Plan Review Details - Permit 05042008
Plan Review Stops For Permit 05042008
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-11 Cont ID  
Sent By shill Date 2005-07-11 Time 12:44 Rev Time 0.00
Received By shill Date 2005-07-11 Time 12:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-22 Cont ID  
Sent By shill Date 2005-06-22 Time 15:59 Rev Time 0.50
Received By shill Date 2005-06-22 Time 15:59 Sent To PC
Notes
2005-06-22 00:00:00****PLAN CHECK ONLY****
  
 PLANS CODE COMPLIANT - PLEASE APPLY FOR
 PERMIT
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-06-01 Cont ID  
Sent By shill Date 2005-06-01 Time 16:57 Rev Time 0.50
Received By shill Date 2005-06-01 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-29 Cont ID  
Sent By btrobaug Date 2005-11-29 Time 13:56 Rev Time 0.50
Received By btrobaug Date 2005-11-29 Time 13:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 17:22 Rev Time 0.25
Received By dpalmer Date 2005-06-15 Time 17:21 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 15:04 Rev Time 0.25
Received By dpalmer Date 2005-05-09 Time 15:03 Sent To  
Notes
2005-05-09 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE PLANS HAVE BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND NOT
 FOR PERMIT.
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/ GFI
 PROTECTED. 210.8A6
  
 3)NOTE: PLEASE NOTE CIRCUITING FOR NEW
 ELECTRICAL SHOWN. THIS MAY BE NOTED TO
 EXISTING CIRCUITS.
 PLEASE INCLUDE NOTE FOR NEW KITCHEN
 RECEPTS TO BE ON EITHER NEW OR EXISTING
 SMALL APPL CIRCUIT, #12 20A.
 210.11C1, 220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-16 Cont ID  
Sent By mwennerg Date 2005-06-16 Time 13:19 Rev Time 0.00
Received By mwennerg Date 2005-06-16 Time 13:14 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-27 Cont ID  
Sent By mwennerg Date 2005-05-27 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2005-05-18 Time 10:40 Sent To  
Notes
2005-05-27 00:00:00****DENIED****
  
 1) PLEASE BE ADVISED THAT THESE PLANS
 HAVE BEEN SUBMITTED FOR PLAN REVIEW
 ONLY.
  
 2) PLEASE SHOW THE LOCATIONS OF NEW OR
 EXISTING SMOKE DETECTORS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
 4) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 10:08 Rev Time 0.00
Received By shill Date 2005-06-08 Time 10:08 Sent To E
Notes
2005-06-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-05 Cont ID  
Sent By adarroug Date 2005-04-27 Time 11:54 Rev Time 0.00
Received By adarroug Date 2005-04-27 Time 17:01 Sent To  
Notes
2005-05-05 00:00:005/5/05-TO "COMM" BD#50
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-03 Cont ID  
Sent By kstevens Date 2005-06-03 Time 10:48 Rev Time 0.25
Received By kstevens Date 2005-06-03 Time 10:48 Sent To  
Notes
2005-06-03 00:00:00FIXTURE REPLACEMENT IN SAME LOCATION -
 NO RISERS REQUIRED. PLUMBING PERMIT
 REQUIRED