug Date 2005-05-18 Time 17:20 Sent To M
Notes
2005-05-24 00:00:00 
 PLEASE SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND THE
 TRANSFER SWITCH.
  
 PLEASE DRAW A SITE PLAN TO SHOW WHERE
 THE 200 AMP DISCONNECT IS LOCATED.IS IT
 ON A BUILDING OR IN THE GENERATOR?
  
 THE LINE DRAWING DOES NOT SHOW HOW
 UTILITY POWER IS TRANSFERRED.
  
 PLEASE NOTE THAT DISCONNECTS MUST BE
 GROUPED PER 225.34.
  
 SEE 225.32 FOR DISCONNECTS AT THE GARAGE
 AND HOUSE.
  
 SEE 250.30 AND 250.32D FOR GROUNDING
 REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 15:53 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 15:53 Sent To E
Notes
2005-09-21 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 14:26 Sent To M
Notes
2005-07-11 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 11:40 Rev Time 0.00
Received By shill Date 2005-06-10 Time 11:40 Sent To E
Notes
2005-06-10 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 16:27 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 16:27 Sent To E
Notes
2005-05-13 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 17:30 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 17:30 Sent To Z
Notes
2005-05-03 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-20 Cont ID  
Sent By rregueir Date 2005-07-20 Time 17:30 Rev Time 0.00
Received By rregueir Date 2005-07-20 Time 17:30 Sent To B
Notes
2005-07-20 00:00:00----------------PROVISO-----------------
  
 GENERATOR EXHAUST TO TERMINATE MIN. 10'
 FROM OPENINGS INTO BUILDING STRUCTURE
 (DOORS,WINDOWS) PER FBC,M 403 AND IN
 COMPLIANCE WITH FBG,FG SEC 804.3
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-06-27 Cont ID  
Sent By hmoser Date 2005-06-27 Time 13:33 Rev Time 0.00
Received By hmoser Date 2005-06-27 Time 13:32 Sent To E
Notes
2005-06-27 00:00:00PLAN DENIED
 1) PLEASE INDICATE TYPE OF FUEL USED FOR
 GENERATOR.
 2) PLEASE PROVIDE A PLAN SHOWING WINDOWS
 AND LOCATION OF THE GENERATOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By pkrauss Date 2005-05-31 Time 16:33 Rev Time 0.30
Received By pkrauss Date 2005-05-31 Time 16:31 Sent To P
Notes
2005-05-31 00:00:00DENIED:
 1.PROVIDE MANUFACTURER SUBMITTAL DATA
 & INSTALLATION INSTRUCTIONS.
  
 2.INDICATE WHAT TYPE OF FUEL THIS WILL
 REQUIRE, (LP GAS, NATURAL GAS, DIESEL
 FUEL).
  
 3.PROVIDE DISTANCES TO STRUCTURE,
 WINDOWS, DOORS, FRESH AIR INTAKES.
  
 ADDTIONAL PERMITS MAY BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-06-03 Cont ID  
Sent By kstevens Date 2005-06-03 Time 18:24 Rev Time 0.25
Received By kstevens Date 2005-06-03 Time 18:23 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-12 Cont ID  
Sent By mmclean Date 2005-05-12 Time 11:14 Rev Time 0.00
Received By mmclean Date 2005-05-12 Time 11:14 Sent To I
Notes
***NONE***